Our agents are available:
9:00 AM - 6:00 PM EST
Fluke N6K PP64
Power Phase Analyzer
   Search: HACKER SAFE certified sites prevent over 99.9% of hacker crime.
   

   
   




Fluke N6K PP64
Power Phase Analyzer



Fluke N6K PP64
Click image to enlarge

 Fluke N6K PP64

    Announcement


Features
  • 0.3 V – 1000 V, 0.03 A – 10 A direct
  • Sampling rate 341 kHz
  • Bandwidth DC to 3 MHz
  • 0.03% basic accuracy for 2 years



  Models, Options, & Accessories


Model Description List Price Sale Price
N6K PP64 EA1640Z, POWER PHASE VOLT/CUR, NORMA 6000 $4395.00
$4153.28 
N6K PP69 EA1690Z, POWER PHASE VOLT/CUR, NORMA 6000 $4395.00
$4153.28 



Ranges
Voltage
8 ranges 0.3 – 1 – 3 – 10 – 30 – 100 – 300 – 1000 V
Upeak = 2 x range
Input impedance 2 MOhm / 20 pF
CMR Common Mode Rejection 120 dB at 100 kHz
Current
6 ranges 30 – 100 mA – 0.3 – 1 – 3 – 10 A
Ipeak = 2 x range; max level 150 % at sine wave (limit of error as at 100 %).
Input impedance with integrated shunts
Ranges 30 mA, 100 mA 1 Ohm
Ranges 0.3 A, 1 A 0.1 Ohm
Ranges 3 A, 10 A 0.01 Ohm
Current overload max. 15A continuous
30 A < 5 sec / 15 sec no load
100 A < 0.1s / 30 sec no load
Input for external shunt or probe
BNC terminal 100 kOhm / 30pF
30 – 100 mV – 0.3 – 1 – 3- 10 V
Overload max. 20 Vrms
CMR common mode rejection 120 dB at 100 kHz

Error of Amplitude
Basic accuracy PP64
Sum limit of error U I
Range 0.02% 0.02%
Reading 0.01% 0.01%
Voltage and current depending on the input level at 45 – 65 Hz frequency range
Input level Sum limit of error U Sum limit of error I
in % in % in %
100 0.03 0.03
50 0.05 0.05
30 0.08 0.08
10 .21 .21
5 .41 .41
3 .68 .68
1 2.01 2.01

PP64 Bandwidth
  U and I via BNC I direct measured
Bandwidth -3dB 3 MHz 1 MHz
Current measurement accuracy depending on the frequency (reading + range)
Frequency Limits of error current [ % ]
[Hz] Internal shunt BNC input
0 0.03 -0.03 0.03 -0.03
10 0.03 -0.03 0.03 -0.03
45 0.03 -0.03 0.03 -0.03
65 0.03 -0.03 0.03 -0.03
500 0.03 -0.03 0.03 -0.03
1000 0.03 -0.03 0.03 -0.03
2000 0.08 -0.21 0.06 -0.15
5000 0.13 -0.45 0.10 -0.31
10000 0.18 -0.63 0.13 -0.43
20000 0.23 -0.81 0.16 -0.55
50000 0.28 -1.05 0.20 -0.71
100000 0.33 -1.23 0.23 -0.83
Voltage measurement accuracy depending on the frequency (reading + range)
Frequency in Hz Limits of error voltage in %
0 0.03 -0.03
10 0.03 -0.03
45 0.03 -0.03
65 0.03 -0.03
500 0.03 -0.03
1000 0.03 -0.03
2000 0.06 -0.15
5000 0.10 -0.31
10000 0.13 -0.43
20000 0.16 -0.55
50000 0.20 -0.71
100000 0.23 -0.83
Valid for averaged values at 23 ±5 °C ambient temperature, sine waveform and after 1 hour turn on time with measuring signal.

Power / Angular Error
PP64 Between U and IBNC Between U and IShunt
Angular Error 0.0025° +0.0025° / kHz 0.005° +0.005° / kHz
Error Power
Frequency in Hz Limit of error power in % at Lamda = 1
45 0.5 -0.5
65 0.5 -0.5



   
  Welcome | Companies | Search by Type | How To Order | Leasing | About Us  
  Tequipment.NET
205 Westwood Ave
Long Branch, NJ 07740
For our Electronic Whiteboard division visit www.touchboards.com
BBBOnline Reliability Seal. Tequipment.NET
Phone: 1-877-742-TEST (8378) / 732-222-7077
Fax: (732) 222-7088
E-mail: salesteam@Tequipment.NET