Fluke Memobox Power Distribution Network Analyzers
   Search: HACKER SAFE certified sites prevent over 99.9% of hacker crime.
   

   
   




Fluke Memobox Power Distribution Network Analyzers




  Specifications

General
Intrinsic error Refers to the reference conditions and is guaranteed for two years
Warranty 2 years
Recalibration interval 2 years recommended
Quality system developed, designed, and manufactured according to DIN ISO 9001
Reference conditions 23°C ±2K, Um=230 V ±10%, 50 Hz ±0.1 Hz or 60 Hz ±0.1 Hz phase sequence L1, L2, L3,
interval length 10 minutes
Star connection (L1, L2, L3 to N)
Power supply 88 V ... 265 V AC
Environment conditions
Working temp. range -10°C ... +55 C
Operating temp. range 0°C … +35°C
Storage temp. range -20°C … +60°C
Reference temp. range 23°C ± 2K
Relative humidity 10...80 %, no dewing
Safety IEC/EN 61010-1 600 V CAT III, 300 V CAT IV, pollution degree 2, double insulation
Type test voltage 5.2 kV r.m.s., 50 Hz / 60 Hz, 5 s
EMC
Emission IEC/EN 61326-1, EN55022
Immunity IEC/EN 61326-1
Power Supply
Functional range 88 V …440 V AC, 50 Hz / 60 Hz 100 V … 400 V DC
Internal fuse 630 mA T
Safety IEC/EN 61010-1 300 V CAT IV pollution degree 2, double insulation
Via test leads in parallel to measuring input (max. 440V)
Power consumption max. 7 VA
Intervals see table on page 1
Events >13.000
Memory model linear, circular
Interface RS 232, 9600...115 000 Baud, automatic Baud rate selection, 3-wire communication
Dimensions, weight MEMOBOX 808 A: 282 mm x 216 mm x 74 mm, 2.4 kg
MEMOBOX 300 P, A: 170 mm x 125 mm x 55 mm, 1.1 kg
Measurements
A/D converter 16 bit, sample rate: 10.24 kHz
Anti-aliasing filter FIR-Filter, fC =4.9 kHz
Frequency response Error < 1 % for UN = 230 V for 40 Hz…2500 Hz
Interval length 5, 10, 30 s, 1, 5, 10, 15, 60 minutes
Averaging time for Min/max values ½, 1 mains period, 200 ms,1 , 3 , 5 s
Time base deviation: max. 2s/day at 23°C
Inputs
Voltage
Input range VI P-N 69 V / 115 V / 230 V / 480 V AC
Input range VI P-P 120 V / 200 V / 400 V / 830 V AC
Max. overload voltage 1.2 VI
Input range selection by job programming in CODAM software
Connections P-P or P-N, 1- or 3-phase
Nominal voltage UN ≤ 999 kV
Input resistance appr. 820kΩ per channel
Intrinsic error 0.1 % of VI
Voltage transformer ratio: <999 kV / VI
Current measurement with LEM~flex
Input ranges II
A, B, C, N 15 A / 150 A / 1500 A / 3000 A AC
Measurement range 0.75 A … 3000 A AC
Intrinsic error <2 % of II
Position influence max. ±2% of m.v. – for distance conductor to meas. head >30 mm
Stray field influence <±2 A AC for Iext=500 A AC and distance to measuring head >200 mm
Temperature coefficient < 0.05% / °C
Transformer ratio ≤ 999 kA / ≤ II
Ratio selection by job programming
Connection 3-phase, 3-phase and Neutral 2-phase L1, L3 (2W-meter-method)
Current measurement with clamps (instrument without sensors)
Input ranges II
A, B, C, N 0.5V nominal, 1.4 Vpeak
Intrinsic error <0.3 % of II
Overload capacity 10 V AC max.
Input resistance appr. 8.2 kΩ
Transformer ratio ≤ 999 kA / ≤ II
Connections 3-phase, 3-phase and Neutral wire 2-phase L1, L3, (2W-meter-method)
RMS measurements
Slow voltage variations
Measuring values Mean-value: RMS values averaged over interval length
Min-, Max-values Averaging with selectable
averaging time 0.5 periods to 5 s
Max-value Max. r.m.s. value per interval
Min-value Min. r.m.s. value per interval
Current
Measuring values
Mean-value RMS values integrated over interval length
Max-value Highest r.m.s. value per interval
Events
Dips, swells, interruptions
Limit value variable, lower limit: 0…95 % VN upper limit: 105…120 % VN set in CODAM PLUS
Range 0...UI + 20 %
Measuring value ½ period RMS value
Intrinsic error < 2 % of VI
Response time ½ mains period (10ms in 50 Hz systems)
Flicker
Measuring value Flicker level (Plt/Pst) according to IEC 61000-4-15
Intrinsic error Pst < 5 % of m.v.
Measuring range Pst 0.4 … 4
Power
P, Q, S, |P|
Active power P as per EN 61036, class 2
Reactive power Q as per EN 61268, class 2
Mean- value averaged over interval length
Max-value highest value per interval
Min-value smallest value per interval
Phase error < 0.5 degrees
Conditions conductor centred within clamp/LEM~flex
Harmonics
Um, Im, THD V, THD I as per IEC/EN61000-4-7 2002
Voltage harmonics
Intrinsic error for Vm < 3% UN: < 0.15% VN
for Vm ≥ 3% UN < 5% Vm
Current harmonics
Intrinsic error for Im < 10% IN: < 0.5% IN
for Im ≥ 10% IN < 5% Im
THD V (MEMOBOX 300 P)
Intrinsic error at UN for THD V < 3%: < 1%
for THD V ≥ 3% < 5%
THD V (MEMOBOX 300 A, 808 A)
Intrinsic error at UN for THD V < 3%: < 0.15%
for THD V ≥ 3% < 5%
THD I
Intrinsic error at IE for THD I < 3%: < 2%
for THD I ≥ 3% < 5%
Statistics
Frequency 42 classes for 10 s mean values
Ripple control signals,
Interharmonics 21 classes for 3 s mean values
Analysis of measurement data
Programming and analysis with PC software CODAM PLUS.



   
  Welcome | Companies | Search by Type | How To Order | Leasing | About Us  
  Tequipment.NET
205 Westwood Ave
Long Branch, NJ 07740
For our Electronic Whiteboard division visit www.touchboards.com
BBBOnline Reliability Seal. Tequipment.NET
Phone: 1-877-742-TEST (8378) / 732-222-7077
Fax: (732) 222-7088
E-mail: salesteam@Tequipment.NET