Dranetz-BMI DFACP3K36 Probe AC Current Flexible 36in 915mm Dranetz-BMI DFACP3K36 DF ACP3K 36 DF-ACP3K-36
company logo Dranetz-BMI DFACP3K36
AC Current 36in (915mm) Flexible Probe
     Search: HACKER SAFE certified sites prevent over 99.9% of hacker crime.  
 
 
 



Dranetz-BMI DFACP3K36
AC Current 36in (915mm) Flexible Probe




Click image to enlarge

 DFACP3K36

Features:
  • UL Listed
  • BNC connector, with 4mm safety jack included
  • Available in 24”, 36” and 48” lengths
  • Smaller diameter core for more flexibility
  • New snap lock technology
  • CAT III 1000V, CAT IV 600V Rated
  • For use with DMM’s, O-scope’s, Power Analyzer’s



  Description

The PRO~flex ACP3000_4 are AC current probes utilising Rogowski principle. They can be used to measure AC current up to 3000A, when used with oscilloscopes, recorders or data loggers. The flexible probe allows current measurements on conductors that are hard to reach.

The probes provide a 3V full scale AC output proportional to the current being measured with three selectable ranges.




  Models, Options, & Accessories


Model Description List Price Sale Price
DFACP3K36 DranFlex ACP 30/300/3000A/36, BNC/4MM
$415.00 
DFACP3K24 DranFlex ACP 30/300/3000A/24, BNC/4MM
$345.00 
DFACP3K48 DranFlex ACP 30/300/3000A/48, BNC/4MM
$485.00 
DFACP6K24 DranFlex ACP 60/600/6000A/24, BNC/4MM
$450.00 
DFACP6K36 DranFlex ACP 60/600/6000A/36, BNC/4MM
$525.00 
DFACP6K48 DranFlex ACP 60/600/6000A/48, BNC/4MM
$605.00 



  Specifications

Measuring ranges ACP3000_4: 30A / 300A / 3000A AC
ACP6000_4: 60A / 600A / 6000A AC
Output sensitivity (AC coupled) ACP3000_4: 100mV / 10mV / 1mV per A
ACP6000_4: 50mV / 5mV / 0.5mV per A
Accuracy (45-65Hz) ± 1% of reading ± 0.1A: 30/300A or 60/600A ranges
± 1% of reading ± 1A: 3000A or 6000A range
Minimum load 100kΩ for specified accuracy
Frequency range 10Hz to 10kHz (-1dB)
Phase (45-65Hz) >± 1°
Position sensitivity ± 2% of reading
External field ± 0.2% of range with cable >200mm (8") from the probe
Noise 8mV rms in 30A / 60A ranges
2mV rms in 300A / 3000A and 600A / 6000A ranges
Temperature coeff. ± 0.1% /°C
Power supply Two AA MN1500 LR6 alkaline batteries or an external power supply (+3V/100mA)
Battery life 2000 hours typical
External Power Via 2.1mm (0.08") mini power connector
Low battery Indicated by an orange LED
Overload Indicated by a red LED
Enclosure
Material ARNITE T06-200SNF, UL94 V0
Degree of Protection IP40 (not certified by UL)
Dimensions 110 (l) x 65 (w) x 23 (d) mm
Output connection 0.5m coax cable terminated with a safety BNC
Probe
Probe lengths 610mm (24 inches), double insulated
915mm (36 inches), double insulated
1220mm (48 inches), double insulated
Probe diameter 9.9mm (0.39 inches)
Output cable 2m (78.7inches), probe to integrator
Material Alcryn 2070 NC, LATI LATENE 7H2W V0
Degree of Protection IP65 (not certified by UL)
General Characteristics
Operating temp. -20°C to +65°C (-4°F to +149°F)
Storage temp. -40°C to +75°C (-40°F to +167°F)
Operating humidity 15% to 85% (non-condensing)
Safety standards EN 61010-1:2001
EN 61010-031:2002
EN 61010-2-032:2002
EMC EN 61326-2-2:2006
1000 VRMS, Category III, 600 VRMS, Category IV, Pollution Degree 2 (Probe and Integrator)
30V maximum between output and earth
ROHS and WEEE compliant
Rated for continuous use

   Back to Top



 

Welcome | Companies | Search by Type | How To Order | Leasing | About Us | Careers
  Tequipment.NET
205 Westwood Ave
Long Branch, NJ 07740
BBBOnline Reliability Seal, Click for confirmation page. Tequipment.NET
Phone: 1-877-571-7901 / 732-222-7077
Fax: (732) 222-7088
E-mail: salesteam@Tequipment.NET
 




Fluke Sponsored March Madness Bracket Challenge

Quote Request

We Take POs, How To Order

Free Shipping on Select Premier Lines










Live chat by BoldChat
Let our engineers and cs staff help!
Need a quote? Need to check stock?
Have a technical question? No problem.
We are here to help.