| General Specifications |
| Display |
Dual 7-segment 4-digit LED Displays: Red (PV), Green (SV) |
| Status Indicators |
For Control output, Alarm output, Over range, Auto-Tune, and Open Input |
| LED display span |
-1999 to 9999 counts max (Programmable) |
| Indicating Accuracy |
+0.2% Full Scale +1 digit |
| Sampling Time |
1 reading per 0.25 seconds |
| Memory |
Nonvolatile type |
| Meter Enclosure |
ABS Plastic |
| Front Panel |
Lexan (Drip and Dust Proof; IEC IP55, NEMA Equivalent) |
| Power Supply |
85 to 260VAC 50/60 Hz (automatic switching) |
| Power Consumption |
6 Watts |
| Insulation Resistance |
>50M Ω |
| Noise Rejection |
Common Mode - 110 db typical, Normal Mode - 50 db typical |
| Operating Temperature / Humidity |
14 to 122 °, F (-10 to 50 ° C), 90% RH max. |
| Storage Temperature |
-4 to 140 ° F (-20 to 60 ° C) |
| Dimensions (Cutout) |
1.77 x 1.77" ±0.02" (45.0 x 45.0mm ±0.5mm) |
| Input Specifications |
| Thermocouple input |
(Programmable) |
| Types |
J, K, T, E, B, R, S, N; Cold Junction Compensation |
| Thermocouple Break Protection |
Upscale and Downscale |
| Lead Wire Effect |
0.015%/ohm (Input impedance: 10 megohm) |
| RTD input |
Pt 100 ohm (DIN, JIS) |
| RTD Break Protection |
Upscale and Downscale |
| Lead Wire Effect |
0.015/ohm (automatically compensates if one lead wire is < 5 Ω ) |
| Current input |
4-20mA DC (2.7 Ω input impedance) |
| Voltage input |
1-5V DC |
| Thermocouple Ranges |
| Type K |
-58 to 2498 ° F (-50 to 1370 ° C) |
| Type J |
-58 to 1830 ° F (-50 to 1000 ° C) |
| Type B |
32 to 3272 ° F (0 to 1800 ° C) |
| Type T |
-454 to 752 ° F (-270 to 400 ° C) |
| Type E |
-58 to 1382 ° F (-50 to 750 ° C) |
| Type R |
32 to 3182 ° F (0 to 1750 °o C) |
| Type S |
32 to 3182 ° F (0 to 1750 ° C) |
| Type N |
-58 to 2372 ° F (-50 to 1300 ° C) |
| RTD |
PT100 input ranges -392 to 932 ° F (-200 to 500 ° C); (DIN or JIS) |
| Linear input range |
-1999 to 9999 display span (for 4-20mA, 1-5V, or special DC input). |
| Temperature Stability |
5uV/° C typical |
| Repeatability |
0.83 ° C (Thermocouple), 0.2 ° C (RTD), 1 digit (Linear) |
| Output Specifications |
| Control Output Relay |
5 Amps at 110V AC, SPDT (Resistive Load) |
| Control Output DC Voltage |
(Pulsed) 24V DC (DC drive for SSR) |
| ON |
24V DC typical, 29V DC max. |
| OFF |
0.3V DC max |
| Analog Control Output |
(Current) 4-20mA DC; Load limit: 600 Ω max. |
| Alarm/Timer Types |
High/Low Deviation/Absolute Alarms w/deadband adjust plus Soak/Event Timers |
| Alarm Output Relay |
3 Amps at 110VAC, SPST (Resistive Load) |
| Output Control Modes |
| Proportional Band |
0.0 to 100.0% of Full Scale (can be Auto Tuned) |
| Integral Time |
0 to 3000 secs. (can be Auto Tuned) |
| Derivative Time |
0 to 3000 secs. (can be Auto Tuned) |
| Cycle Time |
1 to 100 secs. (0 sec for 4-20mA output) |
| Anti-Reset |
Wind-Up Inhibits integral action outside of the Prop. Band |
| Manual Reset |
0 to 100% of Prop. Band |
| Hysteresis |
0.0 to 25.5% of Full Scale |