AEMC H110 2117.81 Hipot Tester

Click image to enlarge
AEMC 2117.81
|
|
Features:
- Discontinued, Replaced by H111
|
Description
|
The AEMC Hipot Tester Model H110 is designed for AC/DC Withstanding Voltage Testing providing a safe and accurate test environment for the operator. This Electrical Safety Tester complies with the requirements of the electrical equipments and appliance testing standard, UL, CSA and other international standards. The tester can be used for withstanding voltage tests of the various types of electrical equipment and components. The Model H110 provides AC hipot programmable to 5kV@20mA.
|
Models, Options, & Accessories
| Model |
Description |
List Price |
Sale Price |
| 2117.81 |
Hipot Model H110 (5kV@20mA) - Discontinued - replaced by AEMC 2129.60 |
| 2129.60 |
Hipot Model H111 (5kVAC w/SP02) - Discontinued - suggested replacement: Vitrek V61 |
Specifications
| AC HIPOT |
| Voltage Range |
100V to 5000Vac (5kV) |
| Voltage Step Resolution |
5V |
| Voltage Regulation |
1% of Reading +- 5cts |
| Accuracy |
1% of Reading +- 5cts |
| Frequency |
50Hz or 60Hz (programmable) |
| Trip Current |
0.01mA to 20mA in 0.01mA steps |
| Max Current Output |
20mA @ 5kV |
| Accuracy |
1% of Reading +- 5cts |
| Weight |
19.0 Lbs |
| Ramp and Dwell Time |
0.000s to 999.9s |
| Max Current Output |
7.5mA @ 6kVdc |
| Accuracy |
1% of Reading +- 5cts |
| Ramp and Dwell Time |
0.000s to 999.9s |
| CONTINUITY CHECK |
| Resistance Range |
0.001Ω to 1,500Ω; |
| Test Current |
100mA +- 10mA |
| Accuracy |
0.1Ω @ 1Ω; |
| Test Time |
0.000s to 999.9s Programmable cancellation of short resistance of test leads |
| ARC DETECTION |
| Detect Current |
Programmable in 10 steps from 2 to 20mA |
| TEST PROGRAM DATABASE |
| Number of programmable test sequences |
6 |
| Number of steps per test sequences |
6 |
| REMOTE INTERFACE |
| Outputs |
Test, Pass and Fail |
| Inputs |
Start and Reset |
| Output Breakdown Voltage |
±350V |
| Continuous Load Current |
±100mA |
| GENERAL |
| Power Source |
100V, 120V, 220V, 230V, ±10% @ 50/60Hz (selectable on rear panel) |
| Temperature Range |
Operating: 32° to 104°F (0° to 40°C) @ 80% RH max / Storage: -16° to 158°F (-10° to 70°C) @ 70% RH max |
| Operating Environment |
Indoor use only Installation Cat. II, Pollution Degree 2, max, Altitude 6500 ft (2000m) max |
| Dimensions |
17.5 x 13 x 5.8" (446 x 330 x 149mm) |
| Weight |
26.5 lbs (12kg) |
|