AEMC 2620 2125.52 AC Leakage Current Probe

Click image to enlarge
AEMC 2125.52
|
|
Features:
- Very high sensitivity
- Differential or leakage current from 500μA
- Current up to 400A
- Two switch-selectable measurement ranges: 4AAC/400AAC
- Large inside jaw diameter (>4") allows use on large or multiple conductors
- Work with single-, dual- and three-phase networks
- Connect directly to DMMs on mV or VAC range
Applications:
- Preventive maintenance
- Equipment troubleshooting on electrical distribution systems
- High accuracy low-current measurements
- Measure fault currents on three-phase, three-wire systems
|
Description
The AC Leakage Current Probe Model 2620 measures leakage current shunted to ground caused by insulation faults. It enables the operator to locate failures when they occur, or anticipate them before they occur, without shutting down equipment or spending hours troubleshooting.
It is designed specifically for locating low current faults on high current loads. The detector is a sensitive nickel alloy AC current transformer capable of measuring differential or leakage current as low as 500μA. It may also be used to measure current up to 400A continuous duty.
Its 4” jaw opening facilitate both multiple and large conductors.
The Model 2620 may also be used as a highly accurate clamp-on current probe, providing a versatile way to analyze unbalanced current measurements, leakage values on grounding conductors and ground loop currents.
The Model 2620 has switch selectable ranges and is terminate with safety shrouded banana plugs on 5 ft leads, making it compatible with most multimeters.
|
Models, Options, & Accessories
| Model |
Description |
List Price |
Sale Price |
| 2125.52 |
Leakage Current Probe Model 2620 (4A-1V/A, 400A-1mV/A output) |
$499.00
 |
| You may qualify for better pricing. |
| Please call 877-742-TEST (8378) |
| or Email for details. |
|
|
Specifications
| ELECTRICAL - 4A Range |
| Current Range |
500μA to 4A |
| Output Signal |
1mV/mA (4V max) |
| Accuracy |
500μA to 10mA - 3% of Reading ± 1mV 10mA to 100mA - 0.5% of Reading ± 0.5mV 100mA to 4A - 0.5% of Reading ± 0.5mV |
| Phase Shift |
10mA to 100mA - <15° 100mA to 4A - <10° |
| Load Impedance (DMM) |
1MΩ min |
| Frequency Range |
48 to 1000Hz |
| Output Termination |
5 ft (1.5m) Lead with 4mm safety banana plugs |
| MECHANICAL |
| Dimensions |
11.22 x 6.89 x 1.77" (285 x 175 x 45mm) |
| Jaw Opening |
4.4" (112mm) |
| Maximum Conductor Size |
4.4" (112mm) |
| Weight |
2.87 lbs (1300g) |
| ENVIRONMENTAL |
| Operating Temperature |
-14° to 131°F (-10° to 55°C); 0 to 85% RH (non-condensing) |
| Storage Temperature |
-40° to 158°F (-40° to 70°C); 0 to 85% RH (non-condensing) |
| SAFETY |
| Safety Rating |
EN 61010-2-032, 600V Cat. III |
| Double Insulation |
Yes |
| CE Mark |
Yes |
|