Our agents are available:
9:00 AM - 6:00 PM EST
Fluke N4K PP42
Power Phase Analyzer
   Search: HACKER SAFE certified sites prevent over 99.9% of hacker crime.
   

   
   




Fluke N4K PP42
Power Phase Analyzer



Fluke N4K PP42
Click image to enlarge

 Fluke N4K PP42

    Announcement


Features
  • 0.3 V – 1000 V, 0.06 A – 20 A direct
  • Sampling rate 341 kHz
  • Bandwidth dc to 3 MHz
  • 0.2 % basic accuracy for 2 Years



  Models, Options, & Accessories


Model Description List Price Sale Price
N4K PP42 EA1420Z, POWER PHASE VOLT/CUR NORMA 4000 & 5000 $2395.00
$2263.28 
N4K PP30 EA1300Z, POWER PHASE VOLT/CUR NORMA 4000 & 5000 $695.00
$656.78 
N4K PP40 EA1400Z, POWER PHASE VOLT/CUR NORMA 4000 & 5000 $2095.00
$1979.78 



Ranges
Voltage
8 ranges 0.3 – 1 – 3 – 10 – 30 – 100 – 300 – 1000 V
Upeak = 2 x range
Input impedance 2 MOhm / 20 pF
CMR Common Mode Rejection 120 dB at 100 kHz
Current
6 ranges 60 – 200 mA – 0.6 – 2 – 6 – 20 A
Ipeak = 2 x range; max level 150 % at sine wave (limit of error as at 100 %).
Input impedance with integrated shunts
Ranges 60 mA, 200 mA 5 Ohm
Ranges 0.6 A, 1 A 0.5 Ohm
Ranges 6 A, 10 A 0.05 Ohm
Current overload max. 25A continuous
30 A < 5 sec / 15 sec no load
100 A < 0.1s / 30 sec no load
Input for external shunt or probe
BNC terminal 100 kOhm / 30pF
30 – 100 mV – 0.3 – 1 – 3- 10 V
Overload max. 20 Vrms
CMR common mode rejection 120 dB at 100 kHz

Error of Amplitude
Basic accuracy PP42
Sum limit of error U I
Range 0.1% 0.1%
Reading 0.1% 0.1%
Voltage and current depending on the input level at 45 – 65 Hz frequency range
Input level Sum limit of error U Sum limit of error I
in % in % in %
100 0.20 0.20
50 0.30 0.30
30 0.43 0.43
10 1.10 1.10
5 2.10 2.10
3 3.43 3.43
1 10.10 10.10

PP42 Bandwidth
  U and I via BNC I direct measured
Bandwidth -3dB 3 MHz .5 MHz
Current measurement accuracy depending on the frequency (reading + range)
Frequency Limits of error current [ % ]
[Hz] Internal shunt BNC input
0 0.20 -0.20 0.20 -0.20
10 0.20 -0.20 0.20 -0.20
45 0.20 -0.20 0.20 -0.20
65 0.20 -0.20 0.20 -0.20
500 0.20 -0.20 0.20 -0.20
1000 0.20 -0.20 0.20 -0.20
2000 0.25 -0.41 0.23 -0.32
5000 0.30 -0.69 0.27 -0.48
10000 0.35 -0.91 0.30 -0.60
20000 0.40 -1.12 0.33 -0.72
50000 0.45 -1.40 0.37 -0.88
100000 0.50 -1.61 0.40 -1.00
Voltage measurement accuracy depending on the frequency (reading + range)
Frequency in Hz Limits of error voltage in %
0 0.20 -0.20
10 0.20 -0.20
45 0.20 -0.20
65 0.20 -0.20
500 0.20 -0.20
1000 0.20 -0.20
2000 0.23 -0.32
5000 0.27 -0.48
10000 0.30 -0.60
20000 0.33 -0.72
50000 0.37 -0.88
100000 0.40 -1.00
Valid for averaged values at 23 ±5 °C ambient temperature, sine waveform and after 1 hour turn on time with measuring signal.

Power / Angular Error
PP42 Between U and IBNC Between U and IShunt
Angular Error 0.005° +0.005° / kHz 0.025° +0.015° / kHz
Aliasing filter OFF
Error Power
Frequency in Hz Limit of error power in % at Lamda = 1
45 0.33 -0.33
65 0.33 -0.33



   
  Welcome | Companies | Search by Type | How To Order | Leasing | About Us  
  Tequipment.NET
205 Westwood Ave
Long Branch, NJ 07740
For our Electronic Whiteboard division visit www.touchboards.com
BBBOnline Reliability Seal. Tequipment.NET
Phone: 1-877-742-TEST (8378) / 732-222-7077
Fax: (732) 222-7088
E-mail: salesteam@Tequipment.NET