| Measurement Accuracy |
| Voltage |
Range and Resolution: 5.0 V to 600 V rms (AC+DC);
±5.0 V to ±933 V peak
Accuracy: rms: ±(0.5 % + 2 digits); Peak or DC: ±(2 % + 3 digits) (Add 2 digits if < 15 V rms)
|
Current
(1mV/A) Isolated input |
Range and Resolution: 1.00 A to 1000 A rms (AC+DC);
±1.0 A to ±2000 A peak
Accuracy: rms: ±(0.5% + 3 digits)+probe specs;
Peak or DC: ±(2 % + 4 digits) + probe specs
|
Watts/Volt-Amps
(1mV/A) isolated input |
Range and Resolution: 0.0W(VA) to 600 kW(kVA) average;
0.0W(VA) to ±2000 kW(kVA) peak
Accuracy: AC+DC: ±(1 % + 4 digits) + probe specs
|
| Harmonics (harmonic level >5% using Smooth 20) |
Volts: Fundamental to 13th ±(2 %+2 digits);
At 31st ±(8 %+2 digits);
Amps or Watts: Fundamental to 13th ±(3 % + 3 digits) + probe specs;
At 31st ±(8 % + 3 digits) + probe specs
|
| Frequency |
Range & Resolution: 6.0 Hz to 99.9 Hz
Accuracy: ±0.3 Hz |
| Input Bandwidth |
DC, 6 Hz to 2.1 kHz |
| Crest Factor (CF) |
Range & Resolution: 1.00 to 5.00
Accuracy :±4 % |
| Power Factor (PF) |
Range & Resolution: 0.00 to 1.00
Accuracy: ±0.02
|
| Displacement Power Factor (DPF) |
Range & Resolution: 0.00 to 1.00
Accuracy: ±0.04 to ±0.03 (0.30 to 0.89) ±0.02 (0.90 to 1.00)
|
| Phase |
Range & Resolution: -179 º to 180 º
Accuracy (Fundamental): ±2 º + probe specs
|
| K-Factor (KF) |
Range & Resolution: 1.0 to 30.00
Accuracy: ±10 %
|
| % THD-F |
Range & Resolution: 0.00 % to 799.9 %
Accuracy: ±(0.03 Reading + 2.0 %)
|
| % THD-R |
Range & Resolution: 0.0 % to 99.9 %
Accuracy: ±(0.03 Reading + 2.0 %) |