Fluke 1587 FC 2-in-1 Insulation Multimeter with Fluke Connect

Fluke 1587 FC
Catalog #: 4691215
         
5 of 5
2-IN-1 INSULATION MULTIMETER

Click to Listen - Top Features

Features

  • Large display with backlight
  • Insulation test: 0.01 MΩ to 2 GΩ
  • Insulation test voltages: 50 V, 100 V, 250 V, 500 V, 1000 V
  • Live circuit detection prevents insulation test if voltage >30 V is detected
  • Auto-discharge of capacitive voltage
  • AC/DC voltage, DC milliVolts, AC/DC milliamps, Resistance, Continuity
  • Filter for motor drive measurements
  • Capacitance, diode test, temperature, Min/Max, frequency
  • Auto power off to save battery power
  • CAT III 1000 V, CAT IV 600 V measurement category
  • 3-Year warranty
Fluke Connect Features:
  • Fluke Connect allows you to wirelessly transfer data from your existing Fluke tools to your smart phone
  • Fits over the IR port of your existing Fluke tools
  • Upgradeable by USB
  • Immediately enables you to graph, save, and share the tool’s readings with your team from your smart phone
Supported smart phones:
  • Android™ 4.3 & up
  • iPhone® 4s & later
Loading Prices
List Price: $799.99
Sale: $719.99
  + Free shipping over $99

FREE
IWH C-66 High Quality Meter Case


Marketing-Promo-Add-to-Cart-176x92-3-items

Loading Callouts
Request a Quote
Loading Series Compare

Compare Products in this Series

Product Name Type IR Test Voltage Maximum Insulation Resistance Availability Price  
1587 FC
1587 FC
2-IN-1 INSULATION MULTIMETER
Battery 1,000 V, 100 V, 250 V, 50 V, 500 V 2 G Ohms Availability
in stock!
Edu Price Standard Price Gov't Price
1587 T
1587 T
50V/100V Telecom Insulation Multimeter
Battery 100 V, 50 V 100 M Ohms (0.1 G Ohms) Availability
in stock!
Edu Price Standard Price Gov't Price
1577
1577
INSULATION MULTIMETER
Battery 1,000 V, 500 V 600 M Ohms (0.6 G Ohms) Availability
in stock!
Edu Price Standard Price Gov't Price
1587KIT/62MAX+ FC
1587KIT/62MAX+ FC
2-IN-1 ADV ELEC TR INS MULT KIT W/62MAX+ I400
Battery 1,000 V, 100 V, 250 V, 50 V, 500 V 2 G Ohms Availability
in stock!
Edu Price Standard Price Gov't Price
1587/I400 FC
1587/I400 FC
2-IN-1 INSULATION MULTIMETER W/CLAMP
Battery 1,000 V, 100 V, 250 V, 50 V, 500 V 2 G Ohms Availability
in stock!
Edu Price Standard Price Gov't Price
1587/MDT FC
1587/MDT FC
2-IN-1 ADV MOTOR And DRIVE KIT W/9040, I400
Battery 1,000 V, 100 V, 250 V, 50 V, 500 V 2 G Ohms Availability
in stock!
Edu Price Standard Price Gov't Price
1587 FC-NIST
1587 FC-NIST
2-IN-1 INSULATION MULTIMETER ​with NIST Calibration Included
Battery 1,000 V, 100 V, 250 V, 50 V, 500 V 2 G Ohms Availability
in stock!
Edu Price Standard Price Gov't Price
1503
1503
INSULATION TESTER
Battery 1,000 V, 500 V 2 G Ohms Availability
in stock!
Edu Price Standard Price Gov't Price
1507
1507
INSULATION TESTER
Battery 1,000 V, 100 V, 250 V, 50 V, 500 V 10 G Ohms Availability
in stock!
Edu Price Standard Price Gov't Price

Product Information

Fluke 1587 FC Insulation Multimeter

Fluke_1587_FC_tn
 


FLUKE CONNECT COMPATIBLE
Download the free Fluke Connect ® app from iTunes or Google Play to enable graphs within the Pi/DAR function, memory storage, and temperature compensation.

DISPLAY
Large, 6000-count back-lit display.

VFD
Low-pass filter for accurate motor drive measurements.

INSULATION TEST VOLTAGES
1587 FC: 50 V, 100 V, 250 V, 500 V, 1000 V
1577: 500 V, 1000 V

WARRANTY
Three-year standard warranty; extendable to five-years through product registration within 45 days of purchase*



Fluke1587FC
See it. Save it. Share it.
All the facts, right in the field.


Fluke Connect ® with ShareLive™ video call is the only wireless measurement system that lets you stay in contact with your entire team without leaving the field*. The Fluke Connect mobile app is available for iPhone models 4S and up running iOS 8.0 or higher, iPad Air and iPad Mini (2nd generation) in an iPhone frame on iPad and iPod Touch (5th generation) HTC One and One M8 running Android 4.4.x or higher LG G3 and Nexus 5 running Android 4.4.x or higher Samsung Galaxy S4 running Android 4.3.x or higher Samsung Galaxy S5 running Android 4.4.x or higher and works with over 20 different Fluke products—the largest system of connected test tools in the world. And more are on the way. Go to the Fluke website to find out more.

*Within provider’s wireless service area.
Download the app at:
fluke-connect-appstore  fluke-connect-googleplay

The High-Performance 2-in-1 Insulation DMM

 

The Fluke 1587 FC and 1577 Insulation Multimeters combine a digital insulation tester with a full-featured, true-rms digital multimeter in a single compact, handheld unit, which provides maximum versatility for both troubleshooting and preventative maintenance.

The Fluke 1587 FC Insulation Multimeter adds four powerful newdiagnostic functions through the Fluke Connect ®  Measurements app:

  • PI/DAR timed ratio tests with TrendIt ™ graphs identifies moisture and contaminated insulation problems faster.
  • Memory storage through Fluke Connect eliminates writing down results, reduces errors and saves data for historical tracking over time.
  • Temperature Compensation through app for establishing accu- rate baselines and relevant historical comparisons.
  • Historical tracking and trending of assets identifies degradation over time, allows real-time decisions to be made in the field with Fluke Connect ® Assets (sold separately).
Fluke_1587_FC_with_Fluke_Connect_Measurements_App_tn
 

Product Highlights

 

  • PI/DAR timed ratio tests (1587 FC only)
  • Live circuit detection prevents insulation test if voltage > 30 V is detected for added user protection
  • VFD low-pass filter for accurate motor drive measurements (1587 FC only)
  • Auto-discharge of capacitive voltage for added user protection
  • Insulation test (1587 FC: 0.01 MO to 2 GO) (1577: 0.1 MO to 600 MO)
  • Insulation test voltages (1587 FC: 50 V, 100 V, 250 V, 500 V, 1000 V),(1577: 500 V, 1000 V) for many applications
  • AC/DC voltage, DC millivolts, AC/DC milliamps, Resistance (O), Continuity
  • Capacitance, diode test, temperature, Min/Max, frequency (Hz) (1587 FC only)
  • Auto power off to save battery power
  • CAT III 1000 V, CAT IV 600 V measurement category
  • Large display with backlight
Fluke_1587_FC_Product_Hightlights_tn
 

What's In The Box

  • Remote probe
  • Test leads
  • Alligator clips
  • K-type thermocouple
  • Hard case
  • User documentation

Specifications

GENERAL SPECIFICATIONS
Maximum voltage applied to any terminal and common 1000 V
Storage temperature -40 °C to 60 °C (-40 °F to 140 °F)
Operating temperature -20 °C to 55 °C (-4 °F to 131 °F)
Temperature coefficient 0.05 x (specified accuracy) per °C for temperatures <18 °C or >28 °C (<64 °F or >82 °F)
Relative humidity Noncondensing
0 % to 95 % @ 10 °C to 30 °C (50 °F to 86 °F)
0 % to 75 % @ 30 °C to 40 °C (86 °F to 104 °F)
0 % to 40 % @ 40 °C to 55 °C (104 °F to 131 °F)
Vibration Random, 2 g, 5-500 Hz per MIL-PRF-28800F, Class 2 instrument
Radio frequency communication 2.4 GHz ISM Band
Radio frequency certification FCC: T68-FBLE, IC: 6627A-FBLE
Electromagnetic compatibility
International IEC 61326-1 Portable Electromagnetic Environment; IEC 61326-2-2 CISPR 11: Group 1, Class A : Group 1: Equipment has intentionally generated and/or uses conductively-coupled radio frequency energy that is necessary for the internal function of the equipment itself.

Class A: Equipment is suitable for use in all establishments other than domestic and those directly connected to a low-voltage power supply network that supplies buildings used for domestic purposes. There may be potential difficulties in ensuring electromagnetic compatibility in other environments due to conducted and radiated disturbances.

Emissions that exceed the levels required by CISPR 11 can occur when the equipment is connected to a test object. The equipment may not meet the immunity requirements of this standard when test leads and/or test probes are connected.
Korea (KCC) Class A Equipment (Industrial Broadcasting & Communication Equipment)
Class A: Equipment meets requirements for industrial electromagnetic wave equipment and the seller or user should take notice of it. This equipment is intended for use in business environments and not to be used in homes.
USA (FCC) 47 CFR 15 subpart B. This product is considered an exempt device per clause 15.103.
Enclosure protection IEC 60529: IP40 (non-operating)
Safety IEC 61010-1 Pollution Degree 2
IEC 61010-2-033 CAT IV 600 V/CAT III 1000 V
Batteries Four AA batteries (NEDA 15A or IEC LR6)
Battery life Meter use 1000 hours; Insulation test use: Meter can perform at least 1000 insulation tests with fresh alkaline batteries at room temperature. These are standard tests of 1000 V into 1 MO with a duty cycle of 5 seconds on and 25 seconds off.
Size 5.0 cm H x 10.0 cm W x 20.3 cm L (1.97 in H x 3.94 in W x 8.00 in L)
Weight 550 g (1.2 lb)
Altitude Operating 2000 m
Storage 12,000 m
Over-Range capability 110 % of range except for capacitance which is 100 %
Frequency overload protection <107 V-Hz
Fuse Protection for mA input 0.44A, 1000 V, IR 10 kA
 
ELECTRICAL SPECIFICATIONS
AC voltage measurement
Accuracy (1587 FC only)
Range Resolution 50 Hz to 60 Hz ± (% of Rdg + counts) 60 Hz to 5000 Hz ± (% of Rdg + counts)
600.0 mV 0.1 mV ± (1 % + 3) ± (2 % + 3)
6.000 V 0.001 V ± (1 % + 3) ± (2 % + 3)
60.00 V 0.01 V ± (1 % + 3) ± (2 % + 3)
600.0 V 0.1 V ± (1 % + 3) ± (2 % + 3) 1
1000 V 1 V ± (2 % + 3) ± (2 % + 3) 1
1 1 kHz bandwidth
Low-Pass Filter Voltage (1587 FC only)
Range Resolution 50 Hz to 60 Hz ± (% of Rdg + Counts) 60 Hz to 400 Hz ± (% of Rdg + Counts)
600.0 mV 0.1 mV ± (1 % + 3) + (2 % + 3) - (6 % - 3)
6.000 V 0.001 V ± (1 % + 3) + (2 % + 3) - (6 % - 3)
60.00 V 0.01 V ± (1 % + 3) + (2 % + 3) - (6 % - 3)
600.0 V 0.1 V ± (1 % + 3) + (2 % + 3) - (6 % - 3)
1000 V 1 V ± (2 % + 3) + (2 % + 3) - (6 % - 3)
 
1577 accuracy
Range Resolution 50 Hz to 60 Hz ± (% of Rdg + Counts)
600.0 mV 0.1 mV ± (2 % + 3)
6.000 V 0.001 V ± (2 % + 3)
60.00 V 0.01 V ± (2 % + 3)
600.0 V 0.1 V ± (2 % + 3)
1000 V 1 V ± (2 % + 3)
AC Conversion Inputs are ac coupled true-rms responding and specified from 5 % to 100 % of range. Input signal crest factor can be up to 3 up to 500 V, decreasing linearly to a crest factor =1.5 at 1000 V. For non-sinusoidal waveforms add ± (2 % reading + 2 % FS) typical, for a crest factor up to 3.
Input Impedance 10 MΩ (nominal), <100 pF, ac-coupled
Common mode rejection ratio (1 kΩ unbalanced) >60 dB at dc, 50 or 60 Hz
DC voltage measurement
Range Resolution Accuracy 1587 FC1
± (% of Rdg + Counts)
Accuracy 15771
± (% of Rdg + Counts)
6.000 V dc 0.001 V ± (0.09 % + 2) ± (0.2 % + 2)
60.00 V dc 0.01 V ± (0.09 % + 2) ± (0.2 % + 2)
600.0 V dc 0.1 V ± (0.09 % + 2) ± (0.2 % + 2)
1000 V dc 1 V ± (0.09 % + 2) ± (0.2 % + 2)
1 Accuracies apply to ± 100% of range.
Input Impedance: 10 MΩ (nominal), <100 pF
Normal mode rejection ratio: >60 dB @ 50 Hz or 60 Hz
Common mode rejection ratio: >120 dB @ dc, 50 Hz or 60 Hz (1 k unbalanced)
DC millivolts measurement
Range Resolution Accuracy 1587 FC ± (% of Rdg + Counts) Accuracy 1577 ± (% of Rdg + Counts)
600.0 mV dc 0.1 mV ± (0.1 % + 1) ± (0.2 % + 1)
DC and AC current measurement
Range Resolution Accuracy 1587 FC ± (% of Rdg+Counts) Accuracy 1577 ± (% of Rdg+Counts) Burden voltage (Typical)
AC 45 Hz to 1000 Hz 400 mA 0.1 mA ± (1.5 % + 2) 1 ± (2 % + 2) 1 2 mV/mA
60 mA 0.01 mA ± (1.5 % + 2) 1 ± (2 % + 2) 1  
DC 400 mA 0.1 mA ± (0.2 % + 2) ± (1.0 % + 2) 2 mV/mA
60 mA 0.01 mA ± (0.2 % + 2) ± (1.0 % + 2)  
1 1 kHz bandwidth
Overload: 600 mA for 2 minutes maximum
Fuse protection for mA Input: 0.44 mA, 1000 V, IR 10 kA
AC conversion: Inputs are ac coupled true-rms responding and specified from 5 % to 100 % of range. Input signal crest factor can be up to 3 up to 300 mA, decreasing linearly to crest factor =1.5 at 600 mA. For non-sinusoidal waveforms add +(2 % reading + 2 % FS) typical, for a crest factor up to 3.
Ohms measurement
Range Resolution Accuracy 1587 FC1
+ (% of Rdg+Counts)
Accuracy 15771
+ (% of Rdg+Counts)
600.0 Ω 0.1 Ω ± (0.9 % + 2) ± (1.2 % + 2)
6.000 kΩ 0.001 kΩ
60.00 kΩ 0.01 kΩ
600.0 kΩ 0.1 KΩ
6.000 MΩ 0.001 MΩ
50.0 MΩ [2] 0.01 MΩ ± (1.5 % + 3) ± (2.0 % + 3)
1 Accuracies apply from 0 % to 100 % of range. 2 Up to 80 % relative humidity.
Overload protection: 1000 V rms or dc
Open circuit test voltage: <8.0 V dc
Short circuit current: <1.1 mA
Diode test (1587 FC only)
Diode test indication Display voltage drop: 0.6 V at 1.0 mA nominal test current
Accuracy ± (2 % + 3)
Continuity test
Continuity indication Continuous audible tone for test resistance below 25 O and off above 100 O. Maximum reading; 1000 O
Open circuit voltage <8.0 V
Short circuit current 1.0 mA typical
Overload protection 1000 V rms
Response time >1 m sec
Frequency measurement (1587 FC only)
Range Resolution Accuracy ± (% of Rdg+Counts)
99.99 Hz 0.01 Hz ± (0.1 % + 1)
999.9 Hz 0.1 Hz ± (0.1 % + 1)
9.999 kHz 0.001 kHz ± (0.1 % + 1)
99.99kHz 0.01 kHz ± (0.1 % + 1)
Frequency counter sensitivity
Input range V ac Sensitivity (RMS Sine Wave)1 DC trigger levels to 20 kHz2
5 Hz to 20 kHz 20 kHz to 100 kHz  
600.0 mV ac 100.0 mV 150.0 mV NA
6.0 V 1.0 V 1.5 V -400.0 mV and 2.5 V
60.0 V 10.0 V 36.0 V 1.2 V and 4.0 V
600.0 V 100.0 V   12.0 V and 40.0 V
1000.0 V 300.0 V   12.0 V and 40.0 V
1 Maximum input for specified accuracy = 10x range (1000 V max). Noise at low frequencies and amplitudes may affect accuracy.
2 Usable to 100 kHz with full scale input.
Capacitance (1587 FC only)
Range Resolution Accuracy ± (% of Rdg+Counts)
1000 nF 1 nF ± (1.2 % + 2)
10.00 µF 0.01 µF
100.0 µF 0.1 µF ± (1.2 % + 90 counts)
9999 µF 1 µF
Temperature measurement (1587 FC only)
Range Resolution Accuracy 1 ± (% of Rdg+Counts)
-40 ° C to 537 ° C 0.1 °C ± (1 % + 10 counts)
-40 ° F to 998 ° F 0.1 °F ± (1 % + 18 counts)
1 Accuracies apply following 90 minutes settling time after a change in the ambient temperature of the instrument.
INSULATION SPECIFICATIONS
Measurement range Model 1587 FC: 0.01 MΩ to 2 GΩ
Model 1577: 0.1 MΩ to 600 MΩ
Test voltages Model 1587 FC: 50, 100, 250, 500, 1000 V
Model 1577: 500, 1000 V
Test voltage accuracy +20 %, -0 %
Short-Circuit test current 1 mA nominal
Auto discharge Discharge time <0.5 second for C = 1 µF or less
Live circuit detection Inhibit test if terminal voltage > 30 V prior to initialization of test
Maximum capacitive load Operable with up to 1 µF load

Fluke 1587 FC Product Specifications Summary:
(for full specs please see the full specs tab or the data sheet)

Multimeters Template

TypeDigital
StyleHand-Held
Measures AC VYes
Measures DC VYes
Measures AC AYes
Measures DC AYes
True RMS What's This?Yes
Maximum Voltage AC1000 V
Minimum Voltage AC0 V (0 mV)
Resolution AC Volts0.1 V (100 mV)
Maximum Voltage DC1000 V
Minimum Voltage DC0 V (0 mV)
Resolution DC Volts0.001 V (1 mV)
Maximum Current AC What's This?400 mA (0.4 A)
Minimum Current AC1 mA
Resolution AC Current0.01 mA
Maximum Current DC400 mA (0.4 A)
Minimum Current DC1 mA
Resolution DC Current0.01 mA
Basic Accuracy V DC±(0.09%+2)
# Digit Display What's This?3.75
Counts What's This?6000 .
BacklightYes
Manual/Autoranging What's This?Both
Dual DisplayYes
Analog Bargraph on DisplayNo
DecibelsNo
ResistanceYes
FrequencyYes
Continuity What's This?Yes
CapacitanceYes
TemperatureYes
Diode TestingYes
CAT Rating What's This?IV
CAT Voltage What's This?1,000 V, 600 V 
Peak HoldYes
Overload ProtectorYes
Kelvin 4-Wire Measurement Capability What's This?No
Intrinsically Safe What's This?No
Wireless DisplayNo
Data Hold What's This?Yes
Low-Pass Filter What's This?Yes

Micro / Milli / Meg Ohmmeters/Megohmmeter / Insulation Resistance Testers Template

IR Test Voltage What's This?1,000 V, 100 V, 250 V, 50 V, 500 V
Maximum Insulation Resistance What's This?2 G Ohms
Minimum Insulation Resistance0.01 M Ohms (0.00001 G Ohms)
Variable Incremental Voltage What's This?No
Display (Megohmmeter) What's This?Digital
Continuity TestYes
Live Circuit Voltage Detection What's This?Yes 
Power SupplyBattery
TimerNo

Test Equipment General Attributes

Unique FeaturesInsulation test voltages 50V, 100V, 250V, 500V, 1000V
Insulation test: 0.01 MΩ to 2.0 GΩ
Auto discharge of capacitive voltage
Insulation test smoothing reading
Frequency
Capacitance
Diode test
Temperature
Min/Max
Low pass filter (for work on VSD's)
AC/DC Voltage
DC millivolts
AC/DC milliamps
Warranty3 YEARS
Calibration IncludedNone
Power Supply VoltageBattery Powered
Safety ApprovalCSA
Data Logging What's This?No
IP Rating What's This?IP40
Product Weight4.72 LBS
Battery TypeAA 
Product Height7.99 IN
Product Length3.97 IN
Product Width7.96 IN
Shipping Weight5.19 LBS
Country of OriginUnited States
Shipping Height7.99 IN
Shipping Length3.97 IN
Shipping Width7.96 IN
UPC095969262958

Reviews

Fluke 1587 FC Customer Reviews

4 Reviews
5 stars
 (4)
4 stars
 (0)
3 stars
 (0)
2 stars
 (0)
1 star
 (0)
 
 
 
 
 
Average Customer Review
         
5 of 5
4 customer reviews
Share your thoughts with other customers
Create your own review
 
Most Helpful First | Newest First      Prev Page
 
Prev Page
 

Accessories

Loading Accessories

Fluke Price List

X


secured website

Interworld Highway, LLC dba TEquipment.NET

205 Westwood Avenue. Long Branch, NJ 07740

Privacy Policy | Terms and Conditions | Site Map

Copyright© 2016 Interworld Highway, LLC

secured website
We Price Match!

Give our sales team a call at 877.571.7901 (Toll Free) or 732.222.7077 (International) and we'll match any competitor's price.

X