Tequipment
An InterWorld Highway, LLC Company
Call Us 1.877.571.7901
Fluke Accessoires
 
 
 
 
 
Top Categories >

Fluke 1760 TR Basic Three Phase Power Quality Recorder Topas

 
Our Customers get the best price
Free In Person Demo
Fluke 1760TR BASIC
Catalog #: 2637629
         
0 reviews
POWER QUALITY RECORDER W/TRANS - TOPAS,W/O V OR I PROBES

Features

  • 2 GB data memory: Enables detailed, simultaneous recording of numerous power parameters for long periods of time
  • Plug and play: Allows quick setup with automatic sensor detection; sensors are instrument powered, eliminating the need for batteries
  • 10 MHz, 6000 Vpk waveform capture: Get a detailed picture of even the shortest event
  • Fully Class-A compliant: Conduct tests according to the stringent international IEC 61000-4-30 Class-A standard
  • GPS time synchronization: Correlate data with events or datasets from other instruments with precision
  • Flexible and fully configurable thresholds and scale factors: Allows user to pinpoint specific issues by defining the detailed criteria for detection and recording of disturbances.
  • Uninterrupted power supply (40 minutes): Never miss important events - even record the beginning and end of interruptions and outages to help determine the cause
  • Rugged field design: Insulated housing and a solid state design with no rotating components enable reliable testing under nearly any conditions
  • Comprehensive software included: Provides trend diagrams for root cause analysis, statistical summaries, report writing and real-time data monitoring in the online mode
Loading Prices
Sale: $23,999.99
  + Free shipping over $74

Marketing-Promo-Add-to-Cart-176x92-3-items

Questions?
Ask Our Factory
Trained Engineers
M-F 8AM - 9PM EST
• 877.571.7901

Compare Products in this Series

Product Name Type (Power Quality) Maximum Voltage AC Maximum Voltage DC Availability Price
1760TR BASIC
1760TR BASIC
POWER QUALITY RECORDER W/TRANS - TOPAS,W/O V OR I PROBES
3 Phase 1000 V 1000 V
1760 BASIC
1760 BASIC
POWER QUALITY RECORDER-TOPAS,W/O V OR I PROBES,NO TRANS
3 Phase 1000 V 1000 V
1760 US
1760 US
POWER QUALITY RECORDER - TOPAS,CONFIGURED US/CAN RANGE,NO TRANS
3 Phase 1000 V 1000 V
1760 TR US
1760 TR US
POWER QUALITY RECORDER W/TRANS-TOPAS,CONFIGURED US/CAN RANGE
3 Phase 1000 V 1000 V
Fluke 1760 TR Basic Three Phase Power Quality Recorder Topas

Fluke 1760 Power Quality Recorder TR Basic Three Phase Topas

         
0 reviews
  Add to cart

Product Information

Class-A compliance for the most demanding power quality tests

The Fluke 1760 Three-Phase Power Quality Recorder is fully compliant to IEC 61000-4-30 Class-A, for advanced power quality analysis and consistent compliance testing. Designed for analysis of utility and industrial power distribution systems, in medium- and low-voltage networks, this power quality monitor provides the flexibility to customize thresholds, algorithms, and measurement selections. The 1760 power recorder captures the most comprehensive details on user-selected parameters.

Applications

  • Detailed disturbance analysis - Perform high-speed transient analysis and uncover root cause of equipment malfunction for later mitigation and predictive maintenance. The fast transient option, with its 6000 V measurement range, allows capture of very short impulses such as lightning strikes.
  • Class-A quality-of-service compliance - Validate incoming power quality at the service entrance. Thanks to Class A compliance, the Fluke 1760 allows undisputable verification.
  • Event correlation at multiple locations - Utilizing GPS time synchronization, users can quickly detect where a fault occurred first, either inside or outside the facility.
  • Galvanic separation and DC coupling - Allows complete measurements on dissimilar power systems. For example troubleshoot UPS systems by simultaneously recording the battery voltage and power output
  • Power quality and power load studies - Assess baseline power quality to validate compatibility with critical systems before installation and verify electrical system capacity before adding loads.

  There are four Fluke 1760 models to select from:
 

Product Feature Fluke 1760 Basic Fluke 1760TR Basic Fluke 1760 Fluke 1760TR
Power quality statistics according to EN50160
Voltage event list (dips, swells and interruptions)
Continuous recording of:
Voltage
Current
Power P, Q, S
Power factor
kWh
Flicker
Unbalance
Frequency
Voltage and current harmonics to the 50th / Interharmonics
THD
Mains signaling
Triggered recordings
Online mode (Oscilloscope, transients and events)
Fast transient analysis up to 10 MHz    
4, 600V voltage probes    
4 dual-range flexible current probes (1000 A / 200 A ac)    
GPS time sync receiver    
Memory 2 GB Flash memory

What's In The Box

  • Internal Flash-memory 2 GB
  • PQ Analyze software on CD-ROM
  • Ethernet cable for network connection (1)
  • Crosslink Ethernet cable for direct PC connection (1)
  • Mains cable (1)
  • Operational manuals
  • Carrying bag
  • Fast transient analysis up to 10 MHz

Specifications

Technical Data
Overview of Measurement Functions
Statistical Evaluation Power quality statistics according to EN50160 and DISDIP tables like ITIC, CEBEMA, ANSI
Continuous Recording Fluke 1760 records rms values together with corresponding minimum and maximum values for:
  • Voltage
  • Current
  • Power P, Q, S
  • Power Factor
  • kWh
  • Flicker
  • Unbalance
  • Frequency
  • Harmonics/Interharmonics

continuously with the following time aggregations:
Day
10 min
Free Interval, e.g.: 15 min, 2h

Triggered Recordings rms: Aggregation time is adjustable between 10 ms (1/2 cycle), 20ms (1 cycle), 200ms (10/12 cycles) or 3 sec (150/180 cycles).
Calculating rms values, Harmonics and Interharmonics is performed synchronous to the power frequency. Basic aggregation for harmonics and interharmonics is 200ms
Oscilloscope: Sample rate is 10.24 kHz for all 8 channels
Fast Transients: Sample rate is selectable from 100 kHz to 10 MHz for channel 1-4 FFT of Fast Transients
Mains Signalling Phases and N-conductor, Voltage and current
Online Mode Variable refresh rate. This feature allows verification of instrument set up and delivers a quick overview of oscilloscope, transients and events.
General Data
Intrinsic uncertainty refers to reference conditions and is guaranteed for two years
Quality system developed, manufactured as per ISO 9001: 2000
Environment conditions
Operating temperature range: 0 °C to +50 °C; 32 °F to +122 °F
Working temperature range: -20 °C to +50 °C; -4 °F to +122 °F
Storage temperature range: 20 °C to +60 °C; -4 °F to 140 °F
Reference temperature: 23 °C ± 2 K; 74 °F ± 2 K
Climatic class: B2 (IEC 654-1), -20 °C to +50 °C; -4 °F to +122 °F
Max. operating altitude: 2000 m: max. 600 V CAT IV*, power supply: 300 V CAT
2000 m: max. 600 V CAT IV*, power supply: 300 V CAT III 5000 m: max 600 V CAT III*, power supply: 300 V CAT II
* depending on sensor
Reference conditions
Environment temperature: 23 °C ± 2 K ; 74°F ± 2 K
Power supply: 230 V ± 10 %
Power frequency: 50 Hz / 60 Hz
Signal: declared input voltage Udin
Averaging: 10 minute intervals
Housing insulated, robust plastics housing
EMC
Emission: Class-A as per IEC/EN 61326-1
Immunity: IEC/EN 61326-1
Power supply
Range: AC: 83 V to 264 V, 45 to 65 Hz
DC: 100 V to 375 V
Safety: IEC/EN 61010-1 2nd edition
300 V CAT III
Power consumption: max. 54VA
Battery pack: NIMH, 7.2 V, 2.7 Ah
In case of a power supply failure an internal battery maintains the supply for up to 40 minutes. Afterwards, or in case of discharged accumulators the Fluke 1760 is turned off and continues the measurements with the latest settings as soon as the supply voltage returns. The battery can be replaced by the user.
Display
  Fluke 1760 features LED indicators for the status of the 8 channels, phase sequence, power supply (mains or accumulator), memory usage, time synchronization, and data transfer.
Power LED: • Permanent light: normal power supply from mains.
• OFF: supply via internal accumulator in case of a power failure.
Channel LEDs 3-color LEDs per channel for:
• overload condition
• under load condition
signal level in nominal range
Data memory 2 GB Flash memory depending on model
Memory model Linear
Interfaces Ethernet (100MB/s), compatible to Windows® 98/ME/NT/2000/XP RS 232, external modem via RS 232
Baud rate for RS 232 9600 Baud to 115 kBaud
Dimensions 325 mm x 300 m x 65 mm; 2.8 x 11.8 x 2.6 in. (H x W x D)
Weight appr. 4.9 kg; 10.8 lbs. (without accessories)
Warranty 2 years
Calibration interval 1 year recommended for Class-A, otherwise 2 years
Signal Conditioning
Range for 50 Hz systems 50 Hz ± 15 % (42.5 Hz to 57.5 Hz)
Range for 60 Hz systems 60 Hz ± 15 % (51 Hz to 69 Hz)
Resolution 16 ppm
Sampling frequency for 50 Hz power frequency 10.24 kHz, The sampling rate is synchronized to mains frequency.
Uncertainty for frequency measurements < 20 ppm
Uncertainty of internal clock < 1s / day
Measurement intervals
  Aggregation of the interval values as per IEC 61000-4-30 Class-A
Min-, Max-values: Half cycle, e.g.: 10 ms rms values at 50Hz
Transients: Sample rate 100 kHz to 10 MHz per channel
Harmonics as per IEC 61000-4-7:2002: 200 ms
Flicker as per EN 61000-4-15:2003: 10 min (Pst), 2 h (Plt)
Measurement Inputs
Number of inputs 8 galvanically isolated inputs for voltage and current measurements.
Sensor safety up to 600 V CAT IV depending on sensor
Basic safety 300 V CAT III
Nominal voltage (rms) 100 mV
Range (peak value) 280 mV
Overload capacity (rms) 1000 V, continuously
Voltage rise rate max. 15 kV / µs
Input resistance 1 MΩ
Input capacitance 5 pF
Input filter Each channel is equipped with a passive low-pass filter, an anti-aliasing filter and a 16-bit A/D converter. All channels are sampled synchronously with a common quartz-controlled clock pulse.
The filters protect against voltage transients and limit the signal rise rate, reduce high frequency components and especially the noise voltage above half the sampling rate of the A/D converter by 80 dB, thus achieving very small measuring errors in an exceptionally large amplitude range. This is also valid under extreme operating conditions like transient voltages at the output of converters.
Uncertainties
Uncertainty at reference conditions
  Uncertainty including the voltage sensors is in compliance with IEC 61000-4-30 Class-A. All voltage sensors are suitable for DC up to 5 kHz
With Sensor 1000 V 0,1% at Udin = 480 V and 600 V P-N
Sensor 600 V 0,1% at Udin = 230 V P-N
Intrinsic uncertainty for harmonics Class I as per EN 61000-4-7:2002
Reference conditions 23 ° ± 2 K < 60 % rH; 74 °F ± 2 K < 60 % rH
Warmed up instrument > 3h
Power supply: 100 V to 250 V ac
Temperature drift 100 ppm / K
Aging < 0.05 % / year
Common mode rejection > 100 dB at 50 Hz
Temperature drift Change of amplification through temperature: < 0.005 %/K
Aging Change of amplification due to ageing: < 0.04 %/year
Noise Noise voltage, input short-circuited: < 40 µV
DC ± (0.2% rdg + 0.1% sensor)

Fluke 1760TR BASIC Product Specifications Summary:
(for full specs please see the full specs tab or the data sheet)

Power Measurement/Power Quality Analyzer Template

Type (Power Quality) What's This?3 Phase
Maximum Voltage AC1000 V
Maximum Voltage DC1000 V
True Power / Work ( W) What's This?Yes
Apparent Power (VA) What's This?Yes
Reactive Power (VAR) What's This?Yes
Measurement Frequency (Power Quality)50 Hz, 60 Hz
Display (Power Quality)Digital
AlarmsYes
Transient Capture What's This?Yes 
Displays Waveform What's This?Yes
Energy What's This?Yes
Phasor Diagrams What's This?No
Power Factor (Power Quality) What's This?Yes
Harmonics What's This?Yes
Maximum Harmonics Range200 
Current Clamps IncludedNo
Class A Compliant What's This?Yes
Crest FactorYes 
CAT Rating What's This?IV

Test Equipment General Attributes

Country of OriginGermany
Other Information

Statistical Evaluation: Power quality statistics according to EN50160 and DISDIP tables like ITIC, CEBEMA, ANSI

Continuous Recording: Fluke 1760 records rms values together with corresponding minimum and maximum values for:

  • Voltage
  • Current
  • Power P, Q, S
  • Power Factor
  • kWh
  • Flicker
  • Unbalance
  • Frequency
  • Harmonics/Interharmonics

continuously with the following time aggregations:
Day
10 min
Free Interval, e.g.: 15 min, 2h

Triggered Recordings: rms: Aggregation time is adjustable between 10 ms (1/2 cycle), 20ms (1 cycle), 200ms (10/12 cycles) or 3 sec (150/180 cycles).
Calculating rms values, Harmonics and Interharmonics is performed synchronous to the power frequency. Basic aggregation for harmonics and interharmonics is 200ms
Oscilloscope: Sample rate is 10.24 kHz for all 8 channels
Fast Transients: Sample rate is selectable from 100 kHz to 10 MHz for channel 1-4 FFT of Fast Transients

Mains Signalling: Phases and N-conductor, Voltage and current

Online Mode: Variable refresh rate. This feature allows verification of instrument set up and delivers a quick overview of oscilloscope, transients and events.

Intrinsic uncertainty: refers to reference conditions and is guaranteed for two years

Quality system: developed, manufactured as per ISO 9001: 2000

Operating temperature range:: 0 ?C to +50 ?C; 32 ?F to +122 ?F

Working temperature range:: -20 ?C to +50 ?C; -4 ?F to +122 ?F

Storage temperature range:: 20 ?C to +60 ?C; -4 ?F to 140 ?F

Reference temperature:: 23 ?C ? 2 K; 74 ?F ? 2 K

Climatic class:: B2 (IEC 654-1), -20 ?C to +50 ?C; -4 ?F to +122 ?F

Max. operating altitude:: 2000 m: max. 600 V CAT IV*, power supply: 300 V CAT
2000 m: max. 600 V CAT IV*, power supply: 300 V CAT III 5000 m: max 600 V CAT III*, power supply: 300 V CAT II
* depending on sensor

Environment temperature:: 23 ?C ? 2 K ; 74?F ? 2 K

Power supply:: 230 V ? 10 %

Power frequency:: 50 Hz / 60 Hz

Signal:: declared input voltage Udin

Averaging:: 10 minute intervals

Housing: insulated, robust plastics housing

Emission:: Class-A as per IEC/EN 61326-1

Immunity:: IEC/EN 61326-1

Range:: AC: 83 V to 264 V, 45 to 65 Hz
DC: 100 V to 375 V

Safety:: IEC/EN 61010-1 2nd edition
300 V CAT III

Power consumption:: max. 54VA

Battery pack:: NIMH, 7.2 V, 2.7 Ah
In case of a power supply failure an internal battery maintains the supply for up to 40 minutes. Afterwards, or in case of discharged accumulators the Fluke 1760 is turned off and continues the measurements with the latest settings as soon as the supply voltage returns. The battery can be replaced by the user.

 : Fluke 1760 features LED indicators for the status of the 8 channels, phase sequence, power supply (mains or accumulator), memory usage, time synchronization, and data transfer.

Power LED:: ? Permanent light: normal power supply from mains.
? OFF: supply via internal accumulator in case of a power failure.

Channel LEDs: 3-color LEDs per channel for:
? overload condition
? under load condition
signal level in nominal range

Data memory: 2 GB Flash memory depending on model

Memory model: Linear

Interfaces: Ethernet (100MB/s), compatible to Windows? 98/ME/NT/2000/XP RS 232, external modem via RS 232

Baud rate for RS 232: 9600 Baud to 115 kBaud

Dimensions: 325 mm x 300 m x 65 mm; 2.8 x 11.8 x 2.6 in. (H x W x D)

Weight: appr. 4.9 kg; 10.8 lbs. (without accessories)

Warranty: 2 years

Calibration interval: 1 year recommended for Class-A, otherwise 2 years

Range for 50 Hz systems: 50 Hz ? 15 % (42.5 Hz to 57.5 Hz)

Range for 60 Hz systems: 60 Hz ? 15 % (51 Hz to 69 Hz)

Resolution: 16 ppm

Sampling frequency for 50 Hz power frequency: 10.24 kHz, The sampling rate is synchronized to mains frequency.

Uncertainty for frequency measurements: 20 ppm

Uncertainty of internal clock: 1s / day

 : Aggregation of the interval values as per IEC 61000-4-30 Class-A

Min-, Max-values:: Half cycle, e.g.: 10 ms rms values at 50Hz

Transients:: Sample rate 100 kHz to 10 MHz per channel

Harmonics: as per IEC 61000-4-7:2002: 200 ms

Flicker: as per EN 61000-4-15:2003: 10 min (Pst), 2 h (Plt)

Number of inputs: 8 galvanically isolated inputs for voltage and current measurements.

Sensor safety: up to 600 V CAT IV depending on sensor

Basic safety: 300 V CAT III

Nominal voltage (rms): 100 mV

Range (peak value): 280 mV

Overload capacity (rms): 1000 V, continuously

Voltage rise rate: max. 15 kV / ?s

Input resistance: 1 MO

Input capacitance: 5 pF

Input filter: Each channel is equipped with a passive low-pass filter, an anti-aliasing filter and a 16-bit A/D converter. All channels are sampled synchronously with a common quartz-controlled clock pulse.
The filters protect against voltage transients and limit the signal rise rate, reduce high frequency components and especially the noise voltage above half the sampling rate of the A/D converter by 80 dB, thus achieving very small measuring errors in an exceptionally large amplitude range. This is also valid under extreme operating conditions like transient voltages at the output of converters.

Reviews

Accessories

Loading Accessories

Reviews

Fluke 1760TR BASIC Customer Reviews

0 Reviews
5 stars
 (0)
4 stars
 (0)
3 stars
 (0)
2 stars
 (0)
1 star
 (0)
 
 
 
 
 
Average Customer Review
         
0 reviews
0 customer reviews
Share your thoughts with other customers
Create your own review
No reviews found to display for this rating.

Fluke Price List

Hioki Clampon HiTester
X


secured website

Interworld Highway, LLC dba TEquipment.NET

205 Westwood Avenue. Long Branch, NJ 07740

Privacy Policy | Terms and Conditions | Site Map

Copyright© 2016 Interworld Highway, LLC

secured website
We Price Match!

Give our sales team a call at 877.571.7901 (Toll Free) or 732.222.7077 (International) and we'll match any competitor's price.

X