Phenix Technologies HC2 Portable High Current Test Set (2000A max output)

Phenix HC2
         
0 reviews
Portable High Current Test Set (2000A max output)

Features

  • Built for field or shop use
  • Combines a variable high current output with appropriate controls and instrumentation
  • Ideal for testing thermal, magnetic and solid-state motor overload relays as well as molded-case circuit breakers and ground fault trip devices
  • Provides a short duration output of 2000 amps through a typical 150 ampere molded-case circuitbreaker when an instataneous trip element must be tested
  • Unique auto-sensing feature makes these testers easy to operate
  • Sensing leads, which operate on either normally-open or normally-closed devices, are connected to the test object
  • Output current level can be easily pre-set
  • When the output is initiated the pre-set output current locks on and the timer starts
  • When the test set senses a change in state of the test object (NO to NC or NC to NO), the current shuts off and the timer stops
  • Memory feature of the current meter holds the peak current value until reset by operator
  • Made in the USA
Loading Prices
Loading Callouts
Request a Quote
Loading Series Compare

Compare Products in this Series

Product Name Country of Origin Availability Price  
HC2
HC2
Portable High Current Test Set (2000A max output)
United States Availability
in stock!
Edu Price Standard Price Gov't Price
HC5
HC5
Mobile High Current Test Set (5000A max output)
Availability
in stock!
Edu Price Standard Price Gov't Price
HC3
HC3
Mobile High Current Test Set (4000A max output)
Availability
in stock!
Edu Price Standard Price Gov't Price
HC1
HC1
Portable High Current Test Set (1000A max output)
Availability
in stock!
Edu Price Standard Price Gov't Price

Product Information

These High Current Test Sets are built for field or shop use. Designed using the latest technology; these units combine a variable high current output with the appropriate controls and instrumentation. The test set is ideal for testing thermal, magnetic, and solid-state motor overload relays as well as molded-case circuit breakers and ground fault trip devices. They can also be used in many other applications requiring a high current source.

The HC2 is capable of a 2000 amp instantaneous output. Sufficient current is available for testing the time delay characteristics of motor overload relays and molded case circuit breakers.

The unique auto-sensing feature makes these testers easy to operate. Sensing leads, which operate on either normally-open or normally-closed devices, are connected to the test object. The output current level can be easily pre-set. When the output is initiated, the pre-set output current locks on and the timer starts. When the test set senses a change in state of the test object (NO to NC or NC to NO), the current shuts off and the timer stops. For instantaneous trip tests, the memory feature of the current meter holds the peak current value until reset by the operator.

Control Panel Layout.

  1. Current Meter
  2. Current Memory/Continous Mode Selector Switch
  3. Timer
  4. Cycles/Seconds Mode Selector
  5. Sensing Selector Switch
  6. External Sensing Lead Jacks
  7. Output Terminations
  8. Fuse Protection
  9. Power ON/OFF Switch
  10. Jog Switch
  11. High Current OFF
  12. High Current ON
  13. Trip Indicator/Reset Switch
  14. Raise Current Dial
  15. Current Range Selector
  16. Cable Storage Area

 


Back to Top

Specifications

Input 120 or 230 VAC +/-5%, 50 or 60 Hz 
(Voltage and Frequency must be specified.)
  HC1 HC2
120 V 20 Amp-Delay 20 Amp-Delay
220 V 10 Amp-Delay 12 Amp-Delay
Output 0-120 V @ 5 A 0-70 V @ 25 A
0-24 V @ 25 A 0-14 V @ 125 A
0-6 V @ 120 A 0-7 V @ 250 A
0-3 V @ 240 A 0-3.5 V @ 500 A
Overload 1000 Amps 2000 Amps
Short duration overloads are possible on each tap. The test set is capable of outputs up to those indicated above, depending on the impedance of the test circuit.
Duty Cycle Continuous @ 100%
5 min ON / 15 min OFF @ 200%
1 min ON / 5 min OFF @ 300%
30 sec ON / 5 min OFF @ 400%
Instrumentation
Currentmeter 3 ½ digit LCD
Ranges 0-1.999/19.99/199.9/1999 A
Accuracy ±0.5%
Timer 6 digit LCD, in cycles or seconds
Range 0-999999 cycles or 0-9999.99 seconds
Accuracy ±0.1% of reading
Dimensions 21" W x 17" D x 13" H
533 mm x 432 mm x 330 mm
Weight 70 lbs. (32 kg) 112 lbs. (51 kg)
Output Leads (5 feet) Timer Control Leads (2) Timer Control Leads (2)
Low current leads, 10 ga. (2) Low current leads, 10 ga. (2)
High current leads, 2 ga. (2) High current leads, 4 ga. (2)
High current leads, 4/0 (2)
Specifications are subject to change without notice.

Reviews

Phenix HC2 Customer Reviews

0 Reviews
5 stars
 (0)
4 stars
 (0)
3 stars
 (0)
2 stars
 (0)
1 star
 (0)
 
 
 
 
 
Average Customer Review
         
0 reviews
0 customer reviews
Share your thoughts with other customers
Create your own review
 
Most Helpful First | Newest First      Prev Page
 
Prev Page
 

Q & A

Q: Can the HC2 take input power from a single phase?
A: Yes, the HC2 can take input power from single phase.

Accessories

Loading Accessories

Phenix Price List

X


secured website

Interworld Highway, LLC dba TEquipment.NET

205 Westwood Avenue. Long Branch, NJ 07740

Privacy Policy | Terms and Conditions | Site Map

Copyright© 2016 Interworld Highway, LLC

secured website
We Price Match!

Give our sales team a call at 877.571.7901 (Toll Free) or 732.222.7077 (International) and we'll match any competitor's price.

X