Our agents are available:
9:00 AM - 6:00 PM EST
Fluke 1744 Power Quality Logger Memobox
   Search: HACKER SAFE certified sites prevent over 99.9% of hacker crime.
   

   
   




Fluke 1744 Power Quality Logger Memobox




Specifications
General
Intrinsic error Refers to the reference conditions and is guaranteed for two years
Warranty 2 years
Recalibration interval 2 years recommended
Quality system developed, designed, and manufactured according to DIN ISO 9001
Reference conditions 23 °C ± 2 K; 74 °F ± 2 K , Vm = 230 V ± 10 % 50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz
phase sequence L1, L2, L3
interval length 10 minutes
Wye connection (L1, L2, L3 to N)
Power supply: 88 V to 265 V ac
Ambient conditions
Working temperature range -10 °C to 55 °C (14 °F to 131 °F)
Storage temperature range -20 °C to 60 °C (-4 °F to 140 °F)
Reference temperature range 23 °C ± 2 K (74 °F ± 2 K)
Relative humidity Fluke 1745: Class B2 acc. IEC 60654-1
Fluke 1744/43: Class C2 acc. IEC 60654-1
Housing robust, fully insulated housing and accessories
Environmental protection Fluke 1745: IP50 as per EN60529
Fluke 1744/43: IP65 as per EN60529
Safety IEC/EN 61010-1 600 V CAT III
300 V CAT IV, pollution degree 2
double insulation
Type test voltage 5.2 kV rms, 50 Hz/60 Hz, 5 s
EMC
Emission IEC/EN 61326-1, EN55022
Immunity IEC/EN 61326-1
Input voltage
Input range VI P-N max 480 V AC
Input range VI P-P max 830 V AC
Max. overload voltage 1.2 VI
Input range selection By job programming
Connections P-P or P-N, 1- or 3-phase
Nominal voltage VN <= 999 kV with PTs and ratio
Input resistance App. 820 kΩ per chan. Lx-N Single phase (L1 or A, L2 or B, L3 or C connected): app. 300 kΩ
Intrinsic uncenrtainty 0.1 % of VI
Voltage transformer Ratio: <999 kV / VI
Ration selection By job programming
Current input with Flexi Set
Input ranges II L1 or A, L2 or B, L3 or C, N 15 A / 150 A / 1500 A / 3000 A ac
Measuring range 0.75 A … 3000 A ac
Intrinsic uncertainty < 2 % of II
Position influence Max. ± 2 % of measured value – for distance conductor to meas. head > 30 mm
Stray field influence < ± 2 A ac for Iext=500 A ac and distance to measuring head > 200 mm
Temperature coefficient < 0.05 % / K
Current transformer Ratio <= 999 kA / II
Ratio selection By job programming
Connection 3-phase, 3-phase +N, 2 phase L1 or A and L3 or C (2 W-meter-method) 7 pole connector
Current input for clamp
Input ranges II L1 or A L2 or B, L3 or C, N: 0.5 V nominal (for II) 1.4 Vpeak
Intrinsic uncertainty < 0.3 % of II
Max. overload 10 V ac
Input resistance App. 8.2 kΩ
Current transformer Ratio Ω 999 kA / II
Power systems Delta, 2-Element Delta, Wye, Single Phase, Split Single Phase
Power supply
Functional Range 88 V to 660 V absolute, 50 Hz / 60 Hz
100 V to 350 V dc Internal fuse 630 mA T
Power consumption 5 Watts
Ride through Fluke 1745: Internal battery for typ. > 5 hours ride through with intelligent power management
Fluke 1743/44 3 sec Capacitor
Fuse Power supply fuse can be replaced in service facility only. Supply can be connected in parallel to measuring inputs (up to 660 V)
Display
Display, indicators LEDs for status and voltage levels
Fluke 1745: LC-display with backlight for voltage, current, active power, phase sequence.
Interface RS 232, 9600...115 000 Baud, automatic Baud rate selection, 3-wire communication
Dimensions
Fluke 1745 282 mm x 216 mm x 74 mm (115in x 88in x 33in)
Fluke 1743/1744 170 mm x 125 mm x 55 mm (69in x 51in x 22in)
Weight
Fluke 1745 approx. 3 kg
Fluke 1744/1743 approx. 2 kg
Measurement
A/D converter 16 bit, sample rate: 10.24 kHz
Anti-aliasing filter FIR-Filter, fc =4.9 kHz
Frequency response Uncertainty < 1 % of Vm for 40 Hz to 2500 Hz
Interval length 1, 3, 5, 10, 30 s, 1, 5, 10, 15, 60 minutes
Averaging time for Min/max values ½, 1 mains period, 200 ms,1 , 3 , 5 s
Time base Resolution: 10 ms (at 50 Hz), deviation: 2s/day at 23 °C; 74 °F ± 2K



   
  Welcome | Companies | Search by Type | How To Order | Leasing | About Us  
  Tequipment.NET
205 Westwood Ave
Long Branch, NJ 07740
For our Electronic Whiteboard division visit www.touchboards.com
BBBOnline Reliability Seal. Tequipment.NET
Phone: 1-877-742-TEST (8378) / 732-222-7077
Fax: (732) 222-7088
E-mail: salesteam@Tequipment.NET