Fluke T3 Voltage and Continuity Tester
| Technical Specifications |
| Electrical |
Voltage LED: On at between 70% and 100% of marked voltage
Continuity threshold: Beeper on at <20,000Ω
Input impedance: 750 kΩ nominal
AC frequency response: 45 Hz to 66 Hz
Battery: (2) AA Life: 250 hours
|
Environmental Requirements
|
Operating temperature: 14°F to 122°F (-10°C to 50°C)
Storage temperature: -22°F to 140°F (-30°C to 60°C)
Humidity: 0% to 95% - 32°F to 86°F (0°C to 30°C) 0% to 75% - 86°F to 104°F (30°C to 40°C) 0% to 45% - 104°F to 122°F (40°C to 50°C)
Dust/water resistant: IP52 per IEC 529, no vacuum applied
Operating Altitude: approx. 9,800 ft. (3,000 m)
|
| Mechanical |
Size: 1.3" H x 1.8" W x 6.3" L (3.3cm x 4.6cm x 16cm)
Weight: 8 oz. (227 g ) with batteries
|
| Safety |
Maximum operating voltage: 1000 V AC/DC between any terminal and earth ground (protection only)
Voltage rating: Complies with IEC 1010-1 to 1000 V; OVERVOLTAGE Category III, Pollution Degree 2, and with IEC 664-1 to 600 V; OVERVOLTAGE Category IV, Pollution Degree 2.*
Agency approvals: UL, CSA, CE, VDE (pending)
|
|
* OVERVOLTAGE (Installation) Categories refer to the level of Impulse Withstand Voltage protection provided at the specified Pollution Degree. Equipment of
OVERVOLTAGE Category III is equipment in fixed installations. Examples include switch gear and polyphase motors. Equipment of OVERVOLTAGE Category IV is for use at the origin of the installation. Examples
include electricity meter and primary over-current protection equipment.
|
|
General Specifications
|
|
Warranty
|
1 Year
|
|
Calibration
|
None
|
|