| RA 3-pole ground resistance measurement (IEC 1557-5) |
| Measuring Voltage |
Fluke 1623 Vm = 48 V ac Fluke 1625 Vm = 20/48 V ac |
| Short circuit current |
Fluke 1623 > 50 mA Fluke 1625 250 mA ac |
| Measure frequency |
Fluke 1623 128 Hz Fluke 1625 94, 105, 111, 128Hz |
| Resolution |
Fluke 1623 0.001 Ω to 10 Ω Fluke 1625 0.001 Ω to 100 Ω |
| Measuring range |
Fluke 1623 0.001 Ω to 19.99 kΩ Fluke 1625 0.001 Ω to 299.9 kΩ |
| Intrinsic error |
Fluke 1623 ± (2 % of reading + 3 digit) Fluke 1625 ± (2 % of reading + 2 d) |
| Operating error |
Fluke 1623 ± (5 % of reading + 3 d) Fluke 1625 ± (5 % of reading + 5 d) |
| RA 4-pole ground resistance measurement (IEC 1557-5) |
| Measuring Voltage |
Fluke 1623 Vm = 48 V ac Fluke 1625 Vm = 20/48 V ac |
| Short circuit current |
Fluke 1623 > 50 mA Fluke 1625 250 mA ac |
| Measure frequency |
Fluke 1623 128 Hz Fluke 1625 94, 105, 111, 128Hz |
| Resolution |
Fluke 1623 0.001 Ω to 10 Ω Fluke 1625 0.001 Ω to 100 Ω |
| Measuring range |
Fluke 1623 0.001 Ω to 19.99 kΩ Fluke 1625 0.001 Ω to 299.9 kΩ |
| Intrinsic error |
Fluke 1623 ± (2 % of reading + 3 d) Fluke 1625 ± (2 % of reading + 2 d) |
| Operating error |
Fluke 1623 ± (5 % of reading + 3 d) Fluke 1625 ± (5 % of reading + 5 d) |
| RA 3-pole ground resistance measurement with current clamp |
| Measuring Voltage |
Fluke 1623 Vm = 48 V ac Fluke 1625 Vm = 20/48 V ac |
| Short circuit current |
Fluke 1623 > 50 mA Fluke 1625 250 mA ac |
| Measure frequency |
Fluke 1623 128 Hz Fluke 1625 94, 105, 111, 128Hz |
| Resolution |
Fluke 1623 0.001 Ω to 10 Ω Fluke 1625 0.001 Ω to 10 Ω |
| Measuring range |
Fluke 1623 0.001 Ω to 19.99 kΩ Fluke 1625 0.001 Ω to 29.99 kΩ |
| Intrinsic error |
Fluke 1623 ± (7 % of reading + 3 d) Fluke 1625 ± (7 % of reading + 2 d) |
| Operating error |
Fluke 1623 ± (10 % of reading + 5 d) Fluke 1625 ± (10 % of reading + 5 d) |
| RA 4-pole selective ground resistance measurement with current clamp |
| Measuring Voltage |
Fluke 1623 Vm = 48 V ac Fluke 1625 Vm = 20/48 V ac |
| Short circuit current |
Fluke 1623 > 50 mA Fluke 1625 250 mA ac |
| Measure frequency |
Fluke 1623 128 Hz Fluke 1625 94, 105, 111, 128Hz |
| Resolution |
Fluke 1623 0.001 Ω to 10 Ω Fluke 1625 0.001 Ω to 10 Ω |
| Measuring range |
Fluke 1623 0.001 Ω to 19.99 kΩ Fluke 1625 0.001 Ω to 29.99 kΩ |
| Intrinsic error |
Fluke 1623 ± (7 % of reading + 3 d) Fluke 1625 ± (7 % of reading + 2 d) |
| Operating error |
Fluke 1623 ± (10 % of reading + 5 d) Fluke 1625 ± (10 % of reading + 5 d) |
| Stakeless ground loop measurement |
| Measuring Voltage |
Fluke 1623 Vm = 48 V ac Fluke 1625 Vm = 20/48 V ac |
| Measure frequency |
Fluke 1623 128 Hz (125 Hz on request) Fluke 1625 94, 105, 111, 128Hz |
| Noise current (Iext) |
Fluke 1623 Max. Iext = 10 A (ac) (RA < 20 Ω) Max. Iext = 2 A (ac) (RA < 20 Ω) Fluke 1625 Max. Iext = 3 A |
| Resolution |
Fluke 1623 0.001 Ω to 0.1 Ω Fluke 1625 0.001 Ω to 10 Ω |
| Measuring range |
Fluke 1623 0.001 Ω to 199.9 kΩ Fluke 1625 0.001 Ω to 29.99 kΩ |
| Intrinsic error |
Fluke 1623 ± (7 % of reading + 3 d) Fluke 1625 ± (7 % of reading + 2 d) |
| Operating error |
Fluke 1623 ± (10 % of reading + 5 d) Fluke 1625 ± (10 % of reading + 5 d) |
| Environmental Specifications |
| Working temperature |
-10 °C to +50 °C |
| Operating Temperature |
0 °C to +35 °C |
| Nominal temperature |
+18 °C to +28 °C |
| Storage Temperature |
Fluke 1623 -20 °C to +60 °C Fluke 1625 -30 °C to +60 °C |
| Climatic class |
C1 (IEC 654-1), -5 °C to + 45 °C, 5 % to 95 % RH |
| Protection Class |
IP56 for case, IP40 for battery door according to EN 60529 |
| Safety Specifications |
| Safety Rating |
CAT II, 300 V |
| Mechanical & General Specifications |
| Display |
Fluke 1623 1999 digit LCD – display with special symbols, digit height 25 mm, fluorescent backlight
Fluke 1625 2999 Digit LCD – 7 segment liquid crystal display with special symbols and backlight |
| Size |
133 mm x 187 mm x 250 mm |
| Weight |
Fluke 1623 + 1625 1.1 kg (including batteries) |
| Warranty |
Two years |
| Battery Life |
Fluke 1623 Typical > 3000 measurements
Fluke 1625 Typical 3000 measurements (RE+RH <e; 1 kΩ) Typical 6000 measurements (RE+RH <e; 10 kΩ) |