AEMC H215 2117.84 Hipot Tester

Click image to enlarge
AEMC 2117.84
|
|
Features:
- Discontinued, Replaced by H216
|
Description
|
The AEMC Hipot Tester Model H215 is designed for AC/DC Withstanding Voltage Testing and Insulation Resistance Testing (IR) providing a safe and accurate test environment for the operator. This Electrical Safety Tester complies with the requirements of the electrical equipments and appliance testing standard, UL, CSA and other international standards. The tester can be used for withstanding voltage tests of the various types of electrical equipment and components. The Model H215 provides AC hipot programmable to 5kV @ 20mA and DC hipot programmable to 6kV @ 7.5mA.
|
Models, Options, & Accessories
| Model |
Description |
List Price |
Sale Price |
| 2117.84 |
Hipot Model H215 (5kV@20mA, 6kV@7.5mA) - Discontinued - suggested replacement: Vitrek V63 |
| 2129.63 |
Hipot Model H216 (5kVAC/6kVDC and IR w/SP02) - Discontinued - suggested replacement: Vitrek V63 |
Specifications
| AC HIPOT |
| Voltage Range |
100V to 5000Vac (5kV) |
| Voltage Step Resolution |
5V |
| Voltage Regulation |
1% of Reading +- 5cts |
| Accuracy |
1% of Reading +- 5cts |
| Frequency |
50Hz or 60Hz (programmable) |
| Trip Current |
0.01mA to 20mA in 0.01mA steps |
| Max Current Output |
20mA @ 5kV |
| Accuracy |
1% of Reading +- 5cts |
| Weight |
19.0 Lbs |
| Ramp and Dwell Time |
0.000s to 999.9s |
| DC HIPOT |
| Voltage Range |
100V to 6000Vdc (6kV) |
| Voltage Step Resolution |
5V |
| Voltage Regulation |
1% of Reading +- 5cts |
| Accuracy |
1% of Reading +- 5cts |
| Trip Current |
0.01mA to 7.50mA in 0.01mA steps |
| Max Current Output |
7.5mA @ 6kVdc |
| Accuracy |
1% of Reading +- 5cts |
| Ramp and Dwell Time |
0.000s to 999.9s |
| INSULATION RESISTANCE |
| DC Test Voltage |
500V & 100V |
| Measurement Range |
1 to 9999MΩ; |
| Accuracy |
5% (1 to 500MΩ) 10% (500 to 2000MΩ;) |
| Test Time |
0.000s to 999.9s |
| CONTINUITY CHECK |
| Resistance Range |
0.001Ω to 1,500Ω; |
| Test Current |
100mA +- 10mA |
| Accuracy |
0.1Ω @ 1Ω; |
| Test Time |
0.000s to 999.9s Programmable cancellation of short resistance of test leads |
| ARC DETECTION |
| Detect Current |
Programmable in 10 steps from 2 to 20mA |
| TEST PROGRAM DATABASE |
| Number of programmable test sequences |
6 |
| Number of steps per test sequences |
6 |
| REMOTE INTERFACE |
| Outputs |
Test, Pass and Fail |
| Inputs |
Start and Reset |
| Output Breakdown Voltage |
±350V |
| Continuous Load Current |
±100mA |
| GENERAL |
| Power Source |
100V, 120V, 220V, 230V, ±10% @ 50/60Hz (selectable on rear panel) |
| Temperature Range |
Operating: 32° to 104°F (0° to 40°C) @ 80% RH max / Storage: -16° to 158°F (-10° to 70°C) @ 70% RH max |
| Operating Environment |
Indoor use only Installation Cat. II, Pollution Degree 2, max, Altitude 6500 ft (2000m) max |
| Dimensions |
17.5 x 13 x 5.8" (446 x 330 x 149mm) |
| Weight |
26.5 lbs (12kg) |
|