Fluke 330 Series Clamp Meter
| Technical Specifications |
AC Current

|
| Range |
| 333: |
0-400.0 A |
| 334,335,336: |
0-600.00 A |
| 337: |
0-999.9 A |
|
| Accuracy |
| 333, 334, 335: |
2% ± 5 counts (50/60 Hz) |
| 336, 337: |
2% ± 5 counts (10-100 Hz) |
|
6% ± 5 counts(100-400 Hz) |
|
| Crest Factor |
| 333, 334: |
Not Applicable |
| 335: |
2.4@500 A, 2.0@600 A add 2% for CF>2 |
| 336: |
3@500 A, 2.5@600 A add 2% for CF>2 |
| 337: |
3@500 A 2.5@600 A 1.42@1000 A add 2% for CF>2 |
|
| AC Response |
| 333, 334: |
Averaging |
| 335, 336, 337: |
True-rms |
|
|
|
In-Rush |
| Integration Time |
| 333: |
Not Applicable |
| 334, 335, 336, 337: |
100 ms |
|
|
DC Current

|
| Range |
| 333, 334, 335: |
Not Applicable |
| 336: |
0-600.0 A |
| 337: |
0-999.9 A |
|
| Accuracy |
| 333, 334, 335: |
Not Applicable |
| 336, 337: |
2% ± 3 counts |
|
|
|
AC Volts

|
| Range |
| 333, 334, 335, 336, 337: |
0-600.0 V |
|
| Accuracy |
| 333, 334, 335: |
1% ± 5 counts (50/60 Hz) |
| 336, 337: |
1% ± 5 counts (20-100 Hz), 6% ± 5 counts (100-400 Hz) |
|
| AC Response |
| 333, 334: |
Averaging |
| 335, 336, 337: |
True-rms |
|
|
|
DC Volts

|
| Range |
| 333, 334, 335, 336, 337: |
0-600.0 V |
|
| Accuracy |
| 333, 334, 335, 336, 337: |
1% ± 5 counts |
|
|
|
Resistance

|
| Range |
| 333: |
0-600.0 Ω |
| 334, 335, 336, 337: |
0-600.0 Ω, 601-6000 Ω |
|
| Accuracy |
| 333, 334, 335, 336, 337: |
1.5% ± 5 counts |
|
|
|
Continuity
|
|
| 333, 334, 335, 336, 337: |
≤30 Ω |
|
|
|
Frequency

(AC Only)
|
| Range |
| 333, 334, 335, 336: |
Not Applicable |
| 337: |
0-600.0 Ω, 601-6000 Ω |
|
| Accuracy |
| 333, 334, 335, 336: |
Not Applicable |
| 337: |
5-400 Hz |
|
| Trigger Level |
| 333, 334, 335, 336: |
0.5% ± 5 counts |
| 337: |
10-100 Hz > 5 A 5-10 Hz, 100-400 Hz > 10 A |
|
|
| General Specifications |
| Min/Max |
337 Only |
| Backlight |
333: No 334,335,336,337: Yes |
| Operating Temperature |
-14 °F to 122 °F (-10 °C to 50 ° C) |
| Battery Life |
Alkaline 150 hours continuous, automatic low battery indicator |
| Safety Rating |
IEC 1010-2-031, 600 V CAT III |
| Warranty |
Three years |
| Temperature De-rating |
Add 0.1 x specified accuracy for each °C above 28°C or below 18°C |
| Storage Temperature |
-40 °F to 140 °F (-40 °C to 60 °C) |
| Display Hold |
Yes |
| Size |
Height 9.375" (23.8 cm)
Width 3.125" (7.9 cm)
Depth 1.625" (4.10 cm) |
| Weight |
11 oz. (311.8 g) |
| User's Manuals & Other Documentation |
| Instruction Card |
333, 334, 335 Instruction Card (PDF, 357kB) |
| Instruction Card |
336, 337 Instruction Card (PDF, 413kB) |
| Safety Sheet |
333, 334, 335, 336, 337 Safety Sheet (PDF, 3.15MB) |
| Safety Sheet Supplement |
333, 334, 335, 336, 337 Safety Sheet Supplement (PDF, 7kB) |
| Calibration Information |
333, 334, 335, 336, 337 Calibration Information (PDF, 406kB) |
|