Our agents are available:
9:00 AM - 6:00 PM EST
Fluke ISOPLUSM LEM Contractor and service technician insulation tester and multimeter
   Search: HACKER SAFE certified sites prevent over 99.9% of hacker crime.
   

   
   




Fluke ISOPLUSM LEM Contractor and service technician insulation tester and multimeter




  Specifications

General
Display 1999 digit dual LCD with special symbols, digit height 17 mm, 30 segment analogue bar with over/ underflow and special display symbols, EL backlight
Working temp. -10° C ... +50° C (+14° F...+122° F )
Operating temp. 0° C ... +35° C (+32° F...+95° F )
Storage temp. -20° C ... +60° C (-4° F...+140° F )
Reference temp. +23° C ± 2° C (+73° F ± 4° F )
Temperature coefficient 0.1 x operating error/K Intrinsic Error refers to the reference temperature range
Climatic class B2 (IEC 654-1), -5° C..+45°C, 5%...85% RH, no dew
Maximum operating altitude 2000m
Protective type IP40 according to EN 60529
Safety Protection by reinforced insulation 600V CATIII pollution degree 2
Test voltage 5550 V AC, measuring circuit to enclosure
Emission IEC/EN 61326-1:1997 +A1:1998 class B
Immunity EN 61000-4-2:1995 - B,EN 61000-4-3:1996
EN 61000-4-4:1995 - B,EN 61000-4-5:1995
EN 61000-4-6:1996 - B,EN 61000-4-8:1993
Intrinsic error Refers to the reference temperature range and is guaranteed for 2 years.
Operating error Refers to the operating temperature range and is guaranteed for 2 years.
Quality system Developed, designed and manufactured according to DIN ISO 9001
External voltage Measurement inhibited for external voltage Ux >10% of UN for MΩ and >3V for R
Max. overload 800 Veff RMS or RMS x frequency < 5x104VHz
Auxiliary power 4 x 1.5 V mignon cells alkali-manganese(IEC LR6)
Battery life span Typical (no backlight) > 2000 measurements in MΩ. 100 hours continuous operation for resistance, voltage measurements and mA measurements.
Fuse 630mA quick acting 600V 10kA/32x6.3mm
Dimensions 220 x 98 x 52 mm (12 x 3.75 x 2 inches)
Weight 0.8 kg / 1.8 lbs (including batteries)
Warranty 2 years
Calibration interval 2 years recommended
MΩ - RISO Insulation Resistance
Method Voltage/current measurement as per EN 61557–2
Nominal test voltage UN = 100V, 250V, 500V, 1000V DC
Open circuit voltage U0 < 1.1 x UN
Nominal current IN ≥ 1mA DC at UN IN ≥ 2.5mA DC at 100kΩ at 250V
Short circuit current <10mA DC
R – Low Resistance Measurement
Method Voltage/current measurement as per EN 61557–4
Open circuit voltage U0 ≥ 4V
Short circuit current Ik ≥ 200mA DC up to 2Ω as pe



   
  Welcome | Companies | Search by Type | How To Order | Leasing | About Us  
  Tequipment.NET
205 Westwood Ave
Long Branch, NJ 07740
For our Electronic Whiteboard division visit www.touchboards.com
BBBOnline Reliability Seal. Tequipment.NET
Phone: 1-877-742-TEST (8378) / 732-222-7077
Fax: (732) 222-7088
E-mail: salesteam@Tequipment.NET