| Operating Range |
| Current Range |
4 to 500AAC |
| Frequency Range |
48 to 1000Hz |
| Common Mode Voltage |
600VAC |
| Current Overload |
700A for 10 min |
| Load Impedance |
5W max noninductive |
| Open Secondary Voltage |
Limited to 10V Peak max |
| Reference Conditions |
23°C ±5°K, 20 to 75% RH, external magnetic field <40A/m, no DC component, no external current carrying conductor, test sample centered, 5W load |
| Ratio |
| Ratio |
1000:1 |
| Working Voltage |
600VAC |
| Influence of Adjacent Conductor |
| Range Value |
50Hz |
| Influence of Adjacent Conductor |
< 30mA/A |
| Influence of Conductor Position |
| Influence of Conductor Position |
± 1.5% ±0.1A of Reading @ 50/60Hz |
| Output Signal |
| Output Signal |
1mAAC / AAC |
| Phase |
| Range Value |
45 to 1000Hz |
| Phase Shift |
< 7° |
| Mechanical Specifications |
| Altitude |
Operating: 0 to 2000m; Non-operating: 0 to 12km |
| Colors |
Dark gray handles |
| Dimensions |
2.6 x 7.68 x 1.34" (66 x 195 x 34mm) |
| Drop Test |
1.5m (IEC 68-2-32) |
| Jaw Opening |
1.3" (33mm) |
| Material |
Handles: 10% Fiberglass charged polycarbonate UL 94 V0 |
| Maximum Bus Bar Size |
2.48 x 0.20" (63 x 5mm) |
| Maximum Cable Diameter |
1.18" (30mm) |
| Mechanical Shock |
100g (IEC 68-2-27) |
| Operating Temperature |
-5° to 122°F (-15° to 50°C) |
| Output |
Double insulated 5 ft (1.5m) lead with safety banana plugs |
| Protection Index (IP) |
IP 20 (IEC 529) |
| Storage Temperature |
-40° to 185°F (-40° to 85°C) |
| Vibration |
Test per IEC 68-2-6 |
| Weight |
14.82 oz (420g) |
| External Influences |
| Influence of Temperature |
<0.1% per 10K° |
| Safety Reference Specifications |
| Safety Ratings |
EN 61010-2-32 |
| Agency Approvals |
CE Mark |