| AC/DC
Voltage Measurements |
| Accuracy |
Range: 600.0 V
Resolution: 0.1 V
50 Hz to 400 Hz ± (% of Rdg + Digits): ±(2
% + 3) |
| Input
Impedance |
3
MΩ (nominal), < 100 pF |
| Common
mode rejection ratio (1 kΩ unbalanced) |
> 60 dB at dc, 50 or 60 Hz |
| Overload
Protection |
600
V rms or dc |
| Earth
bond resistance measurement |
| Range/Resolution |
20.00 Ω 0.01 Ω
200.0 Ω 0.1 Ω
2000 Ω 1.0 Ω
20.00 kΩ 0.01 kΩ |
| Accuracy |
±(1.5%
+ 3) |
| Overload
Protection |
2 V rms or dc |
| Open
Circuit Test Voltage |
>
4.0 V, < 8 V |
| Short
circuit current |
>
200.0 mA |
| Insulation
Specifications |
| Measurement
Range |
0.01 MΩ to 2000 MΩ |
| Test
voltages |
500 V, 1000V |
| Test
Voltage Accuracy |
+
20 %, - 0 % |
| Short
circuit current |
1
mA nominal |
| Auto
Discharge |
Discharge
time < 0.5 second for C = 1 µF or less |
| Live
circuit indicator |
Inhibit test if terminal voltage > 30 V prior to initialization
of test |
| Maximum
Capacitive Load |
Operable
with up to 1 µF load |
| Measure
Accuracy |
50
V: ±(3 % + 5)
100 V: ±(3 % + 5)
250 V: ±(1.5 % + 5)
500 V: ±(1.5 % + 5)
1000 V: ±(1.5 % + 5) to 2000 MΩ, ±(10
% + 3) above 2000 MΩ |
| General
Specifications |
| Maximum
voltage applied to any terminal: |
600 V ac rms or dc |
| Storage
temperature |
-40 °C to 60 °C (-40 °F to 140 °F) |
| Operating
temperature |
-20 °C to 55 °C (-4 °F to 131 °F) |
| Temperature
Coefficient |
0.05 x (specified accuracy) per °C for temperatures < 18
°C or > 28 °C (< 64 °F or > 82 °F) |
| Relative
Humidity |
0
% to 95 % @ 10 °C to 30 °C (50 °F to 86 °F)
0 % to 75 % @ 30 °C to 40 °C (86 °F to 104 °F)
0 % to 40 % @ 40 °C to 55 °C (104 °F to 131 °F) |
| Vibration |
Random,
2 g, 5-500 Hz per MIL-PRF-28800F, Class 2 instrument |
| Shock |
1
meter drop per IEC 61010-1 2nd Edition (1 meter drop test, six sides,
oak floor) |
| Electromagnetic
compatibility |
In
an RF field of 3 V/M, accuracy = specified accuracy (EN 61326-1:1997) |
| Safety |
Complies
with ANSI/ISA 82.02.01 (61010-1) 2004, CAN/CSA-C22.2 NO. 61010-1-04,
and IEC/EN 61010-1 2nd Edition for measurement category IV 600 V
(CAT IV) |
| Certifications |
CSA
per standard CSA/CAN C22.2 No. 61010.1-04; TUV per standard IEC/EN
61010-1 2nd Edition |
| Batteries |
Four
AA batteries (NEDA 15A or IEC LR6) |
| Battery
life |
Insulation
test use: Tester can perform at least 1000 insulation tests
with fresh alkaline batteries at room temperature. These are standard
tests of 1000 V into 1 MΩ with a duty cycle of 5 seconds on
and 25 seconds off.
Resistance measurements: Tester can perform at
least 2500 earth bond resistance measurements with fresh alkaline
batteries at room temperature. These are standard tests of 1 Ω
with a duty cycle of 5 seconds on and 25 seconds off. |
| Size |
5.0
cm H x 10.0 cm W x 20.3 cm L (1.97 in H x 3.94 in W x 8.00 in L) |
| Weight
|
550
g (1.2 lb) |
| IP
Rating |
IP40 |
| Altitude
|
Operating:
2000 m CAT IV 600 V, 3000 m CAT III 600 V
Non-operating (storage): 12,000 m |
| Over-range
capability |
110
% of range |
| Included
accessories |
TL224
Test Leads, TP74 Test Probes, clips PN 1958654 (red) and PN 1958646
(black), holster and remote probe |