AEMC 3910 2111.27 Power Meter

Click image to enlarge
AEMC 2111.27
|
|
Features:
- Simple, user-friendly operation
- True RMS measurements for distorted waveform environments
- Direct display of multiple measurements for easy readings
- Measures directly Arms, Vrms, PF, kW, kVar, kVA and Hz
- Peak and memory functions for load analysis
- Compact and rugged instrument complete with 500A clamp-on current probe
- Designed for everyday use - accurate and economical
- Built to IEC safety standards
|
Description
The auto-ranging, True RMS power meter is designed for today's electrical environments. Operation is simple. There are no programming requirements or menus, just four pushbuttons for direct access. The Model 3910 is also auto-ranging, and ensures the best range for measurements.
Troubleshooting and measuring power is done simply by connecting two voltage leads and clamping on the current probe. The Model 3910 performs current and voltage measurements in True RMS, and provides immediate readings of Power Factor (PF), Active Power (kW), Reactive Power (kVar), Apparent Power (kVA) and Frequency (Hz).
The Model 3910 is housed in a protective holster, and comes ready for field use with test leads, test probes, and 500AAC current probe in a rugged carrying case. A 1000A probe is optional.
|
Models, Options, & Accessories
| Model |
Description |
List Price |
Sale Price |
| 2111.27 |
TRMS Power Meter Model 3910 (Digital w/500A probe), Model 3910 - Discontinued - replaced by AEMC 8230 |
Specifications
| CURRENT TRUE RMS |
| INPUT RANGE |
1 to 500 Arms |
| TYPICAL ACCURACY (and Phase Shift) |
with 500 A Current Probe MD313: 25 A: 5%R (4°), 100 A: 2%R (2°), 500 A: 2%R (1.5°) |
| TYPICAL ACCURACY (and Phase Shift) |
with 1000 A Current Probe SD613: 50 A: ±0.9%R (1.5°), 200 A: ±0.5%R (0.5°), 1000 A: ±0.5%R (0.5°) |
| RESOLUTION |
1 to 9.99 A: 10 mA, 10.0 to 99.9 A: 100 mA, 100 A to 500 A: 1 A |
| VOLTAGE TRUE RMS |
| INPUT RANGE |
0 to 600 Vrms |
| ACCURACY |
1 to 99.9 V: 0.5% ±0.6 V, 100 to 600 V: 0.3% ±2 V |
| RESOLUTION |
0 to 99.9 V: 0.1 V, 100 to 600 V: 1 V |
| VOLTAGE DC |
VOLTAGE DC |
| INPUT RANGE |
0 to 600 V DC |
| FREQUENCY INPUT RANGE (from voltage input) |
30 to 100 Hz, 101 to 999 Hz |
| ACCURACY |
30 to 100 Hz: 0.03%R ± 0.1 Hz, 101 to 999 Hz: 0.5%R ± 1 Hz |
| POWER FACTOR |
POWER FACTOR |
| RANGE |
-0.00 (Lag) to +0.00 (Lead) ACCURACY: Sum of the V, A accuracy plus the probe phase shift |
| ACTIVE POWER RANGE |
0 to 300 kW (600 kW with SD613 probe) ACCURACY: Sum of the V and A accuracy |
| REACTIVE POWER RANGE |
0 to 300 kVar (600 kVar with SD613 probe) ACCURACY: Sum of the V and A accuracy @ Sin F = 1 |
| APPARENT POWER RANGE |
0 to 300 kVA (600 kVA with SD613 probe) ACCURACY: Sum of the V and A accuracy |
| GENERAL Specifications |
| DISPLAY |
40 x 50 mm multidisplay LCD |
| POWER |
Four 1.5 V ?AA? alkaline batteries |
| Low Battery Indicator |
?BAT? on display |
| BATTERY LIFE |
50 hours approx., continuous use |
| DIMENSIONS |
3.2 x 6.9 x 1.3" (80 x 175 x 32 mm) With yellow holster: 3.5 x 7.7 x 2.1" (90 x 195 x 54 mm) |
| WEIGHT |
With batteries: 15 oz (400 g) In yellow holster: 17.6 oz (500 g) |
| CURRENT PROBE |
Accommodates two 500 MCM or one 750 MCM |
| Safety Specification |
| PROTECTION LEVEL |
IEC 348 Class II |
| PROTECTION INDEX |
IP40 per IEC 529 |
| MAX. OVERLOAD |
VOLTAGE: 825 Vrms, 1170 V peak |
|