TPI 712 Combustion Analyzer

Click image to enlarge
TPI 712
|
Features:
- Easy to use
- Large, easy-to-read display
- Data log up to ten sets; timed logging 400 sets
- PC interface
- IR printer port
- Protective rubber boot included
|
Functions:
- Combustion Efficiency Analyzer
- Measure O2 and CO
- Calculate CO2, efficiency, excess air and ratio.
- Will work with high efficiency furnaces, hot water heaters, and other combustible gas appliances.
- Combustible Gas Detector
- Set at 100 ppm sensitivity for natural gas
- CO Analyzer
- Differential Thermometer
- Dual input K-Type thermocouple temperature tester
- Differential Digital Manometer
- Dual input differential manometer with 3 selectable units of measure: kPa, mBar, inH2O.
|
| Model |
Description |
List Price |
Sale Price |
| 712 |
Combustion Analyzer w/pump, soft case, stack probe, O2, CO, Temp,pressure |
$849.95 |
| $764.96 |  |
|
| 712A740 |
712 Combustion Analyzer and A740 |
$949.95 |
| $854.96 |  |
|
| Model |
Accessories |
List Price |
Sale Price |
| A767 |
IRDA adapter for 712 and 714 |
$74.95 |
| $67.46 |  |
|
| A772 |
PC Software |
$69.95 |
| $62.96 |  |
|
| A740 |
IR printer |
$199.95 |
| $179.96 |  |
|
Specifications
| Temperature Measurement |
Range: -40° to 1472°F, or -40° to 800°C
Resolution: 1°F or C
Accuracy (K-type): ±0.3%, ±2°F or ±1°C
|
| Draft/Pressure Measurement |
Selectable Ranges: mBar, kPa, and inH2O
Ranges: -150 mBar to +150 mBar, -15 kPa to +15 kPa, -60 inH2O to +60 inH2O
Resolution: 0.01mBar
Accuracy: ±0/5% fsd
|
| Gross/Net Efficiency |
Range: 0 to 100%
Resolution: 0.1%
|
| Oxygen (O2) Measurement |
Range: 0 to 25%
Resolution:0.1%
Accuracy:±0.3%
|
| Carbon Monoxide (CO) Measurement |
Range: 0 to 10,000 ppm
Resolution: 1 ppm
Accuracy: ±5 ppm or 5%, whichever is greater
|
| Carbon Dioxide (CO2) |
Range: 0 to 25%
Resolution: 0.1%
Accuracy: Calculated
|
| CO/CO2 Ratio |
Range: 0 to 0.999
Resolution: 0.001
Accuracy: Calculated
|
| General |
Operating Temperature Range: 14° to 122°F (-10° to 50°C)
Battery: Rechargeable Ni-MH, >6 Hour Life
Charger Input Voltage: 115V or 230V : 50/60 Hz AC
Fuels: Natural Gas, LPG, Light Oil, Heavy Oil
Display: Backlit LCD
Data Storage: 10 sets of readings
Data Logging: 400 sets of readings on ‘Timed Interval Logging’
Time & Date: 24 Hour Real Time Clock
Dimensions: 200mm x 90mm x 60mm
Weight: 500g
Exhaust: Safety Spigot
Conforms To: BS7927 (and the draft BS7967)
|
|