Measurement Function
V dc Range and Resolution
400.0 mV, 4.000 V, 40.00 V, 400.0 V, 1000 V

Best Accuracy (% of reading + LSD)
0.1 % + 1

V ac (true-rms) Range and Resolution
400.0 mV, 4.000 V, 40.00 V, 400.0 V, 1000 V

Best Accuracy (% of reading + LSD)
0.7 % + 2

mA dc Range and Resolution
30.000 mA

Best Accuracy (% of reading + LSD)
.05 % + 2

A dc Range and Resolution
1.000 A (0.440 A continuous)

Best Accuracy (% of reading + LSD)
0.2 % + 2

A ac Range and Resolution
1.000 A (0.440 A continuous)

Best Accuracy (% of reading + LSD)
1 % + 2

Resistance Range and Resolution
400.0 Ohms, 4.000 k, 40.00 k, 400.0 k, 4.0 M, 40 M

Best Accuracy (% of reading + LSD)
0.2 % + 1

Frequency (0.5 Hz to 20 kHz) Range and Resolution
199.99 Hz, 1999.9 Hz, 19.999 kHz

Best Accuracy (% of reading + LSD)
.005 % + 1

Diode Test Range and Resolution
2.000 V (shows diode voltage drop)

Best Accuracy (% of reading + LSD)
2 % + 1

Continuity Range and Resolution
Beeps for resistance < approx. 100 ohms


Output Function
DC Current Output
(Internal battery operation)
Range and Resolution
0.000 to 20.000 mA or 4.000 to 20.000 mA
(selectable at power-up)
Over-range to 24.000 mA

Drive Capability (% of span)
24 V compliance, or,
1,200 Ohms, @ 20 mA

Accuracy
.05 %

DC Current Simulate
(Ext. 24 Volt loop supply)
Range and Resolution
0.000 to 20.000 mA or 4.000 to 20.000 mA,
(selectable at power-up)
Over-range to 24.000 mA

Drive Capability (% of span)
1000 Ohms, @ 20 mA

Accuracy
.05 %

24 V Loop Supply Range and Resolution
Minimum 24 V

Drive Capability (% of span)
250 Ohms @ 20 mA

Accuracy
> 24 V

Current Adjustment Modes  Range and Resolution
Manual: 0.001 mA, 0.1 mA, 25 % and 100 % step
Automatic: Slow Ramp, Fast Ramp, 25 % step
      *Temperature range of 18 °C to 28 °C, for one year after calibration


General Specifications
Maximum voltage applied between
any jack and earth ground:
1000 V RMS
Storage temperature: -40 °C to 60 °C
Operating temperature: -20 °C to 55 °C
Temperature coefficient: 0.05 x (specified accuracy) per °C (for temperatures < 18 °C or > 28 °C)
Relative humidity 95 % up to 30 °C;
75 % up to 40 °C; 45 % up to 50 °C;
35 % up to 55 °C
Vibration: Random, 2 g, 5-500 Hz
Shock: 1 meter drop test
Safety: Designed in accordance with
EN61010, ANSI/ISA S82.01-1994 and
CAN/CSA C22.2 No. 1010..1-92
Over-voltage Category III
Size: 50 mm H x 100 mm W x 203 mm L
(1.97 in H x 3.94 in W x 8.00 in L)
Weight: 600 g (1.3 lbs)
Battery: Four AA alkaline batteries
Battery life: 140 hours typical (measurement), 10 hours typical (sourcing 12 mA)
Warranty: 3 years


User's Manual & Other Documentation
789 Product Overview Product Overview (.pdf 633 KB)
789 Product Overview Supplement Product Overview Supplement (.pdf 9.87 KB)
789 User's Manual User's Manual (.pdf 771 KB)
789 User's Manual Supplement User's Manual Supplement (.pdf 9.99 KB)
789 Calibration Manual Calibration Manual (.pdf 947 KB)




 

Welcome | Companies | Search by Type | How To Order | Leasing | About Us | Careers
  Tequipment.NET
205 Westwood Ave
Long Branch, NJ 07740
BBBOnline Reliability Seal, Click for confirmation page. Tequipment.NET
Phone: 1-877-571-7901 / 732-222-7077
Fax: (732) 222-7088
E-mail: salesteam@Tequipment.NET
 




Fluke Sponsored March Madness Bracket Challenge

Free Fluke Laser Distance Meter

Fluke Educational Grant Program

Fluke Stock Guarantee

Fluke 110% Price Match Guarantee

Quote Request

We Take POs, How To Order

Free Shipping on Fluke










Live chat by BoldChat
Let our engineers and cs staff help!
Need a quote? Need to check stock?
Have a technical question? No problem.
We are here to help.