| Measurement Accuracy |
| Voltage |
Range and Resolution: 5.0V to 600V rms (AC+DC);
±5.0V to ±933V peak
Accuracy: rms: ±(0.5% + 2 digits); Peak or DC: ±(2% + 3 digits) (Add 2 digits if < 15V rms)
|
Current
(1mV/A) Isolated input |
Range and Resolution: 1.00A to 1000A rms (AC+DC);
±1.0A to ±2000A peak
Accuracy: rms: ±(0.5% + 3 digits)+probe specs;
Peak or DC: ±(2% + 4 digits) + probe specs
|
Watts/Volt-Amps
(1mV/A) isolated input |
Range and Resolution: 0.0W(VA) to 600kW(kVA) average;
0.0W(VA) to ±2000kW(kVA) peak
Accuracy: AC+DC: ±(1% + 4 digits) + probe specs
|
| Harmonics (harmonic level >5% using Smooth 20) |
Volts: Fundamental to 13th ±(2%+2 digits);
At 31st ±(8%+2 digits);
Amps or Watts: Fundamental to 13th ±(3% + 3 digits) + probe specs;
At 31st ±(8% + 3 digits) + probe specs
|
| Frequency |
Range & Resolution: 6.0 Hz to 99.9 Hz
Accuracy: ±0.3 Hz |
| Input Bandwidth |
DC, 6 Hz to 2.1 kHz |
| Crest Factor (CF) |
Range & Resolution: 1.00 to 5.00
Accuracy :±4% |
| Power Factor (PF) |
Range & Resolution: 0.00 to 1.00
Accuracy: ±0.02
|
| Displacement Power Factor (DPF) |
Range & Resolution: 0.00 to 1.00
Accuracy: ±0.04 to ±0.03 (0.30 to 0.89) ±0.02 (0.90 to 1.00)
|
| Phase |
Range & Resolution: -179º to 180º
Accuracy (Fundamental): ±2º + probe specs
|
| K-Factor (KF) |
Range & Resolution: 1.0 to 30.00
Accuracy: ±10%
|
| % THD-F |
Range & Resolution: 0.00% to 799.9%
Accuracy: ±(0.03 Reading + 2.0%)
|
| % THD-R |
Range & Resolution: 0.0% to 99.9%
Accuracy: ±(0.03 Reading + 2.0%) |