| Technical |
| AC Voltage including Sags and Surges |
0 - 600V ±(0.5% Rdg + 2 LSD) |
| AC Current |
5 - 1000A (expandable to 3000A with optional CTs) ±(0.5% Rdg + 2 LSD) |
| Power |
Working (W), Reactive (VAR) and Apparent (VA) ±(1.0% Rdg + 2 LSD) |
| Power Factor |
0.00 1.00 |
| Energy |
Working (kWh), Reactive (VARh) and Apparent (VAh) ±(1.0% Rdg + 2 LSD) |
| Peak Demand |
kW ±(1.0% Rdg + 2 LSD) |
| Harmonics |
THD, DC and individual up to 49th ±(0.5% Rdg + 2 LSD) @ DC to 25 harmonics |
| Frequency measurement |
57 to 63.6Hz at 60Hz fundamental, 47 to 53Hz at 50Hz fundamental ±(1.0% Rdg + 2 LSD) |
| Phase sequence |
1-2-3 |
| Co-generation |
Measures Absorbed and Generated Power and Energy |
| Selectable Fundamental Frequencies |
50/60Hz |
| Available Recording Time |
Several hours to several years depending on setup |
| Mechanical Features |
| Dimensions |
8.9(L) x 6.5 (La) x 4.1(H) 225(L) x 165(La) x 105(H) mm |
| Weight |
3.3 Lb (1.5kg) |
| Internal power supply |
6 batteries 1.5V series AA LR6 |
| Battery Life |
50 hours |
| External power supply |
Use only Amprobe power supply Adapter code 9821-120120V. |
| Display |
dot matrix with backlight resolution 128 x 128 dots (16384 dots) dot size 0.5mm x 0.5mm visible area 2.9 x 2.9 (73mm x 73mm) |
| Sampling speed |
156.25usec a 50Hz. |
| No. of samples per period |
128 |
| Clamp |
Opening 2.15 (53 mm) |
| Maximum diameter of the cable |
2.00 (50 mm) |
| Operating Conditions |
| Reference temperature |
73°F ± 2°F (23°C ± 1°C) |
| Operating temperature |
32°F to 122°F (0°C to 50 °C) |
| Relative humidity |
<70% |
| Storage temperature |
14°F to 140°F (-10°C to 60 °C) |
| Storage humidity |
<80% |
| EMC |
This instrument has been designed in compliance with the EMS standards in force and its compatibility has been tested for EN61326-1 (1997) + A1 (1997). |