AEMC 565 2117.56 Leakage Current Meters and Probe

Click image to enlarge
AEMC 2117.56
|
|
Features:
- Check for leakage and locate insulation breakdowns on live circuits.
- Measures leakage current up to 600mA with up to 10μA resolution.
- Measures current up to 100Arms
- Measures up to 600Vac/dc
- Measures Hz on either V or A inputs
- Measures Resistance and Continuity
- Hold feature freezes Value
- Max feature keeps track of highest measured In-rush value
- Zero button ideal for measuring relative values
- Filter to isolate 50/60Hz fundamental from harmonics
- Compatible with VDE 0404
- The Model 565 includes two color-coded test leads, soft carrying case and user manual.
Applications:
- Ground fault current measurement
- Electrical safety compliance testing
- Medical device safety testing
- Process loop monitoring
- General AC load monitoring
- Industrial troubleshooting checks
|
Description
The TRMS Clamp-On Leakage Current Meter Model 565 is designed to measure low AC currents, which are typically leakage currents in ground conductors. Low currents are measured using either 60mA or the 600mA range. The high sensitivity of the probe (10μA and 100μA) is possible through special jaw construction and, in particular, critical shielding of the jaws. At low measurement levels, this shielding out of the noise is critical for low sensitivity, accuracy and stability.
The Model 565 may be used as a standard clamp-on meter measuring to 100Arms, as well as AC Volts and DC Volts, resistance and continuity (with a buzzer).
The Model 565 is ergonomic in design and fits well in the hand, facilitating one hand operation. The jaw size is compact yet designed to accommodate the most common conductors up to 1" (26mm) in diameter.
|
Models, Options, & Accessories
| Model |
Description |
List Price |
Sale Price |
| 2117.56 |
Clamp-On Leakage Current Meter Model 565 (TRMS, 100A, 600VAC/DC, Hz, Ohms, Continuity) |
$269.00
 |
| You may qualify for better pricing. |
| Please call 877-742-TEST (8378) |
| or Email for details. |
|
|
Specifications
| mA AC Current (TRMS, Auto-Ranging) |
| Measurement Range |
0 to 600mA |
Resolution 60mA 600mA
|
0.01mA (10μA) 0.1mA (100μA) |
Accuracy 50 to 60Hz 50 to 500Hz 500Hz to 3kHz |
1.2% of Reading ± 5cts 2.5% of Reading ± 5cts 3.5% of Reading ± 10cts |
| AC Current (TRMS, Auto-Ranging) |
| Measurement Range |
10 to 100A |
Resolution 10A 100A |
0.001A (1mA) 0.01A (10mA) |
Accuracy 50 to 60Hz 50 to 500Hz 500Hz to 3kHz |
1.2% of Reading ± 5cts 2.5% of Reading ± 5cts 3.5% of Reading ± 10cts |
| AC Voltage (TRMS) |
| Measurement Range |
0 to 600V |
| Resolution |
0.1V |
Accuracy 50 to 60Hz 50 to 500Hz 500Hz to 3kHz |
1.0% of Reading ± 5cts 1.2% of Reading ± 5cts 2.5% of Reading ± 10cts |
| DC Voltage |
| Measurement Range |
0 to 600V |
| Resolution |
0.1V |
| Accuracy |
1.0% of Reading ± 3cts |
| Frequency (Auto-Ranging) |
| Function |
A-Hz | V-Hz |
Resolution 0 to 100Hz 100Hz to 1kHz |
0.1Hz | 0.1Hz 1Hz | 1Hz |
| Sensitivity |
10mArms min | 5Vrms min |
| Accuracy |
0.5% of Reading ± 2cts |
| Resistance |
| Measurement Range |
0 to 1kΩ |
| Resolution |
0.1Ω |
| Accuracy |
1.0% of Reading ± 3cts |
| Continuity |
| Measurement Range |
0 to 1kΩ |
| Resolution |
0.1Ω |
| Buzzer |
<35Ω ±25Ω |
| Overload Protection |
660Vrms/150Arms |
| Nominal Sample Rate |
Two measurements per second (approx.) |
| MAX Sample Rate |
100ms |
| Filter |
On (50/60Hz only); Off (Full frequency range) |
| In-Rush |
Max 100ms sample time |
| Power Source |
Two 1.5V AAA batteries |
| Battery Life |
45 hrs (approx.) |
| Power-Off |
10 min approx with user override |
| Low Battery Indication |
is displayed when battery voltage is low |
| MECHANICAL |
| Dimensions |
8.5 x 2.5 x 1.18" (218 x 64 x 30mm) |
| Jaw Opening |
1.10" (28mm) |
| Maximum Conductor Size |
1" (26mm) |
| Weight |
10 oz (280g) with batteries |
| DISPLAY |
| Display Type |
Four digit LCD |
| Backlight |
LED with 180 sec Auto-Off |
| ENVIRONMENTAL |
| Operating Temperature |
32° to 104°F (0° to 40°C); <80% RH (non-condensing) |
| Storage Temperature |
14° to 140°F (-10° to 60°C); <70% RH (non-condensing) |
| SAFETY |
| Safety Rating |
EN 61010-1 Ed. 2001, EN 61010-2-032 Ed. 2003, 600V, Cat. III |
| Double Insulation |
Yes |
| CE Mark |
Yes |
|