Technical Data
Inputs
Number 4 voltage and current (3 phases + neutral)
Maximum voltage 1000 Vrms (6 kV peak)
Maximum sampling speed 200 kS/s on each channel simultaneously
Volt/Amps/Hertz
Vrms (AC + DC)
Measurement range 1 ... 1000 V
Accuracy 0.1% of Vnom
Vpeak
Measurement range 1 ... 1400 V
Accuracy % of Vnom
Crest factor, voltage
Measurement range 1.0 ... > 2.8
Accuracy ±5%
Arms (AC + DC)
Measurement range 0 ... 20 kA
Accuracy ±0.5% ± 5 counts
Apeak
Measurement range 0 ... 5.5 kA
Accuracy 5%
Crest factor, A
Measurement range 1 ... 10
Accuracy ±5%
Hz 50 Hz nominal
Measurement range 42.50 ... 57.50 Hz
Accuracy ±0.01 Hz
Dips and swells
Vrms (AC+DC) ²
Measurement range 0.0% … 100% of Vnom
Accuracy ±0.2% of nominal voltage
Arms (AC+DC) ²
Measurement range 0 ... 20 kA ?
Accuracy ±1% ± 5 counts
Harmonics
Harmonic (interharmonic) (n)
Measurement range DC, 1..50; (Off, 1..49) measured according to IEC 61000-4-7
Vrms
Measurement range 0.0 … 1000 V
Accuracy ±0.05% of nominal voltage
Arms
Measurement range 0.0 … 4000 mV x clamp scaling
Accuracy ±5% ± 5 counts
Watts
Measurement range Depends on clamp scaling and voltage
Accuracy ±5% ± n x 2% or reading, ± 10 counts
DC voltage
Measurement range 0.0 … 1000 V
Accuracy ±0.2% of nominal voltage
THD
Measurement range 0.0 … 100.0%
Accuracy ±2.5% V and A (± 5% Watt)
Hz
Measurement range 0 … 3500 Hz
Accuracy ± 1 Hz
Phase angle
Measurement range -360º ... +360º
Accuracy ± n × 1.5º
Power and energy
Watt, VA, VAR
Measurement range 1.0 … 20.00 MVA¹
Accuracy ±1% ± counts
kWh, kVAh, kVARh
Measurement range 00.00 …200.0 GVAh¹
Accuracy ± 1.5% ± 10 counts
Power Factor/ Cos ? / DPF
Measurement range 0…1
Accuracy ± 0.03
Flicker
Pst (1 min), Pst, Plt, PF5
Measurement range 0.00 … 20.00
Accuracy ±5%
Unbalance
Volts
Measurement range 0.0 … 5.0%
Accuracy ±0.5%
Current
Measurement range 0.0 … 20%
Accuracy ± 1%
Transient Capture
Volts
Measurement range ±6000 V
Accuracy ±2.5% of Vrms
Minimum detect duration 5 µs (200kS/s sampling)
Inrush mode
Arms (AC+DC)
Measurement range 0.000 … 20.00 kA¹
Accuracy ±1% of meas ± 5 counts
Inrush duration (selectable)
Measurement range 7.5 s ... 30 min
Accuracy ±20 ms (Fnom = 50 Hz)
Autotrend recording
Sampling 5 readings/sec continuous sampling per channel
Memory 1800 min, max and avg points for each reading
Recording time Up to 450 days
Zoom Up to 12x horizontal zoom
Memory
Screens & data 50, shared memory divided between logging, screens and data sets
Notes
¹ Depending on clamp scaling
² Value is measured over 1 cycle, commencing at a fundamental zero crossing, and refreshed each half-cycle

Environmental Specifications
Operating Temperature 0 ºC to +50 ºC

Safety Specifications
Safety EN61010-1 (2nd edition) pollution degree 2; 1000 V CAT III / 600 V CAT IV ANSI/ISA S82.01

Mechanical & General Specifications
Size 256 x 169 x 64 mm
Weight 1.1 kg
Battery Life
Rechargeable NiMH pack (installed) >7 hours
Battery charging time 4 hours typical
Shock & Vibration
Shock 30 g
Vibration 3 g according to MIL-PRF-28800F Class 2
Case Rugged, shock proof with integrated protective holster, IP51 (drip and dust proof)
Warranty 3 years




   
  Welcome | Companies | Search by Type | How To Order | Leasing | About Us  
  Tequipment.NET
205 Westwood Ave
Long Branch, NJ 07740
For our Electronic Whiteboard division visit www.touchboards.com
BBBOnline Reliability Seal. Tequipment.NET
Phone: 1-877-742-TEST (8378) / 732-222-7077
Fax: (732) 222-7088
E-mail: salesteam@Tequipment.NET