Fluke 1630 Earth Ground Clamp Meter
   Search: HACKER SAFE certified sites prevent over 99.9% of hacker crime.
   

   
   




Fluke 1630 Earth Ground Clamp Meter




General specifications
Operating error Refers to the operating temperature range and is guaranteed for 2 years
Storage temp. range -20 °C to 60 °C (-4 °F to 140 °F )
Reference temp. range 23 °C ± 5 °C (73 °F ± 9 °F )
Storage humidity < 75 % RH
Operating humidity < 85 % RH
Display 9999 digit LC-display with special symbols
Protection IP20 according to IEC 529/EN 60529
Safety 300 V, CAT III / pollution degree 2 IEC 61010-1
Weight 640 g (1.4 lb)
Conductor size 35 mm (1.38 in) approximately
Dimension (length x width x depth) 257 mm x 100 mm x 47 mm
(1 in x 3.9 in x 1.9 in)
Emission IEC 1000 4-2, IEC 61326-1 class B
Immunity IEC 61000-4-2, 8 kV (air) criteria A
IEC 61000-4-3, 3 V/m performance criteria A
Range selection Auto
Overload indicator “OL” on display
Measuring time 0.4 sec
Measuring frequency 3.333 kHz
Battery type 9 V alkaline (type IEC 6 LR 61)
Battery life ≥ 8 hours (continuous operation)
Power consumption 40 mA
Low battery indication Display symbol
Ground Loop Resistance (Autorange)
Operating temperature 0 °C to 50 °C (14 °F to 122 °F)
Range Resolution Operating error1
0.025 - 0.250 Ω 0.002 Ω ± 1.5 % rdg ± 0.05 Ω
0.250 - 9.999 Ω 0.02 Ω ± 1.5 % rdg ± 0.1 Ω
10.00 - 99.99 Ω 0.04 Ω ± 2.0 % rdg ± 0.3 Ω
100.0 - 199.9 Ω 0.4 Ω ± 3.0 % rdg ± 1.0 Ω
200.0 - 400.0 Ω 2 Ω ± 5.0 % rdg ± 5 Ω
400.0 - 600.0 Ω 5 Ω ± 10 % rdg ± 10 Ω
600.0 - 1500 Ω 20 Ω ± 20 %
1Note: Loop resistance with no inductance, external magnetic field < 50 A/m, external electrical field < 1 V/m, conductor centered.
Continuity
Beep if resistance < approx. 40 Ω
Ground/leakage current mA~
(Autorange, 50/60 Hz, true-rms, crest factor < 3.0)
Operating temperature -10 °C to 50 °C (14 °F to 122 °F)
Range Resolution Operating error
0.200 - 1.000 mA 0.001 mA ± 2.5 % rdg ± 0.05 mA
1.00 - 10.00 mA 0.01 mA ± 2.5 % rdg ± 0.05 mA
10.0 - 100.0 mA 0.1 mA ± 2.0 % rdg ± 0.3 mA
100 - 1000 mA 1 mA ± 2.0 % rdg ± 3 mA
Current A~
(Autorange, 50/60 Hz, true-rms, crest factor < 3.0 )
Operating temperature -10 °C to 50 °C (14 °F to 122 °F)
Range Resolution Operating error
0.20 - 15.00 A0.01 A ± 2.0 % rdg ± 0.03 A
15.00 - 30.00 A0.01 A ± 3.0 % rdg ± 0.03 A
HI/LO Limit Evaluation
Values from 0 Ω to 1510 Ω may be preset for automatic comparison. If the measured value is outside of the limit an audible and visual signal is given.
Recording
Measured values can be saved or logged with a defined time interval from 1 to 255 s. Recorded values may then be recalled on the display of the instrument.



   
  Welcome | Companies | Search by Type | How To Order | Leasing | About Us  
  Tequipment.NET
205 Westwood Ave
Long Branch, NJ 07740
For our Electronic Whiteboard division visit www.touchboards.com
BBBOnline Reliability Seal. Tequipment.NET
Phone: 1-877-742-TEST (8378) / 732-222-7077
Fax: (732) 222-7088
E-mail: salesteam@Tequipment.NET