company logo AEMC 721 1208.52 Clamp-on Power Meter
     Search: HACKER SAFE certified sites prevent over 99.9% of hacker crime.  
 

 
 




AEMC 721 1208.52 Clamp-on Power Meter



AEMC 1208.52
Click image to enlarge

 AEMC 1208.52

Features:
  • Designed for traditional and nonlinear loads
  • Simple clamp-on operation with power quality features
  • No menus, no calculations and no analyzing
  • Accurate True RMS readings of amperes and volts
  • Direct reading of %THD, %DF, CF, and Peak
  • Recording mode for Min, Max, Avg, Max Peak
  • Works with oscilloscopes as a harmonic and current transducer
  • Rugged Lexan construction for professional daily use
  • Built to UL, CSA, VDE, GS and IEC 1010 safety standards
  • Includes two test leads, 9V battery, two test probes, two grip probes, insulated bannana jack to BNC probe, hared carrying case, and manual.



  Description

The Model 721 combines the simplicity and familiarity of digital clamp-ons with today's critical information on power quality and harmonics.

Operation is simple and direct, with no menus, calculations or complex analyzer procedures. Select Amps or Volts on the rotary dial, connect, and measure. The push of a button gives additional information. You can troubleshoot and measure power quality with the ease of using a digital clamp-on - simply, safely, and economically.



  Models, Options, & Accessories


Model Description List Price Sale Price
1208.52 Clamp-On Harmonic Meter Model 721 (9999-count, TRMS, V, A, F, Hz, THD, CF) - Discontinued - no replacement



  Specifications

AC Current
Input Range 0.05 to 700.0Arms, ±9.99.9A Peak
Range 0.3 to 99.99A 100.0 to 400.0A 400.0 to 700.0A
Basic Accuracy 2% of Reading +20cts 2% of Reading 5% of Reading
Crest Factor >3.0 below 300A
Frequency Range 15Hz to 10kHz
Current Peak
Input Range 0.05 to ±999.9A Peak
Range 0.05 to 99.99A / 100 to 600A / 600 to 999.9A
Basic Accuracy ±3% of Reading + 30cts / ±8% of Reading
AC Volts
Input Range 0.05 to 600Vrms, 0.05 to ±1200V Peak
Range 0.5 to 399.9V / 400.0 to 999.9V
Basic Accuracy ±1.5% of Reading + 4cts / ±1.5% of Reading
Crest Factor >4.0 below 300V
Input Impedance 1MW, 47pF
Frequency Range 15Hz to 10kHz
Voltage Peak
Input Range 0.05 to 99.99V / 100 to 999.9V
Basic Accuracy ±3% of Reading + 30cts
THD
Range 0.5% to 600.0%
Resolution 0.001
Minimum Input 300mA, 300mV
Basic Accuracy ±3% of Reading + 2cts
Accuracy Hz 50/60Hz
Frequency Range Fundamental 45 to 65Hz, 25th harmonic
Display Digital: %THD, Bar graph: True RMS (A or V)
Crest Factor
Input Range 1.00 to 10.00
Resolution 0.0001
Minimum Input 300mA, 300mV
Accuracy (40 to 450Hz) ±10% of Reading + 3cts
Frequency Range 15Hz to 10kHz
Display Digital: CF, Bargraph: True RMS (A or V)
Frequency
Range 0.5 to 999.9Hz / 1000 to 9999Hz
Minimum Input Signal 1A or 1V
Accuracy ±0.1% of Reading + 1ct / ±0.2% of Reading + 1ct
Display Digital: Hz, Bar graph: True RMS (A or V)
Overload Protection
Voltage 1.5kV Peak permanent
Current 3000A AC permanent
Analog Output 1.5kV Peak permanent
General Specifications
Display Quadriplexed LCD with 12.5mm digits; 4 digits, 9999 counts
Case Gray Lexan 920A, UL 94 V2
Jaws Red Lexan 500R, 10% fiberglass, UL 94 V0
LCD Lens Crystal Lexan 920A, UL 94 V1
Battery 9V Alkaline (NEDA 1604, 6LF22, 6LR61)
Battery Life Approximately 50 hr continuous use
Dimensions 10 x 3.8 x 1.7" (254 x 97 x 44mm)
Weight 1.3lb (600g)
Mechanical Specifications
Envelope Protection IEC 529: IP 40
Drop Test IEC 68-2-32: 1m
Vibration IEC 68-2-6
Shocks IEC 68-2-27
Electromagnetic Compatibility
Electrostatic Discharge IEC 801-2: No influence: 4kV class 2; Non-destructive: 15kV class 4
RF IEC 801-3: No influence: 3V/m class 2; Minor influence: 10V/m class 3
Transients IEC 801-4: No influence: 2kV class 4
Electric Shocks IEC 801-5: No influence: 1kV class 3; CE Mark
Environmental Specification
Operating Temperature +14° to 131°F (-10° to +55°C)
Storage Temperature -40° to 158°F (-40° to 70°C)
Operating Humidity 0 to 80%RH to +40°C (50%RH @+55°C)
Storage Humidity 0 to 95%RH
Safety Reference Specifications
Protection Level Double insulation; EN 61010-1, 600V, Cat. III, Pollution degree 2
Working Voltage 600VRMS
Dielectric Test 5.5kV, 50/60Hz, I minute
Agency Approvals UL, CSA, GS, VDE




 

Welcome | Companies | Search by Type | How To Order | Leasing | About Us | Careers
  Tequipment.NET
205 Westwood Ave
Long Branch, NJ 07740
BBBOnline Reliability Seal, Click for confirmation page. Tequipment.NET
Phone: 1-877-571-7901 / 732-222-7077