| Power Required |
None... Self powered |
| Accuracy |
0.5% FS, True RMS Power
+/- 0.5 Hz |
| Voltage Range |
120-600 VAC, Auto Range Select, Up to 12 KV with optional Potential Transformers |
| Amperage Range |
5-1500 A with ProteCTs
50-10,000 A with Current Output (5A) CTs |
| Isolation Voltage |
3,700 VAC |
| Built In Fuse rating |
600 VAC, 0.5A (No External fuses required) |
| Connections |
Voltage: 12" Leads, # 18 AWG, pre-tinned
Current Inputs & All Outputs: Captive screw terminal accept # 14-22 AWG wire |
| Environmental |
-18 to 50 C (0 to 122 F), 0-95% RH, NC |
| Dimensions |
Module: 9"Hx6.5"Wx2.6"D (23x16.5x6.5CM)
NEMA1: 10"Hx10"Wx4"D(26x24x10CM) |
| Modbus Software Set |
RTU Version |
| Modbus Hardware Set |
RS485 Addressable, 9600 Baud |
| Optional |
RS 232 Point to Point, 9600Baud |
| Approvals |
UL and UL-C Listed |
Modbus Network Variables (All Values True RMS, 24 Points)
| |
FA |
FB |
FC |
Total |
| Voltage |
. |
. |
. |
|
| Amperage |
. |
. |
. |
|
| kW |
. |
. |
. |
. |
| kWH |
. |
. |
. |
. |
| kVA |
. |
. |
. |
|
| Power Factor |
. |
. |
. |
|
| Frequency |
. |
. |
. |
|
| CT Value |
|
|
|
. |