| Measurement Range |
| Type |
Ground Resistance Ranges |
| Range |
Autoranging 0.01 to 1200W |
| Measurement Range |
0.10 to 1.00W / 1.0 to 50.0W / 50.0 to 100.0W / 100 to 200W / 200 to 400W / 400 to 600W |
| Resolution |
0.01W / 0.1W / 0.5W / 1W / 5W / 10W |
| Accuracy in % of Reading |
± (2% Reading ± 0.02W ) / ± (1.5% Reading ± 0.1W ) / ± (2.0% Reading ± 0.5W ) / ± (3.0% Reading ± 1W ) / ± (6% Reading ± 5W ) / ± (10% Reading ± 10W ) |
| Resistance Measurement Frequency |
1.689kHz |
| Resistance Overload |
OL displayed above 1200W |
| Current Measurement Frequency |
47 to 800Hz |
| Current Overload |
OL displayed above 30Arms |
| Power Source |
9V Alkaline battery |
| Battery Life |
typical: 8 hours or approx. 1,000 measurements of 30 seconds |
| Mechanical Specifications |
| Display |
3-3/4 Digit, 1.73" x 1.10" (44 x 28mm) |
| Operating Temperature |
14° to 131°F (-10° to 55°C) |
| Storage Temperature |
40° to 158°F (-40°C to 70°C) |
| Relative Humidity |
0 to 90% RH @ 14 to 104°F (-10°C to 40°C), 75% RH @ 131°F (55°C) |
| Dimensions |
9.25 x 3.94 x 2.17" (235 x 100 x 55mm) |
| Weight |
2.2 lbs (1kg) |
| Jaw Window Diameter |
1.25" (32mm) |
| Jaw Opening |
1.38" (35m) |
| Case |
Lexan 920A (UL94V) |
| Colors |
Gray body, red jaws |
| Drop Test |
(1m); IEC 68-2-32 |
| Dielectric Test |
2500VAC |
| Environmental |
IP30, IEC 359 Group III |
| Working Voltage |
150V Cat. III - Pollution Degree 2 300V, Cat. II - Pollution Degree 1 |
| Max Overload (A or OHM Function) |
100A continuous, 200A (<5s) 50/60Hz |