Bacharach HGM300 CFC, HFC, HCFC and Halon Gas Monitor Bacharach HGM-300, HGM300, HGM 300
Our agents are available:
9:00 AM - 6:00 PM EST
Bacharach HGM300 - CFC, HFC,
HCFC and Halon Gas Monitor
   Search: HACKER SAFE certified sites prevent over 99.9% of hacker crime.
   
   
   



Bacharach HGM300 - CFC, HFC,
HCFC and Halon Gas Monitor


Features:
  • Select refrigerants to be measured - point by point
  • Eliminate false alarms with use of non-dispersive IR source and sample draw system
  • Measure all gases up to 10,000 ppm with a sensitivity of 1 ppm
  • Sample points locate up to 500 feet from unit
  • Remotely interrogate, acknowledge alarms
  • Quick field expansion from 4 to 16 sampling zones
  • Bolt-in, bolt-out internal components so the unit never leaves the wallt
  • Full two-way communication via RS-458
  • RS-232 port for local / modem communication
  • Split-architecture design keeps your investment to a minimum
  • UL and CE approved
  • Two-year warranty



  Description

Multi-Zone - Fixed Refrigerant Gas Monitors

The HGM300 / AGM300 Multi-Zone Refrigerant Monitor, and the RDM-800 / ADM-800 Remote Display Module combine to provide a multiple refrigerant gas and multiple area monitoring system for low level continuous monitoring of CFC, HCFC, HFC, and ammonia refrigerant gases.

HGM300 / AGM300 - Multiple refrigerant gas and multiple area monitor. May be used "stand alone" or combined with other HGM300 /AGM300 units reporting to the RDM-800 / ADM-800 remote display.

System design supports compliance to the refrigerant monitoring requirements of ANSI / BSR ASHRAE 15 1994/2001. Certified in compliance to UL # 3101-1, CE # EN613262, and EN61010-1.




  Models, Options, & Accessories


Model Description List Price Sale Price
HGM300 Please call or email us for pricing and availability.
AGM300 Please call or email us for pricing and availability.
Model Accessories List Price Sale Price
3015-2875 RDM 800, 120V AC, 50 / 60 HZ INPUT POWER $1420.00
$1349.00 
3015-2885 RDM 800, 240V AC, 50 / 60 HZ INPUT POWER $1420.00
$1349.00 
3015-4195 ADM 800, 120V AC, 50 / 60 HZ INPUT PWR $1420.00
$1349.00 
3015-4196 ADM 800, 240V AC, 50 / 60 HZ INPUT PWR $1420.00
$1349.00 
3015-4121 12O VAC SURGE PROTECTOR, HGMSZ $310.00
$294.50 
3015-4122 230 VAC Surge Protector $310.00
$294.50 
3015-4123 4-20 mA DC SURGE PROTECTOR, HGMSZ $206.00
$195.70 
3015-3133 DUAL 4-20 MILLIAMP DC OUTPUT PCB $335.00
$318.25 
3015-3069 VISUAL ALARM, 120 VAC, HGMSZ $170.00
$161.50 
3015-3070 AUDIO ALARM, 120 VAC, HGMSZ $140.00
$133.00 
3015-3076 AUDIO-VISUAL ALARM, 120 VAC, HGMSZ $350.00
$332.50 
3015-3423 MAINTENANCE KIT (1 inline filter, 1 charcoal filter assy) $115.00
$109.25 
3015-3235 AIR SAMPLING TUBING (250 FT ROLL) $67.00
$63.65 


Ordering Information For Monitors



  Specifications

Refrigerants HGM300: CFC: R11, R12, R113, R114, R502, R404a (HP62), R407a, R407c (AC9000), R134a, R410a (AZ20), R507 (AZ50), R508b (SUVA95) HCFC: R22, R123, R124, R500, R503, R401a (MP39), R402a (HP80), R40b (HP81), R408a, R409a, R23 HALON: 1301
AGM300: R-717 (Ammonia)
Measuring Range HGM300: All gases 0 to 10,000 ppm
AGM300: 25 to 10,000 ppm
Inputs 4 points standard, expandable to 16 points in 4 point increments
Output Signal 4-20 mA DC (optional)
Detector Type Non-dispersive infrared
Sensitivity All gases 1 ppm
Accuracy All gases ±10 ppm from 0 to 100 ppm, ±10% of reading from 100 to 10,000 ppm
Front Panel Display Green LED indicates when unit is operating properly
Red LED indicates when any monitored point is above its alarm setting
Yellow LED indicates a clogged sample line or other system fault
Response Time 5 to 120 seconds, depending on tube length and gas concentration
Max. Monitoring Distance Up to 500 feet from measuring point to monitor
Operating Temperature 32 to 113 °F (0 to 45 °C)
Power 120/240 VAC, 50/60 Hz
Size/Weight 17" x 12" x 5.5" / 15 lbs (may be wall or rack mounted)


REMOTE DISPLAY MODULES
RDM800 Model Compatible with HGM300 Model
ADM800 Model Compatible with AGM300 Model
Inputs Accepts from one to four inputs via RS-485 from up to four HGM300 Refrigerant Monitors
Display Backlit LCD displays the measured point in ppm
Trend Mode / Data logging User may select a graphical display of the ppm trend for any measured point (100 data entries per point)
Output Signal 2 SPDT, 5 Amp, 240 VAC assignable alarm relays
Alarm Indications Channel display flashes, red light flashes, alarm signal sent via RS-485
Input Fault Indication Yellow light flashes and the LCD indicates location of input fault
Max. Monitoring Distance Maximum of 4,875 wiring feet from the furthest HGM300 to the RDM800 Display
Power 120 / 240VAC, 50 / 60 Hz
Size/Weight 11" L x 10" W x 3" D / 5 lbs (wall mounted)


  ORDERING INFORMATION FOR MONITORS

When ordering this product, you must specify 3 codes: These 3 codes will build up a part number. Codes must be listed in the following sequence.
Code A- Model Number
Code B- Number of Zones
Code C- Input Power Type

For example, to order a 4-zone, 120 VAC Ammonia Monitor with a standard analog output and standard calibration, you would order a: AGM300-11-1

Remote Display Modules, options and accessories must be ordered as separate line items.



ORDERING INFORMATION FOR MONITORS
Code A Model Number
HGM300 For use with CFC, HFC, HCFC and Halon Refrigerants
AGM300 For use with Ammonia Refrigerants
Code B Number of zones and connection type
-11 4 Zones with metal tube fittings
-12 8 Zones with metal tube fittings
-13 12 Zones with metal tube fittings
-14 16 Zones with metal tube fittings
Code C Input Power Type
-1 120 VAC / 60 Hz (Standard)
-2 240 VAC / 50 Hz

   back to top


   
  Welcome | Companies | Search by Type | How To Order | Leasing | About Us  
  Tequipment.NET
205 Westwood Ave
Long Branch, NJ 07740
For our Electronic Whiteboard division visit www.touchboards.com
BBBOnline Reliability Seal. Tequipment.NET
Phone: 1-877-742-TEST (8378) / 732-222-7077
Fax: (732) 222-7088
E-mail: salesteam@Tequipment.NET