Our agents are available:
9:00 AM - 6:00 PM EST
Fluke 345 Power Quality Clamp Meter
   Search: HACKER SAFE certified sites prevent over 99.9% of hacker crime.
   

   
   




Fluke 345 Power Quality Clamp Meter




Display
Color transmissive LCD 320 x 240 pixels (70 mm diagonal) with 2 level backlight
Power supply
Battery type 1.5 V Alkaline AA MN 1500 or IEC LR6 x 6
Battery life typically > 10 hours (backlight on full)
> 12 hours (backlight reduced)
Battery Eliminator BE345 Input: 110 V/230 V, 50/60 Hz
Output: 15 V dc, 300 mA
Ambient conditions (For indoor use only)
Reference conditions All accuracies stated at 23 °C ± 1 °C (73.4 °F ± 1.8 °F)
Operating temperature 0 °C to 50 °C (32 °F to 122 °F)
Temperature coefficient of current ≤ ± 0.15 % of rdg per °C
Temperature coefficient of voltage ≤ ± 0.15 % of rdg per °C
Maximum relative humidity 80 % for temperatures up to 31 °C (87 °F) decreasing linearly to 50 % relative humidity at 40 °C (104 °F)
Maximum operating altitude 2000 m
Electrical safety
Safety Rating IEC 61010-1 600 V CAT IV, double or reinforced insulation, pollution degree 2
Protection IP40; EN60529
Maximum safe working voltages
Current measurement 600 V ac rms or dc between uninsulated conductor and ground
Voltage measurement 600 V ac rms or dc between either input terminal and ground, or 825 V between energized phase voltages (delta power config.)
EMC
Emission IEC/EN 61326-1:1997 class B
Immunity IEC/EN 61326-1:1997
Mechanical
Dimensions (length x width x depth) 300 mm x 98 mm x 52 mm (12 in x 3.75 in x 2 in)
Weight including batteries 820 g/1.8 lb
Jaw opening 60 mm
Jaw capacity 58 mm diameter
Cleaning The unit can be cleaned with an Isopropanol impregnated cloth. Do not use abrasives or
other solvents.
Electrical data
All accuracies stated at 23 °C ± 1 °C (73.4 °F ± 1.8 °F).
See Ambient conditions specifications for temperature coefficients.
Current measurement (dc, dc rms, ac rms)
Measuring range 0 to 2000 A dc or 1400 ac rms
Autorange facility 40 A/400 A/2000 A
Resolution 10 mA in 40 A range
100 mA in 400 A range
1 A in 2000 A range
Accuracy
DC and dc rms
I > 10 A ± 1.5 % rdg ± 5 digits
I < 10 A ± 0.2 A
AVG
I > 10 A ± 3 % rdg ± 5 digits
I < 10 A ± 0.5 A
Pk
I > 10 A ± 5 % rdg ± 5 digits
I < 10 A ± 0.5 A
AHr
I > 10 A ± 2 % rdg ± 5 digits
I < 10 A ± 0.5 AHr
CF (Crest Factor)
1.1 ≤ CF < 3 ± 3 % rdg ± 5 digits
3 ≤ CF < 5 ± 5 % rdg ± 5 digits
Resolution 0.01
RPL (Ripple)
2 % ≤ RPL < 100 % ± 3 % rdg ± 5 digits
100 % ≤ RPL < 600 % ± 5 % rdg ± 5 digits
Resolution 0.1 %
  Idc > 5 A
  Iac > 2 A
All measurements dc and 15 Hz to 1 kHz
Maximum overload 10,000 A or rms x frequency < 400,000
Amps rms is a true-rms measurement (ac + dc)
Voltage measurement (dc, dc rms, ac rms)
Measuring range 0 to 825 V dc or ac rms
Autorange facility 4 V/40 V/400 V/750 V
Resolution 1 mV in 4 V range
10 mV in 40 V range
100 mV in 400 V range
1 V in 750 V range
Accuracy
DC and dc rms
V > 1 V ± 1 % rdg ± 5 digits
V < 1 V ± 0.02 V
AVG
V > 1 V ± 3 % rdg ± 5 digits
V < 1 V 0.03 V
Pk
V > 1 V ± 5 % rdg ± 5 digits
V < 1 V ± 0.03 V
CF (Crest Factor)
1.1 ≤ CF < 3 ± 3 % rdg ± 5 digits
3 ≤ CF < 5 ± 5 % rdg ± 5 digits
Resolution 0.01
RPL (Ripple)
2 % ≤ RPL < 100 % ± 3 % rdg ± 5 digits
100 % ≤ RPL < 600 % ± 5 % rdg ± 5 digits
Resolution 0.1 %
  Vdc > 0.5 V
  Vac > 0.2 V
All measurements dc and 15 Hz to 1 kHz
Maximum overload 1,000 V rms
Volts rms is a true-rms measurement (ac + dc)
Harmonics
THD (Total Harmonic Distortion)
1 % ≤ THD < 100 % ± 3 % rdg ± 5 digits
100 % ≤ THD < 600 % ± 5 % rdg ± 5 digits
Resolution 0.1 %
DF (Distortion Factor)
1 % ≤ DF < 100 % ± 3 % rdg ± 5 digits
Resolution 0.1 %
H02 ≤ Vharm < H13 ± 5 % rdg ± 2 digits
H13 ≤ Vharm ≤ H30 ± 10 % rdg ± 2 digits
All measurements up to 30th harmonic (40th harmonic for 15 Hz to 22 Hz)
Frequency range F0 15 Hz to 22 Hz and 45 Hz to 65 Hz
Vacrms > 1V
Watts measurement (single- and three-phase) (dc, dc rms, ac rms)
Measuring range 0 to 1650 kW dc or 1200 kW ac
Autoranging facility 4 kW, 40 kW, 400 kW, 1650 kW ac
Resolution 1 W in 4 kW
10 W in 40 kW
100 W in 400 kW
1 kW in 1200 kW
Accuracy 2.5 % rdg ± 5 digits
W1Ø < 2 kW ± 0.08 kW
W3Ø < 4 kW ± 0.25 kW
VA measurement (single- and three-phase) (dc, dc rms, ac rms)
Measuring range 0 to 1650 kVA dc or 1200 kVA ac
Autorange facility 4 kVA, 40 kVA, 400 kVA, 1650 kVA
Resolution 1 VA in 4 kVA
10 VA in 40 kVA
100 VA in 400 kVA
1 kVA in 1200 kVA
Accuracy
VA > 2 kVA 2.5 % rdg ± 5 digits
VA < 2 kVA ± 0.08 kVA
VAR measurement (single- and three-phase)
Measuring range 0 to 1250 kVAR
Autorange facility 4 kVAR, 40 kVAR, 400 kVAR, 1200 kVAR
Resolution 1 VAR in 4 kVAR
10 VAR in 40 kVAR
100 VAR in 400 kVAR
1 kVAR in 1200 kVAR
Accuracy
VAR > 4 kVAR ± 2.5 % rdg ± 5 digits
VAR < 4 kVAR ± 0.25 kVAR
Power factor range 0.3 < PF < 0.99
Power factor (single- and three-phase)
Power factor
Measuring range 0.3 capacitive and 1.0 to 0.3 inductive (72.5° capacitive and 0° to 72.5° inductive)
Resolution 0.001
Accuracy ± 3°
Frequency range 15 Hz to 1 kHz
Displacement power factor
Measuring range 0.3 capacitive and 1.0 to 0.3 inductive (72.5° capacitive and 0° to 72.5° inductive)
Resolution 0.001
Accuracy ± 3°
Frequency range 15 Hz to 22 Hz and 45 Hz to 65 Hz
Kilowatt hour (kWHr)
Measuring range 40,000 kWHr
Autorange facility 1 kWHr, 40 kWHr, 400 kWHr, 4,000 kWHr, 40,000 kWHr
Resolution 1 WHr in 4 kWHr
10 WHr in 40 kWHr
100 WHr in 400 kWHr
1 kWHr in 4,000 kWHr
10 kWHr in 40,000 kWHr
Accuracy
kWHr > 2 kWHr ± 3 % ± 5 digits
kWHr < 2 kWHr ± 0.08 kWHr
All Watts /VA /VAR /PF measurements
Frequency range DC and 15 Hz to 1 kHz
Current range 10 A to 1400 A rms
Voltage range 1 V to 825 V rms
Maximum input 825 V rms/1400 A rms
Maximum overload 1000 V rms/10,000 A
Frequency measurement (from current or voltage sources)
Measuring range 15 Hz to 1 kHz
Resolution 0.1 Hz
Accuracy 15 to 22 Hz ± 0.5 % rdg
40 Hz to 70 Hz ± 0.5 % rdg
15 Hz to 1000 Hz ± 1% rdg
Current range 10 A to 1400 A rms
Voltage range 1 V to 825 V rms
Scope function
Current measurement
Ranges 10 A/20 A/40 A/100 A/200 A/400 A/1000 A/2000 A
Resolution 1 A in 40 A
10 A in 400 A
50 A in 2000 A
Accuracy ± 3 % rdg ± 1 pixel
Maximum overload 10,000 A
Voltage measurement
Ranges 4 V/10 V/20 V/40 V/100 V/200 V/400 V/1000 V
Resolution 100 mV in 4 V
1 V in 40 V
10 V in 400 V
31.25 V in 1000 V
Accuracy ± 2 % rdg ± 1 pixel
Maximum overload 1000 V rms
Frequency range DC and 15 Hz to 600 Hz
Time base 2.5 ms, 5 ms, 10 ms, 25 ms, 50 ms/div
Refresh rate 0.5 seconds
Maximum sampling rate 15.625 kHz
Inrush current function
Ranges 40 A, 400 A, and 2000 A
Resolution 10 mA in 40 A range
100 mA in 400 A range
1 A in 2000 A range
Accuracy
I > 10 A ± 5 % rdg ± 1 pixel
I < 10 A ± 0.5 A
All measurements dc and 15 Hz to 1 kHz
Maximum overload Maximum overload 10,000 A or rms x frequency < 400,000
Amps rms is a true-rms measurement (ac + dc)
Capture time 1 s, 3 s, 10 s, 30 s, 100 s, and 300 s
Maximum sampling rate 15.625 kHz
Interface
USB Interface to a PC
Power Log software for download, analysis, and reporting
345 Upgrade Utility for installing a new firmware version
Logging Memory
Logging areas Three areas that can be used individually or combined into one large area
Averaging periods 1 s, 2 s, 5 s, 10 s, 30 s, 1 min, 5 min, 10 min, 15 min, and custom
Logging times
Volts and current mode
Average time Logging time (1 area) Logging time (3 areas)
1 s 1 h 49 m 5 h 12 m
2 s 3 h 38 m 10 h 24 m
5 s 9 h 06 m 1 d 2 h 00 m
10 s 18 h 12 m 2 d 04 h 00 m
30 s 2 d 06 h 36 m 6 d 12 h 01 m
1 min 4 d 13 h 12 m 13 d 00 h 03 m
5 min 22 d 18 h 00 m 65 d 00 h 15 m
10 min 45 d 12 h 00 m 130 d 00 h 30 m
15 min 68 d 06 h 00 m 195 d 00 h 45 m
V & A harmonics mode
Average time Logging time (1 area) Logging time (3 areas)
1 s 0 h 34 m 1 h 38 m
2 s 1 h 08 m 3 h 16 m
5 s 2 h 52 m 08 h 11 m
10 s 5 h 44 m 16 h 23 m
30 s 17 h 13 m 2 d 01 h 11 m
1 min 1 d 10 h 26 m 4 d 02 h 23 m
5 min 7 d 04 h 10 m 20 d 11 h 25 m
10 min 14 d 08 h 20 m 81 d 0 h 50 m
15 min 21 d 12 h 30 m 121 d 13 h 15 m
single- and three-phase power mode
Average Time Logging Time (1 area) Logging Time (3 areas)
1 s 1 h 40 m 4 h 47 m
2 s 3 h 21 m 9 h 34 m
5 s 8 h 22 m 23 h 57 m
10 s 16 h 45 m 1 d 23 h 54 m
30 s 2 d 02 h 17 m 5 d 23 h 42 m
1 min 4 d 04 h 35 m 11 d 23 h 25 m
5 min 20 d 22 h 55 m 59 d 21 h 05 m
10 min 41 d 21 h 50 m 119 d 18 h 10 m
15 min 62 d 20 h 45 m 179 d 15 h 15 m



   
  Welcome | Companies | Search by Type | How To Order | Leasing | About Us  
  Tequipment.NET
205 Westwood Ave
Long Branch, NJ 07740
For our Electronic Whiteboard division visit www.touchboards.com
BBBOnline Reliability Seal. Tequipment.NET
Phone: 1-877-742-TEST (8378) / 732-222-7077
Fax: (732) 222-7088
E-mail: salesteam@Tequipment.NET