Our agents are available:
9:00 AM - 6:00 PM EST
Fluke 434 Power Quality Analyzer
   Search: HACKER SAFE certified sites prevent over 99.9% of hacker crime.
   

   
   




Fluke 434 Power Quality Analyzer





Technical Data
Inputs Number: 4 voltage and current (3 phases + neutral)
Maximum voltage: 1000 Vrms (6 kV peak)
Maximum sampling speed: 200 kS/s on each channel simultaneously
Volt/Amps/Hertz Vrms (AC + DC)
Measurement range: 1 ... 1000 V
Accuracy: 0.5% of Vnom

Vpeak
Measurement range: 1 ... 1400 V
Accuracy: 5% of Vnom

Crest factor
Measurement range: 1.0 ... > 2.8
Accuracy: ±5%

Arms (AC + DC)
Measurement range: 0 ... 20 kA
Accuracy: ±1% ± 5 counts

Apeak
Measurement range: 0 ... 5.5 kA
Accuracy: 5%

Crest factor
Measurement range: 1 ... 10
Accuracy: ±5%

Hz (60 Hz nominal)
Measurement range: 51.00 ... 69.00 Hz
Accuracy: ±1% ± 5 counts

Dips and swells Vrms (AC+DC) ³
Measurement range: 0.0% … 100% of Vnom
Accuracy: ±1% of Vnom

Arms (AC+DC) ³
Measurement range: 0 ... 20 kA
Accuracy: ±1% ± 5 counts
Harmonics Harmonic (interharmonic) (n)
Measurement range: DC, 1..50; (Off, 1..49) measured relative to fundamental or to total rms

Vrms
Measurement range: 0.0 … 1000 V
Accuracy: ±5% ± 2 counts

Arms
Measurement range: 0.0 … 4000 mV x clamp scaling
Accuracy: ±5% ± 5 counts

Watts
Measurement range: Depends on clamp scaling
Accuracy: ±5% ± n x 2% or reading, ± 10 counts

DC voltage
Measurement range: 0.0 … 1000 V
Accuracy: ±5% ± 10 counts
THD
Measurement range: 0.0 … 100.0%
Accuracy: ±2.5%

Hz
Measurement range: 0 … 3500 Hz
Accuracy: ± 1 Hz

Phase angle
Measurement range: -360° ... +360°
Accuracy: ± n × 1.5°
Power and energy Watt, VA, VAR
Measurement range: 1.0 … 20.00 MVA¹
Accuracy: ±1.5% ± 10 counts

kWh, kVAh, kVARh
Measurement range: 00.00 …200.0 GVAh¹
Accuracy: ± 1.5% ± 10 counts

Power Factor/ Cos φ / DPF
Measurement range: 0…1
Accuracy: ± 0.03
Flicker Pst (1 min), Pst, Plt, PF5
Measurement range: 0.00 … 20.00
Accuracy: ±5%
Unbalance Volts
Measurement range: 0.0 … 5.0%
Accuracy: ±0.5%
Current
Measurement range: 0.0 … 20%
Accuracy: ± 1%
Transient Capture Volts
Measurement range: ±6000 V
Accuracy: ±2.5% of Vrms
Minimum detect duration: 5 μs (200kS/s sampling)
Inrush mode Arms (AC+DC)
Measurement range: 0.000 … 20.00 kA¹
Accuracy: ±1% of meas ± 5 counts
Autotrend recording Sampling: Up to 100 readings/s continuous sampling per channel
Memory: Up to 3600 min, max and avg points for each reading
Recording time: Up to 450 days
Zoom: Up to 12x horizontal zoom
Memory Screens: Fluke 434 - 50; Fluke 433 - 25
Data sets including recordings: Fluke 434 - 10; Fluke 433 - 5
Notes ¹ Depending on clamp scaling
² 50 Hz/60 Hz nominal frequency according to IEC 61000-4-30
³ Value is measured over 1 cycle, commencing at a fundamental zero crossing, and refreshed each half-cycle


Enviromental Specifications
Operating temperature 0 °C to +50 °C (32 °F to 122 °F)
Storage temperature -20 °C to +60 °C (-4 °F to 140 °F)
Operating Altitude 3,000 m (9842 ft)


Safety Specifications
Electrical Safety EN 61010-1 CAT IV 600 V / CAT III 1000 V
Standards Measurement methods: IEC61000-4-30 class A; EN50160; IEC 61000-4-15; IEC 61000-4-7


Mechanical & General Specifications
Size 256 x 169 x 64 mm (10 x 6.6 x 2.5 in)
Weight 2 kg (4.4 lb)
Warranty 3 years
Battery life Rechargeable NiMH pack: >7 hours
Charging time: 4 hours typical
Shock & Vibration MiL-PRF-2880F Class 2
Case IP51 (dust, drip, waterproof)



   
  Welcome | Companies | Search by Type | How To Order | Leasing | About Us  
  Tequipment.NET
205 Westwood Ave
Long Branch, NJ 07740
For our Electronic Whiteboard division visit www.touchboards.com
BBBOnline Reliability Seal. Tequipment.NET
Phone: 1-877-742-TEST (8378) / 732-222-7077
Fax: (732) 222-7088
E-mail: salesteam@Tequipment.NET