LEM SATURNGEO 3 and 4 Pole Earth Tester

Click image to enlarge
LEM SATURNGEO
|
|
Features:
- Automatic determination of auxiliary earth electrode- and proberesistance
- Displays all measuring results for as long as desired
- Programmable LIMITS - optical and acoustical warning at limit infringement
- Long battery service-life because of short-time-measuring method and automatic switch-off
- Operator quick reference on rear of instrument
- Splashproof case IP56 (outdoor application)
- Developed, designed and manufactured as per DIN ISO 9001
Advantages:
- One button measurement concept for ease of use
- Rugged housing and protective holster for harsh environment
Accessories supplied:
- Rubber protective cover
- 2 measuring leads 1.5 m long
- 2 alligator clips
- 1 carrying strap
- 6 batteries
- Manual in English, German or French
|
Description
|
At the locations involving the generation, distribution and consumption
of electrical energy, certain safety measures must be met in order to
protect human life. In many cases, these safety measures are
national and international regulations which must be checked regularly.
Earthing, the connection of exposed conductive parts to the earth in
case of a fault, represents the most fundamental safety measure.
Real life requires the earthing of transformers, high and medium voltage
power pylons, railway tracks, tanks, vats, foundations and lightning
protection systems. Large fields of applications, the seasonal variations
of the earth resistance, variations from weather and ground conditions,
require test instrument able to collect and document additional
information in order to ensure that the conditions under which the
measurement was taken are known and that the results are
reproducible. Finally, the device must provide all of this information
reliably with the greatest possible simplicity and ease of use.
The SATURN GEO and SATURN GEO X provide the perfect solution
by combining the latest technology and years of LEM experience into
a compact, field-rugged and extremely easy to use instrument. In
addition to performing standard 3- and 4-pole earth resistance
measurements, an innovative process accurately measures individual
earth electrode resistances in single and meshed earthed systems
without disconnecting any parallel electrodes! One specific
application of this capability is quick and accurate measurement of
power pylon grounds. The SATURN GEO (X) also incorporates the
first truly automatic frequency control (AFC) to minimise interference.
Before measuring, the instruments identify existing interference and
select a measurement frequency to minimise its effect. The SATURN
GEO (X) incorporates microprocessor controlled automatic
measurements including checking probe hookup to ensure
measurements are taken correctly and measuring all probe ground
resistances to ensure reliable, repeatable results. Probe resistance
and auxiliary earth resistance are also measured and displayed. All measured
data, as well as the time-of-day the measurement was taken, can
be sent to computer or printed via an RS-232C interface.
|
Models, Options, & Accessories
| Model |
Description |
List Price |
Sale Price |
| SATURNGEO |
Please call or email us for pricing and availability. |
| SATURNGEOX |
Please call or email us for pricing and availability. |
| Model |
Accessories |
List Price |
Sale Price |
| A 6030 00530 |
Please call or email us for pricing and availability. |
| WINGEO |
Please call or email us for pricing and availability. |
| A 6899 00172 |
Please call or email us for pricing and availability. |
| A 6805 01010 |
Please call or email us for pricing and availability. |
| A 6805 01007 |
Please call or email us for pricing and availability. |
| A 6403 06311 |
Please call or email us for pricing and availability. |
| A 6805 06211 |
Please call or email us for pricing and availability. |
| A 6403 04111 |
Please call or email us for pricing and availability. |
| A 6403 06211 |
Please call or email us for pricing and availability. |
| A 6045 10350 |
Please call or email us for pricing and availability. |
| A 6045 05102 |
Please call or email us for pricing and availability. |
| A 6045 05103 |
Please call or email us for pricing and availability. |
| A 6009 17103 |
Please call or email us for pricing and availability. |
| A 6009 54300 |
Please call or email us for pricing and availability. |
| A 6412 06211 |
Please call or email us for pricing and availability. |
| A 6413 06111 |
Please call or email us for pricing and availability. |
| A 6202 46111 |
Please call or email us for pricing and availability. |
| A 6045 00610 |
Please call or email us for pricing and availability. |
| A 6045 10302 |
Please call or email us for pricing and availability. |
| A 6045 10301 |
Please call or email us for pricing and availability. |
| A 6045 10305 |
Please call or email us for pricing and availability. |
| A 6045 10306 |
Please call or email us for pricing and availability. |
Specifications
| Technical Data |
| Display |
4-digit (2999), 7-segmentliquid crystal display, 18 mm high, with fluorescent and active illumination (GEO X) |
| Working temperature |
-10° C ... + 50° C |
| Operating temperature |
0° C ... + 35° C |
| Reference temperature |
+18° C ... +28° C |
| Storage temperature |
-30° C ...+60° C |
| Operating error |
refers to operating temperature range |
| Intrinsic error |
refers to reference temperature range |
| Climatic class |
JWG as per DIN 40040 |
| Protective type |
IP 56 as per DIN 40050 |
| Operating altitude |
max. 2000 m |
| Safety |
Safety class II ( ) as per IEC/EN 61010-1 |
| Max. noise voltage |
24 V, thereon measurements are locked |
| Power supply |
6 x 1.5 V alkali-mangan batteries (IEC LR 6) or 1.5 V zink-carbon-batteries (IEC R 6) or 1,2 V accus |
| Dimensions |
240 x 180 x 110 mm (L x W x H) |
| Weight |
approx. 1.5 kg incl. batteries approx. 5.9 kg incl. 4 pcs. batteries and accessories in carrying case |
| Warranty |
2 years |
| Calibration interval |
3 years, recomended |
| Noise voltage (DC + AC) (UST) |
| Measuring method |
mean value rectification |
| Measuring rate |
approx. 4 measurements/s |
| Internal resistance |
approx. 1.5 MΩ |
| Max. overload |
Ueff = 250 V |
| Interference frequency (FST) |
| Measuring method |
measurement of period of noise voltage |
| Earthing resistance RA (RE) as per IEC 61557-5 |
| Measuring method |
Current and voltage measurement with probe |
| Measuring voltage |
20/48 V AC - switchable |
| Short circuit current |
250 mA |
| Measuring frequency |
94/105/111/128 Hz manual or autom. (AFC) switchable, 55 Hz for R* |
| Max. overload |
Ueff = 250 V |
| Measuring time |
typ. 8 sec. with fixed frequency chosen max. 30 sec. with autom. frequency selection |
| Max. probe resistance |
<1 MΩ |
| Max. auxiliary earth res. |
<1 MΩ >Display shows warning RS resp. RH, if ratio RH/RE is too high |
| Max. noise voltage |
24 V, above no measurement is started |
| Noise voltage suppr. |
120dB (162/3 , 50, 60, 400 Hz) |
| Resistance (R~) |
| Measuring method |
2-pole current and voltage measurement |
| Measuring voltage |
20 V AC |
| Short circuit current |
250 mA AC |
| Measuring frequency |
94/105/111/128 manual or autom. (AFC) Measuring time: typ. 6 sec. |
| Max. noise voltage |
24 V, above no measurements started |
| Max. overload |
Ueff = 250 V |
|