Our agents are available:
9:00 AM - 6:00 PM EST
Fluke 1760 TR Basic Three Phase
Power Quality Recorder Topas
   Search: HACKER SAFE certified sites prevent over 99.9% of hacker crime.
   

   
   




Fluke 1760 TR Basic Three Phase
Power Quality Recorder Topas


Product Home | Features | Specifications | Models, Options, Accessories & Discounted Prices


Overview of Measurement Functions
Statistical Evaluation Power quality statistics according to EN50160 and DISDIP tables like ITIC, CEBEMA, ANSI
Event List Dips, swells and interruptions are detected and stored in the event list. Also any trigger which fires generates an event added to this list. The Event list shows the exact time when the event occurred as well as the duration and magnitude. Sorting by several attributes of these events is possible to select one for further root cause analysis. RMS values, transients and fast transients can be stored if a trigger fires.
Continuous Recording Fluke 1760 records rms values together with corresponding minimum and maximum values for:
  • Voltage
  • Current
  • Power P, Q, S
  • Power Factor
  • kWh
  • Flicker
  • Unbalance
  • Frequency
  • Harmonics/Interharmonics
continuously with the following time aggregations:
  • Day
  • 10 min
  • Free Interval, e.g.: 15 min, 2h
Triggered Recordings rms: Aggregation time is adjustable between 10 ms (1/2 cycle), 20ms (1 cycle), 200ms (10/12 cycles) or 3 sec (150/180 cycles). Calculating rms values, Harmonics and Interharmonics is performed synchronous to the power frequency. Basic aggregation for harmonics and interharmonics is 200ms
Oscilloscope: Sample rate is 10.24 kHz for all 8 channels
Fast Transients: Sample rate is selectable from 100 kHz to 10 MHz for channel 1-4 FFT of Fast Transients
Mains Signalling Phases and N-conductor, Voltage and current
Online Mode Variable refresh rate. This feature allows verification of instrument set up and delivers a quick overview of oscilloscope, transients and events.

General Data
Intrinsic uncertainty refers to reference conditions and is guaranteed for two years
Quality system developed, manufactured as per ISO 9001: 2000
Housing insulated, robust plastics housing
Data memory 2 GB Flash memory depending on model
Memory model Linear
Interfaces Ethernet (100MB/s), compatible to Windows® 98/ME/NT/2000/XP RS 232, external modem via RS 232
Baud rate for RS 232 9600 Baud to 115 kBaud
Dimensions 325 mm x 300 m x 65 mm; 2.8 x 11.8 x 2.6 in. (H x W x D)
Weight appr. 4.9 kg; 10.8 lbs. (without accessories)
Warranty 2 years
Calibration interval 1 year recommended for Class-A, otherwise 2 years
Operating temp. range: 0 °C to +50 °C; 32 °F to +122 °F
Working temp. range: -20 °C to +50 °C; -4 °F to +122 °F
Storage temp. range: 20 °C to +60 °C; -4 °F to 140 °F
Reference temperature: 23 °C ± 2 K; 74 °F ± 2 K
Climatic class: B2 (IEC 654-1), -20 °C to +50 °C; -4 °F to +122 °F
Max. operating altitude: 2000 m: max. 600 V CAT IV*, power supply: 300 V CAT III 5000 m: max 600 V CAT III*, power supply: 300 V CAT II
* depending on sensor
Reference conditions
Environment temp.: 23 °C ± 2 K ; 74°F ± 2 K
Power supply: 230 V ± 10 %
Power frequency: 50 Hz / 60 Hz
Signal: declared input voltage Udin
Averaging: 10 minute intervals
EMC
Emission: Class-A as per IEC/EN 61326-1
Immunity: IEC/EN 61326-1
Power supply
Range: AC: 83 V to 264 V, 45 to 65 Hz
DC: 100 V to 375 V
Safety: IEC/EN 61010-1 2nd edition
300 V CAT III
Power consumption: max. 54VA
Battery pack: NIMH, 7.2 V, 2.7 Ah
In case of a power supply failure an internal battery maintains the supply for up to 40 minutes. Afterwards, or in case of discharged accumulators the Fluke 1760 is turned off and continues the measurements with the latest settings as soon as the supply voltage returns. The battery can be replaced by the user.
Display Fluke 1760 features LED indicators for the status of the 8 channels, phase sequence, power supply (mains or accumulator), memory usage, time synchronization, and data transfer.
Power LED: Permanent light: normal power supply from mains.
OFF: supply via internal accumulator in case of a power failure.
Channel LEDs 3-color LEDs per channel for:
  • overload condition
  • under load condition
  • signal level in nominal range

Signal Conditioning
Range for 50 Hz systems 50 Hz ± 15 % (42.5 Hz to 57.5 Hz)
Range for 60 Hz systems 60 Hz ± 15 % (51 Hz to 69 Hz)
Resolution 16 ppm
Sampling frequency for 50 Hz power frequency 10.24 kHz, The sampling rate is synchronized to mains frequency.
Uncertainty for frequency measurements < 20 ppm
Uncertainty of internal clock < 1s / day
Measurement intervals Aggregation of the interval values as per IEC 61000-4-30 Class-A
Min-, Max-values: Half cycle, e.g.: 10 ms rms values at 50Hz
Transients: Sample rate 100 kHz to 10 MHz per channel
Harmonics as per IEC 61000-4-7:2002: 200 ms
Flicker as per EN 61000-4-15:2003: 10 min (Pst), 2 h (Plt)

Measurement Inputs
Number of inputs 8 galvanically isolated inputs for voltage and current measurements.
Sensor safety up to 600 V CAT IV depending on sensor
Basic safety 300 V CAT III
Nominal voltage (rms) 100 mV
Range (peak value) 280 mV
Overload capacity (rms) 1000 V, continuously
Voltage rise rate max. 15 kV / µs
Input resistance 1 MO
Input capacitance 5 pF
Input filter Each channel is equipped with a passive low-pass filter, an anti-aliasing filter and a 16-bit A/D converter. All channels are sampled synchronously with a common quartz-controlled clock pulse.
The filters protect against voltage transients and limit the signal rise rate, reduce high frequency components and especially the noise voltage above half the sampling rate of the A/D converter by 80 dB, thus achieving very small measuring errors in an exceptionally large amplitude range. This is also valid under extreme operating conditions like transient voltages at the output of converters.

Uncertainties
Uncertainty at reference conditions Uncertainty including the voltage sensors is in compliance with IEC 61000-4-30 Class-A. All voltage sensors are suitable for DC up to 5 kHz
With Sensor 1000 V 0,1% at Udin = 480 V and 600 V P-N
Sensor 600 V 0,1% at Udin = 230 V P-N
Intrinsic uncertainty for harmonics Class I as per EN 61000-4-7:2002
Reference conditions 23 °C ± 2 K < 60 % rH; 74 °F ± 2 K < 60 % rH
Warmed up instrument > 3h
Power supply: 100 V to 250 V ac
Temperature drift 100 ppm / K
Aging < 0.05 % / year
Common mode rejection > 100 dB at 50 Hz
Temperature drift Change of amplification through temperature: < 0.005 %/K
Aging Change of amplification due to ageing: < 0.04 %/year
Noise Noise voltage, input short-circuited: < 40 µV
DC ± (0.2% rdg + 0.1% sensor)




   
  Welcome | Companies | Search by Type | How To Order | Leasing | About Us  
  Tequipment.NET
205 Westwood Ave
Long Branch, NJ 07740
For our Electronic Whiteboard division visit www.touchboards.com
BBBOnline Reliability Seal. Tequipment.NET
Phone: 1-877-742-TEST (8378) / 732-222-7077
Fax: (732) 222-7088
E-mail: salesteam@Tequipment.NET