Tequipment
An InterWorld Highway, LLC Company
Call Us 1.877.571.7901
Fluke Accessoires
 
 
 
 
 

Fluke 1738/EUS 3-Phase Portable Advanced Power Logger EU/US Version

Fluke 1738/EUS
Catalog #: 4563577
         
0 reviews
POWER LOGGER, EU/US ADVANCED VERSION
Free Gift From Fluke With Purchase

Features

  • 3-Phase Energy Logger EU/US Version
  • Key measurements: Automatically capture and log voltage, current, power, harmonics and associated power quality values.
  • Fluke Connect® compatible*: View data locally on the instrument or via Fluke Connect mobile app and desktop software.
  • Convenient instrument powering: Power instrument directly from the measured circuit.
  • Highest safety rating in the industry: 600 V CAT IV/1000 V CAT III rated for use at the service entrance and downstream.
  • Measure all three phases and neutral: With included 4 flexible current probes.
  • Comprehensive logging: More than 20 separate logging sessions can be stored on the instruments. In fact, all measured values are automatically logged so you never loose measurement trends. They can even be reviewed during logging sessions and before downloading for real-time analysis.
  • Capture dips, swells, and inrush currents: Includes event waveform snapshot and high resolution RMS profile, along with date, timestamp and severity to help pinpoint potential root causes of power quality issues.
  • Bright, color touch screen: Perform convenient in-the-field analysis and data checks with full graphical display.
  • Optimized user interface: Capture the right data every time with quick, guided, graphical setup and reduce uncertainty about your connections with the intelligent verification function.
  • Complete "in-the-field" setup through the front panel or Fluke Connect App: No need to return to the workshop for download nd setup or to take a computer to the electrical panel.
  • Energy Analyze Plus application software: Download and analyze every detail of energy consumption and power quality state of health with our automated reporting.
  • Create IEEE 519 Reports: Compliant reports provide you more insight into harmonic levels, voltage and current distortion, and load current (license required (IEEE519/Report)).
Loading Prices
Sale: $5,499.99
  + Free shipping over $99

Marketing-Promo-Add-to-Cart-176x92-3-items

Loading Callouts
0% APR Financing Available - Eligibility Subject to Applicant's Creditwothiness Request a Quote
Loading Series Compare

Compare Products in this Series

Product Name Input(power loggers) Type(Power loggers) Maximum Current AC Price
1738/EUS
1738/EUS
POWER LOGGER, EU/US ADVANCED VERSION
Single Phase, Three Phase Digital, Portable Hand Held 6000 A Edu Price Standard Price Gov't Price
1736/B
1736/B
3-PHASE ENERGY LOGGER, BASIC VERSION - No CTs
Single Phase, Three Phase Digital, Portable Hand Held 6000 A Edu Price Standard Price Gov't Price
1736/EUS
1736/EUS
POWER LOGGER, EU/US VERSION
Single Phase, Three Phase Digital, Portable Hand Held 6000 A Edu Price Standard Price Gov't Price
1738/B
1738/B
3-PHASE ENERGY LOGGER, ADVANCED VERSION, NO CTs included
Single Phase, Three Phase Digital, Portable Hand Held 6000 A Edu Price Standard Price Gov't Price
1732/B
1732/B
ENERGY LOGGER, BASIC VERSION
Single Phase, Three Phase Digital, Portable Hand Held 6000 A Edu Price Standard Price Gov't Price
1732/EUS
1732/EUS
ENERGY LOGGER, EU/US VERSION
Single Phase, Three Phase Digital, Portable Hand Held 6000 A Edu Price Standard Price Gov't Price
1734/B
1734/B
ENERGY LOGGER, ADVANCED VERSION NO FLEXIS
Single Phase, Three Phase Digital, Portable Hand Held 6000 A Edu Price Standard Price Gov't Price
1734/EUS
1734/EUS
ENERGY LOGGER, EU/US ADVANCED VERSION
Single Phase, Three Phase Digital, Portable Hand Held 6000 A Edu Price Standard Price Gov't Price

Product Information

Fluke 1738/EUS Advanced Power Logger

The Fluke 1738 Three-Phase Power Logger is designed to give users the information they need to make crucial power qualiy and energy decisions as efficently and quickly as possible. Fluke has paired the 1738 with its Fluke Connect® mobile app and desktop software to give users immediate access to critical information anywhere. Out of the box, the 1738 is capable of automatically capturing and storing more than 500 PQ paramters.

Access and share data remotely with your team via the Fluke Connect® app so you can maintain safer working distances and make critical decisions in real-time, reducing the need for protective equipment, site visits and check-ins. Quickly and easily chart and graph measurements with the included Fluke Energy Analyze Plus software package.

Fluke 1736 Power Quality Analyzer

Key Features

  • Measure all three phases and neutral with included 4 flexible current probes.
  • Comprehensive logging:More than 20 separate logging sessions can be stored on the instruments. In fact, all measured values are automatically logged so you never loose measurement trends. They can even be reviewed during logging sessions and before downloading for real-time analysis.
  • Capture dips, swells, and inrush currents: includes event waveform snapshot and high resolution RMS profile, along with date, timestamp and severity to help pinpoint potential root causes of power quality issues.
  • Fully integrated logging: Connect other Fluke Connect devices to the Fluke 1738 to simultaneously log up to two other measurement parameters, virtually any parameter available on a Fluke Connect wireless digital multimeter or module.*
  • Energy Analyze Plus application software: Download and analyze every detail of energy consumption and power quality state of health with our automated reporting.
  • Bright, color touch screen: Perform convenient in-the-field analysis and data checks with full graphical display.
  • Optimized user interface: Capture the right data every time with quick, guided, graphical setup and reduce uncertainty about your connections with the intelligent verification function.
  • Measure all three phases and neutral with included 4 flexible current probes.

Applications

Load Studies:Ensure system capacity before increasing load.

Energy Assessments:Verify energy consumption after system changes in order to test energy saving measures.

Harmonics Measurements:Uncover and identify harmonics issues before they damage critical equipment.

Voltage and Current Event Capture:monitor for dips, swells and inrush currents that cause false resets or nuisance circuit breaker tripping.

Fluke1736-1738_img1_tn
Conduct multiple studies with one instrument; download while studies are in progress via USB stick or Fluke Connect mobile app. Suitable for NEC 220 load studies.
 
Fluke1736-1738_img2_tn
Discover the source of voltage and current distortion that may be affecting your equipment
 
Fluke1736-1738_img3_tn
Capture voltage events and inrush currents with pre-defined thresholds.
 
Fluke1736-1738_img3_tn
Simple setup means all available measured parameters are automatically selected during logging so you can be sure you have the data you need, even before you know you need it.
 

Easy to Use

The four current probes are connected separately; the instrument automatically detects and scales the probes. The thin current probes are designed to easily get through tight conductor spacing and are easily set to 150 or 1500 A for high accuracy in nearly any application. An innovative tangle-free flat voltage lead makes connection simple and reliable and the instrument’s intelligent ‘Verify Connection’ feature automatically checks to make sure the instrument is connected correctly and can digitally correct common connection issues without having to disconnect measurement leads. The detachable power supply can be conveniently and safely powered directly from the measured circuit—no more searching for power outlets or having to run multiple extension cords to the logging location.

Intelligent verification function that digitally corrects most common measurement connections.

Analysis and Reporting

Capturing logged data is just one part of the task. Once you have the data, you need to create useful information and reports that can be easily shared and understood by your organization or customers. Fluke Energy Analyze Plus software makes that task as simple as possible. With powerful analysis tools and the ability to create customized reports in minutes you’ll be able to communicate your findings and quickly solve problems so you can optimize system reliability and savings.

What's In The Box

  • 1738 Power Logger
  • WiFi/Bluetooth adapter (1738 only)
  • USB flash drive (4GB)
  • USB Cable
  • 3PHVL-173 Flat Cable
  • 1x red, 1x black 0.1m cable
  • 1x red, 1x black 1.5m lead
  • Alligator clips
  • C173x Soft Case
  • Color Coding set
  • i173X- flex1500 12" (4)
  • Magnetic Probes (1738 only)
  • Magnetic hanger kit (1738 only
  • Line cord

Specifications

Specifications
Accuracy
Parameter Range Max. resolution Intrinsic accuracy at reference conditions
(% of reading + % of full scale)
Voltage 1000 V 0.1 V ± (0.2% + 0.01%)
Current i17xx-flex 1500 12”
 
150 A
1500 A
0.1 A
1 A
± (1% + 0.02%)
± (1% + 0.02%)
i17xx-flex 3000 24
 
300 A
3000 A
1 A
10 A
± (1% + 0.03%)
± (1% + 0.03%)
i17xx-flex 6000 36”
 
600 A
6000 A
1 A
10 A
± (1.5 % + 0.03%)
± (1.5 % + 0.03%)
i40s-EL clamp 4 A
40 A
1 mA
10 m A
± (0.7% + 0.02 %)
± (0.7% + 0.02 %)
Frequency 42.5 Hz to 69 Hz 0.01 H z ± (0.1%)
Aux input ± 10 V dc 0.1 mV ± (0.2% + 0.02%)
Voltage min/max 1000 V 0.1 V ± (1% + 0.1%)
Current min/max defined by
accessory
defined by
accessory
± (5% + 0.2%)
THD on voltage 1000% 0.1% ± 0.5
THD on current 1000% 0.1% ± 0.5
Voltage harmonics 2nd ...50th 1000 V 0.1 V ≥ 10 V: ± 5% of reading
< 10 V: ± 0.5V
Current harmonics 2nd ...
50th
defined by
accessory
defined by
accessory
≥ 3% of current range: ± 5% of reading
< 3% of current range: ± 0.15% of range
Unbalance 100% 0.1% ± 0.2
 
Intrinsic uncertainty ± (% of reading + % of range)1
Parameter Influence
quantity
iFlex1500 -12
150A/1500A
iFlex3000-24
300A/3000A
iFlex6000-36
600/6000A
i40s-EL
4A/40A
Active Power PActive Energy Ea PF = 0.99 1.2% + 0.005% 1.2% + 0.0075% 1.7% + 0.0075% 1.2% + 0.005%
Apparent Power S Apparent Energy Eap 0 = PF = 1 1.2% + 0.005% 1.2% + 0.0075% 1.7% + 0.0075% 1.2% + 0.005%
Reactive Power Q Reactive Energy Er 0 = PF = 1 2.5 % of measured apparent power
Power Factor PF Displacement Power FactorDPF/cosφ ± 0.025
Additional uncertainty in % of range1 V P-N > 250 V 0.015% 0.0225% 0.0225 % 0.015%
 
Electrical specifications
Power supply
Voltage range 100 V to 500 V using safety plug input when powering from the measurement circuit
100 V to 240 V using standard power cord (IEC 60320 C7)
Power consumption Maximum 50 VA (max. 15 VA when powered using IEC 60320 input)
Efficiency ≥ 68.2 % (in accordance with energy efficiency regulations)
Maximum no-load consumption < 0.3 W only when powered using IEC 60320 input
Mains power frequency 50/60 Hz ± 15 %
Battery Li-ion 3.7 V, 9.25 Wh, customer-replaceable
On-battery runtime Four hours in standard operating mode, up to 5.5 hours in power saving mode
Charging time < 6 hours
Data acquisition
Resolution 16-bit synchronous sampling
Sampling frequency 10.24 kHz at 50/60 Hz, synchronized to mains frequency
Input signal frequency 50/60 Hz (42.5 to 69 Hz)
Circuit types 1-?, 1-? IT, split phase, 3-? delta, 3-? wye, 3-? wye IT, 3-? wye balanced, 3-?
Aron/Blondel (2-element delta), 3-? delta open leg, currents only (load studies)
Data storage Internal flash memory (not user replaceable)
Memory size Typical 10 logging sessions of 8 weeks with 1-minute intervals and 500 events 1
Basic interval
Measured parameters Voltage, current, aux, frequency, THD V, THD A, power, power factor, fundamental
power, DPF, energy
Averaging interval User selectable: 1 sec, 5 sec, 10 sec, 30 sec, 1 min, 5 min, 10 min, 15 min, 30 min
Averaging time min/max values Voltage, Current: Full cycle RMS updated every half cycle (URMS1/2 according to
IEC61000-4-30
Aux, Power: 200ms
Demand Interval (Energy Meter Mode)
Measured parameters Energy (Wh, varh, VAh), PF, maximum demand, cost of energy
Interval User selectable: 5 min, 10 min, 15 min, 20 min, 30 min, off
Power quality measurements
Measured parameter Voltage, frequency, unbalance, voltage harmonics, THD V, current, harmonics, THD
A, TDD
Averaging interval 10 min
Individual harmonics 2nd ...50th harmonic
Total harmonic distortion Calculated on 50 harmonics
Events Voltage: dips, swells, interruptions, current: inrush current
Triggered recordings Full cycle RMS updated every half cycle of voltage and current (Urms1/2 according
to IEC61000-4-30)
Waveform of voltage and current
 
Electrical specifications cont.
Standards Compliance
Harmonics IEC 61000-4-7: Class 1
IEEE 519 (short time harmonics)
Power quality IEC 61000-4-30 Class S, IEC62586-1 (PQI-S device)
Power IEEE 1459
Power quality compliance EN50160 (for measured parameters)
Interfaces
USB-A File transfer via USB flash drive, firmware updates, max. supply current: 120 mA
WiFi File transfer and remote control via direct connection or WiFi infrastructure
Bluetooth Read auxiliary measurement data from Fluke Connect ® 3000 series modules
(requires 1738, or 1736 upgrade option)
USB-mini Data download device to PC
Voltage inputs
Number of inputs 4 (3 phases and neutral)
Maximum input voltage 1000 Vrms, CF 1.7
Input impedance 10 MΩ
Bandwidth 42.5 Hz - 3.5 kHz
Scaling 1:1 and variable
Measurement category 1000 V CAT III/600 V CAT IV
Current inputs
Number of inputs 4, mode selected automatically for attached sensor
Input voltage Clamp input: 500 mVrms/50 mVrms; CF 2.8
Rogowski coil input 150 mVrms/15 mVrms at 50 Hz, 180 mVrms/18 mVrms at 60 Hz; CF 4; all at nominal
probe range
Range 1 A to 150 A/10 A to 1500 A with thin flexible current probe i17XX-flex1500 12”
3 A to 300 A/30 A to 3000 A with thin flexible current probe i17XX-flex3000 24”
6 A to 600 A/60 A to 6000 A with thin flexible current probe i17XX-flex6000 36”
40 mA to 4 A/0.4 A to 40 A with 40 A clamp i40s-EL
Bandwidth 42.5 Hz - 3.5 kHz
Scaling 1:1 and variable
Auxiliary inputs
Number of inputs 2
Input range 0 to ± 10 V dc, 1 reading/s
Scale factor Format: mx + b (gain and offset) user configurable
Displayed units User configurable (7 characters, for example, °C, psi, or m/s)
Wireless connection
Number of inputs 2
Supported modules Fluke Connect ® 3000 series
Acquisition 1 reading/s
 
Environmental specifications
Operating temperature -10 °C to +50 °C (14 °F to 122 °F)
Storage temperature -20 °C to +60 °C (-4 °F to 140 °F), with battery: -20 °C to +50 °C (-4 °F to 122 °F)
Operating humidity 10 °C to 30 °C (50 °F to 86 °F) max. 95 % RH
30 °C to 40 °C (86 °F to 104 °F) max. 75 % RH
40 °C to 50 °C (104 °F to 122 °F) max. 45 % RH
Operating altitude 2000 m (up to 4000 m derate to 1000 V CAT II/600 V CAT III/300 V CAT IV)
Storage altitude 12,000 m
Enclosure IP50 in accordance with EN60529
Vibration MIL-T-28800E, Type 3, Class III, Style B
Safety IEC 61010-1
    IEC Mains Input:Overvoltage Category II, Pollution Degree 2
    Voltage Terminals:Overvoltage Category IV, Pollution Degree 2
IEC 61010-2-031:CAT IV 600 V / CAT III 1000 V
Electromagnetic compatibility (EMC) EN 61326-1: Industrial CISPR 11: Group 1, Class A
Korea (KCC):Class A Equipment (industrial broadcasting and
communication equipment)
USA (FCC):47 CFR 15 subpart B. This product is considered an exempt device per
clause 15.103
Temperature coefficient 0.1 x accuracy specification/°C
General specifications
Color LCD display 4.3-inch active matrix TFT, 480 pixels x 272 pixels, resistive touch panel
Warranty Instrument and power supply: Two-years (battery not included)
Accessories: one-year
Calibration cycle: two-years
Dimensions Instrument: 19.8 cm x 16.7 cm x 5.5 cm (7.8 in x 6.6 in x 2.2 in)
Power supply: 13.0 cm x 13.0 cm x 4.5 cm (5.1 in x 5.1 in x 1.8 in)
Instrument with power supply attached: 19.8 cm x 16.7 cm x 9 cm
(7.8 in x 6.6 in x 3.5 in)
Weight Instrument: 1.1 kg (2.5 lb)
Power supply: 400 g (0.9 lb)
Tamper protection Kensington lock slot
i17xx-flex 1500 12” Flexible Current Probe specifications
Measuring range 1 to 150 A ac/10 to 1500 A ac
Nondestructive current 100 kA (50/60 Hz)
Intrinsic error at reference condition* ± 0.7 % of reading
Accuracy 173x + iFlex ± (1 % of reading + 0.02 % of range)
Temperature coefficient over operating temperature range 0.05 % of reading/°C 0.09 % of reading/°F
Working voltage 1000 V CAT III, 600 V CAT IV
Probe cable length 305 mm (12 in)
Probe cable diameter 7.5 mm (0.3 in)
Minimum bending radius 38 mm (1.5 in)
Output cable length 2 m (6.6 ft)
Weight 115 g
Probe cable material TPR
Coupling material POM + ABS/PC
Output cable TPR/PVC
Operating temperature -20 °C to +70 °C (-4 °F to 158 °F) temperature of
conductor under test shall not exceed 80 °C (176 °F)
Temperature, non-operating -40 °C to +80 °C (-40 °F to 176 °F)
Relative humidity, operating 15 % to 85 % non-condensing
IP rating IEC 60529:IP50
Warranty One-year
 
Model features
  1736 Power Logger 1738 Power Logger
  FLUKE-1736/B FLUKE-1736/EUS   FLUKE-1738/B FLUKE-1738/EUS  
Model Power logger basic version Power logger (EU and US)   Power logger advanced version Power logger advance version (EU and US)  
Functions
PQ Health (EN50160 analysis) Opt. Opt.    
IEEE 519 reporting Opt. Opt.   Opt. Opt.  
Fluke Connect ® module support
(up to 2 modules**)
Opt. Opt.    
Recording
Trend    
Waveform Snapshots + RMS profile Opt. Opt.    
Communication
USB (mini B)    
WiFi download of instrument data    
WiFi download via WiFi access point (requires registration)** Opt. Opt.   Opt. Opt.  
Included Accessories
WiFi only adapter** -   - -  
WiFi and BLE adapter** Opt. Opt.   Opt.  
USB flash drive (4GB)    
USB Cable    
3PHVL-173 Flat Cable    
1x red, 1x black 0.1m cable    
1x red, 1x black 1.5m lead    
Alligator clips 4 4   4 4  
C173x Soft Case    
Color Coding set    
173x-Hanger kit Opt. Opt.    
MP1-Magnet Probe Opt. Opt.   4 4  
i173X-flex1500 12” Opt. 4   Opt. 4  
Line cord EU, UK,
US, AU, BR
EU, US, UK   EU, UK,
US, AU, BR
EU, US, UK  
Compatible Optional Accessories
173X- AUX analog adapter    
i17XX-flex1500 12” Current Probe    
i17XX-flex3000 24” Current Probe    
i17XX-flex6000 36” Current Probe    
i40s-EL Current Clamp    
IEEE 519 reporting opt    
1736 to 1738 upgrade
(1736/UPGRADE)
   

Fluke 1738/EUS Product Specifications Summary:
(for full specs please see the full specs tab or the data sheet)

Power Measurement/Power Loggers Template

Input(power loggers) What's This?Single Phase, Three Phase
Type(Power loggers)Digital, Portable Hand Held
Maximum Current AC What's This?6000 A 
Maximum Voltage AC1000 V 
True RMS What's This?Yes
Power Quality What's This?No
Current Input Channels4
Voltage Input Channels4
Measurement Frequency50 Hz, 60 Hz
Display (Energy Management)Digital, Graphical
Transient Capture What's This?No
Displays Waveform What's This?Yes
Energy What's This?Yes
Phasor Diagrams What's This?No
Power Factor (Power Quality) What's This?Yes
Harmonics What's This?Yes 
Total Harmonic Distortion What's This?Yes
Current Clamps IncludedYes 
Blue Tooth CompatableYes
CAT Rating What's This?IV 
CAT Voltage Rating (V) What's This?600V

Test Equipment General Attributes

Unique Features• Measure all three phases and neutral with included 4 flexible current probes.
• Comprehensive logging: More than 20 separate logging sessions can be stored on the instruments. In fact, all measured values are automatically logged so you never loose measurement trends. They can even be reviewed during logging sessions and before downloading for real-time analysis.
• Capture dips, swells, and inrush currents: includes event waveform snapshot and high resolution RMS profile, along with date, timestamp and severity to help pinpoint potential root causes of power quality issues.
• Bright, color touch screen: Perform convenient in-the-field analysis and data checks with full graphical display.
• Optimized user interface: Capture the right data every time with quick, guided, graphical setup and reduce uncertainty about your connections with the intelligent verification function.
• Complete “in-the-field” setup through the front panel
or Fluke Connect App: no need to return to the workshop
Warranty2 YEARS
Calibration IncludedNone
Power Supply Voltage120V/220V Universal
Data Logging What's This?Yes
Interfaces I/O Bluetooth, Wifi, USB
StorageInternal Memory 
IP Rating What's This?IP50
Product Weight3 LBS
Country of OriginRomania

Reviews

Fluke 1738/EUS Customer Reviews

0 Reviews
5 stars
 (0)
4 stars
 (0)
3 stars
 (0)
2 stars
 (0)
1 star
 (0)
 
 
 
 
 
Average Customer Review
         
0 reviews
0 customer reviews
Share your thoughts with other customers
Create your own review
 
Most Helpful First | Newest First      Prev Page
 
Prev Page
 

Q & A

Q: How many input channels does the Fluke 1738 have?
A:
 The 1738 has 4 voltage inputs and 4 current inputs. The /EUS package comes with (4) i173x 1500A Flex CTs for AC current.  The /B package only comes with voltage leads. If you have current probes from compatible Fluke meter, or want to get current probes that better meet your needs, please check the Accessories tab. 

Q: Can you create IEEE519 compliant reports with the Fluke 1738?
A:
Yes, you can. To comply with the latest IEEE 519 standard reporting requirements, you will need to order the optional software key IEEE519/Report (see accessories list).

Accessories

Loading Accessories

Fluke Price List

Megger MPQ1000 Handheld Power Quality Analyzer
Hioki Clampon HiTester
X


secured website

Interworld Highway, LLC dba TEquipment.NET

205 Westwood Avenue. Long Branch, NJ 07740

Privacy Policy | Terms and Conditions | Site Map

Copyright© 2016 Interworld Highway, LLC

secured website
We Price Match!

Give our sales team a call at 877.571.7901 (Toll Free) or 732.222.7077 (International) and we'll match any competitor's price.

X