Fluke PR1530 LEM Oscilloscope AC/DC Current Probe
   Search: HACKER SAFE certified sites prevent over 99.9% of hacker crime.
   

   
   




Fluke PR1530 LEM Oscilloscope AC/DC Current Probe




  Specifications

Electrical Characteristics
Current Ranges 100 A and 1000 A ACRMS or DC
Measuring Ranges ± 140 A and 1400 A
Output Sensitivity 10 mV/A (100 A)
1 mV/A (1000 A)
Accuracy (at +25°C) (100A range) ± 1% of reading ± 100 mA
(1000A range) ± 1% of reading ± 500 mA
Resolution ± 100 mA (100 A)
± 200 mA (1000 A)
Load Impedance > 10 k Ohms and ≤ 100 pF
Conductor Position Sensitivity ± 1.5% relative to centre reading
Frequency Range……(small signal) DC to 20 kHz (- 2 dB)
Phase Shift below 2 kHz ≤ 2 degrees
Power Supply 9 V Alkaline, MN1604/PP3
40 Hours, low battery indicator
Temperature Coefficient ± 0.1% of reading per °C
Working Voltage (see Safety Standards section) 300 V ACRMS or DC
General Characteristics
Maximum Conductor Size 31 mm diameter
Output Connection safety BNC connector
Output Zero Manual adjust via thumbwheel
Cable Length 2 meters
Operating Temperature Range 0 to +50 °C
Storage Temperature Range (with battery removed -20 to +85 °C
Operating Humidity 15% to 85% (non condensing)
Weight 295 g



   