Our agents are available:
9:00 AM - 6:00 PM EST
Fluke N4K PP30
Power Phase Analyzer
   Search: HACKER SAFE certified sites prevent over 99.9% of hacker crime.
   

   
   




Fluke N4K PP30
Power Phase Analyzer



Fluke N4K PP30
Click image to enlarge

 Fluke N4K PP30

    Announcement


Features
  • 0.3 V – 1000 V, 0.03 A – 10 A direct
  • Sampling rate 100 kHz
  • Bandwidth dc to 1 MHz
  • 0.3 % basic accuracy for 2 Years



  Models, Options, & Accessories


Model Description List Price Sale Price
N4K PP30 EA1300Z, POWER PHASE VOLT/CUR NORMA 4000 & 5000 $695.00
$656.78 
N4K PP40 EA1400Z, POWER PHASE VOLT/CUR NORMA 4000 & 5000 $2095.00
$1979.78 
N4K PP42 EA1420Z, POWER PHASE VOLT/CUR NORMA 4000 & 5000 $2395.00
$2263.28 



Ranges
Voltage
8 ranges 0.3 – 1 – 3 – 10 – 30 – 100 – 300 – 1000 V
Upeak = 2 x range
Input impedance 2 MOhm / 20 pF
CMR Common Mode Rejection 80 dB at 100 kHz
Current
6 ranges 30 – 100 mA – 0.3 – 1 – 3 – 10 A
Ipeak = 2 x range; max level 150 % at sine wave (limit of error as at 100 %).
Input impedance with integrated shunts
Ranges 30 mA, 100 mA 1 Ohm
Ranges 0.3 A, 1 A 0.1 Ohm
Ranges 3 A, 10 A 0.01 Ohm
Current overload max. 15A continuous
30 A < 5 sec / 15 sec no load
100 A < 0.1s / 30 sec no load
Input for external shunt or probe
BNC terminal 100 kOhm / 30pF
30 – 100 mV – 0.3 – 1 – 3- 10 V
Overload max. 20 Vrms
CMR common mode rejection 80 dB at 100 kHz

Error of Amplitude
Basic accuracy PP30
Sum limit of error U I
Range 0.15% 0.15%
Reading 0.15% 0.15%
Voltage and current depending on the input level at 45 – 65 Hz frequency range
Input level Sum limit of error U Sum limit of error I
in % in % in %
100 0.30 0.30
50 0.45 0.45
30 0.65 0.65
10 1.65 1.65
5 3.15 3.15
3 5.15 5.15
1 15.15 15.15

PP30 Bandwidth
  U and I via BNC I direct measured
Bandwidth -3dB 1 MHz 0.3 MHz
Current measurement accuracy depending on the frequency (reading + range)
Frequency Limits of error current [ % ]
[Hz] Internal shunt BNC input
0 0.30 -0.30 0.30 -0.30
10 0.30 -0.30 0.30 -0.30
45 0.30 -0.30 0.30 -0.30
65 0.30 -0.30 0.30 -0.30
500 0.30 -0.30 0.30 -0.30
1000 0.30 -0.30 0.30 -0.30
2000 0.36 -0.54 0.35 -0.48
5000 0.44 -0.86 0.40 -0.72
10000 0.50 -1.10 0.45 -0.90
20000 0.56 -1.34 0.50 -1.08
50000 0.64 -1.66 0.55 -1.32
100000 0.70 -1.90 0.60 -1.50
Voltage measurement accuracy depending on the frequency (reading + range)
Frequency in Hz Limits of error voltage in %
0 0.30 -0.30
10 0.30 -0.30
45 0.30 -0.30
65 0.30 -0.30
500 0.30 -0.30
1000 0.30 -0.30
2000 0.35 -0.48
5000 0.40 -0.72
10000 0.45 -0.90
20000 0.50 -1.08
50000 0.55 -1.32
100000 0.60 -1.50
Valid for averaged values at 23 ±1 °C ambient temperature, sine waveform and after 1 hour turn on time with measuring signal.

Power / Angular Error
PP30 Between U and IBNC Between U and IShunt
Angular Error 0.1° +0.1° / kHz 0.1° +0.1° / kHz
Error Power
Frequency in Hz Limit of error power in % at Lamda = 1
45 0.49 -0.49
65 0.49 -0.49



   
  Welcome | Companies | Search by Type | How To Order | Leasing | About Us  
  Tequipment.NET
205 Westwood Ave
Long Branch, NJ 07740
For our Electronic Whiteboard division visit www.touchboards.com
BBBOnline Reliability Seal. Tequipment.NET
Phone: 1-877-742-TEST (8378) / 732-222-7077
Fax: (732) 222-7088