NK Technologies AT Series Current Transducers

Click Image to Enlarge
NK Technologies AT Series
|
Features:
- Accurate
Factory matched and calibrated single piece transducer is more accurate than traditional two-piece field installed solutions.
- Average Responding
"Average responding" algorithm gives a RMS output on pure sine waves. Perfect for constant speed (linear) loads.
- Jumper Selectable Ranges
- Reduces inventory.
- Eliminates zero and span pots.
- Isolation
- Output is magnetically isolated from the input for safety.
- Eliminates insertion loss (voltage drop).
- UL, CUL and CE Approval
Accepted worldwide.
Applications:
- Automation Systems
Analog current reading for remote monitoring and software alarms.
- Data Loggers
Self-powered transducer does not drain data logger batteries.
- Panel Meters
Simple connection displays power consumption.
|
| Model |
Description |
List Price |
Sale Price |
| AT1-005-000-FF |
0-10, 0-20 & 0-50 Amp Ranges, Front Terminals, 0-5 VDC, Output: 0-5 VDC |
$98.00 |
| $87.22 |  |
|
| AT1-005-000-FT |
0-10, 0-20 & 0-50 Amp Ranges, Top Terminals, 0-5 VDC, Output: 0-5 VDC |
$98.00 |
| $87.22 |  |
|
| AT1-010-000-FF |
0-10, 0-20 & 0-50 Amp Ranges, Front Terminals, 0-10 VDC, Output: 0-10 VDC |
$98.00 |
| $87.22 |  |
|
| AT1-010-000-FT |
0-10, 0-20 & 0-50 Amp Ranges, Top Terminals, 0-10 VDC, Output: 0-10 VDC |
$98.00 |
| $87.22 |  |
|
| AT2-005-000-FT |
0-100, 0-150 & 0-200 Amp Ranges, Top Terminals, 0-5 VDC, Output: 0-5 VDC |
$98.00 |
| $87.22 |  |
|
| AT2-005-000-FF |
0-100, 0-150 & 0-200 Amp Ranges, Front Terminals, 0-5 VDC, Output: 0-5 VDC |
$98.00 |
| $87.22 |  |
|
| AT2-010-000-FF |
0-100, 0-150 & 0-200 Amp Ranges, Front Terminals, 0-10 VDC, Output: 0-10 VDC |
$98.00 |
| $87.22 |  |
|
| AT2-010-000-FT |
0-100, 0-150 & 0-200 Amp Ranges, Top Terminals, 0-10 VDC, Output: 0-10 VDC |
$98.00 |
| $87.22 |  |
|
| AT0-420-24L-FF |
0-2 & 0-5 Amp Ranges, Front Terminal, 4-20 mA, Output: 4-20 mA |
$150.00 |
| $133.50 |  |
|
| AT0-420-24L-FT |
0-2 & 0-5 Amp Ranges, Top Terminal, 4-20 mA, Output: 4-20 mA |
$150.00 |
| $133.50 |  |
|
| AT1-420-24L-FF |
0-10, 0-20, 0-50 Amp Ranges, Front Terminal, 4-20 mA, Output: 4-20 mA |
$140.00 |
| $124.60 |  |
|
| AT1-420-24L-FT |
0-10, 0-20, 0-50 Amp Ranges, Top Terminal, 4-20 mA, Output: 4-20 mA |
$140.00 |
| $124.60 |  |
|
| AT2-420-24L-FF |
0-100, 0-150, 0-200 Amp Ranges, Front Terminal, 4-20 mA, Output: 4-20 mA |
$140.00 |
| $124.60 |  |
|
| AT2-420-24L-FT |
0-100, 0-150, 0-200 Amp Ranges, Top Terminal, 4-20 mA, Output: 4-20 mA |
$140.00 |
| $124.60 |  |
|
| AT3-420-24L-FL |
0-375, 0-500, 0-750 Amp Ranges, Top Terminal, 4-20 mA, Output: 4-20 mA |
$245.00 |
| $218.05 |  |
|
| AT4-420-24L-FL |
0-1000, 0-1333, 0-2000 Amp Ranges, Top Terminal, 4-20 mA, Output: 4-20 mA |
$325.00 |
| $289.25 |  |
|
| AT1-005-000-SP |
0-10, 0-20 & 0-50 Amp Ranges, 0-5 VDC, Output: 0-5 VDC |
$130.00 |
| $115.70 |  |
|
| AT1-010-000-SP |
0-10, 0-20 & 0-50 Amp Ranges, 0-10 VDC, Output: 0-10 VDC |
$130.00 |
| $115.70 |  |
|
| AT2-005-000-SP |
0-100, 0-150 & 0-200 Amp Ranges, 0-5 VDC, Output: 0-5 VDC |
$130.00 |
| $115.70 |  |
|
| AT2-010-000-SP |
0-100, 0-150 & 0-200 Amp Ranges, 0-10 VDC, Output: 0-10 VDC |
$130.00 |
| $115.70 |  |
|
| AT0-420-24L-SP |
0-2 & 0-5 Amp Ranges, 4-20 mA, Output: 4-20 mA |
$180.00 |
| $160.20 |  |
|
| AT1-420-24L-SP |
0-10, 0-20, 0-50 Amp Ranges, 4-20 mA, Output: 4-20 mA |
$170.00 |
| $151.30 |  |
|
| AT2-420-24L-SP |
0-100, 0-150, 0-200 Amp Ranges, 4-20 mA, Output: 4-20 mA |
$170.00 |
| $151.30 |  |
|
AT Current Transducers from NK Technologies combine a current transformer and signal conditioner into a single package. The AT Series has jumper selected current input ranges and industry standard 420mA, 05VDC or 0-10VDC outputs. The AT Series is designed for application on 'linear' or sinusoidal AC loads. Available in a split core case or two types of solid core cases.
Specifications:
| |
-005 Models |
-010 Models |
-420 Models |
| Output Signal |
0-5VDC |
0-10VDC |
4-20mA |
| Output Limit |
10VDC |
15VDC |
40mA |
| Accuracy |
1.0% FS |
1.0% FS |
0.5% FS |
Response Time
(10-90% step change) |
100mS |
100mS |
300mS |
| Frequency Range |
50-60Hz |
50-60Hz |
20-100Hz* |
| Other Frequencies |
Special calibration available for any frequency from 10-400Hz* |
| Power Supply |
Self-powered |
Self-powered |
12?40VDC,
Loop-powered |
| Loading |
1m W minimum for rated accuracy
100K W add 1.3% error |
See "Power Supply" below |
| Isolation Voltage |
UL listed to 1,270VAC, tested to 5KV |
| Input Ranges |
Field Selectable Ranges from 0-200A (see Ordering Information). Custom ranges available, consult factory. |
| Sensing Aperture |
FF Case: 0.55" (14mm) dia.
FT Case: 0.75" (19mm) dia.
SP Case: 0.85" (21.5mm) sq. |
| Case |
UL 94V-0 flammability rated |
| Environmental |
-4 to 122°F (-20 to 50°C), 0-95% RH, non-condensing |
| Listings |
UL 508 Industrial Control Equipment (USA & Canada), CE |
*For sinusoidal waveforms only. Select ATR Transducers for distorted waveforms.
|