AEMC 2610 1201.42 Megohmmeter 500V

Click image to enlarge
AEMC 1201.42
|
|
Features:
- Works on grounded single and three phase networks
- Works on high current circuits
- Extremely sensitive clamp-on ammeter measures as low as 500μAAC leakage on differential current
- Measures current to 200AAC
- Large aperture CT (3.1") clamps directly into conductors without interrupting service
- Locates fault by direct measurement of fault current
- Ideal for preventive maintenance - avoin shut-down time and costly failures
|
Description
The Ground Fault/Current Leakage Probe Model 2610 measures current shunted to ground caused by insulation faults. It enables location of failures when or before they occur, without equipment shutdown. It is designed specifically for locating low current faults on high current loads. It measures differential or leakage current from 500μA and may be used to measure currents up to 200A continuous duty (400A maximum).
The Model 2610 provides, on two ranges, 1mVAC/mAAC or 1mVAC/AAC. When the Model 2610 is used as a current leakage detector, it does not matter if the system is single-phase or polyphase, or if the currents are in-phase or out-of-phase, balanced or unbalanced.
The Model 2610 may be used simply as a highly accurate clamp-on current probe. With its 4" jaw opening and and range of 500μA to 200A, the Model 2610 provides a versatile way to analyze unbalanced current measurements, leakage values on grounding conductors and ground loop currents.
|
Models, Options, & Accessories
| Model |
Description |
List Price |
Sale Price |
| 1201.42 |
Current Leakage/Insulation Probe Model 2610 (4A-1mV/mA, 200A-1mV/A) - Discontinued - no replacement |
| Model |
Accessories |
List Price |
Sale Price |
| 2118.09 |
Case General Carrying Case |
$52.90
 |
| You may qualify for better pricing. |
| Please call 877-742-TEST (8378) |
| or Email for details. |
|
|
| 1017.45 |
Adapter 4mm Non-insulated for Safety Leads |
$15.50
 |
| You may qualify for better pricing. |
| Please call 877-742-TEST (8378) |
| or Email for details. |
|
|
Specifications
| Electrical |
| Nominal Range |
400A |
| Measurement Range |
500μA to 6A/500mA to 200A |
| Transformation Ratio |
Voltage output |
| Output Signal |
1mV/mA (400mV max @ 400A) |
| Accuracy (5A Range) |
500μA to 10mA ±3.0% of Reading + 1mA / 10mA to 4A ±0.5% of Reading + 0.5mA |
| Accuracy (200A Range) |
0.5 to 10A ±0.5% of Reading + 0.5mA / 10 to 200A ±0.5% of Reading + 0.5mA / 200 to 400A ±0.5% of Reading + 1mA |
| Overload |
Between 200A and 400A the max measurement time is 5 min., with 20 min. rest @ 25°C (77°F) or less |
| Frequency |
Range 10 to 1000Hz (100A max @ 1000Hz), 30Hz to 1kHz frequency limited to 100A to 1kHz |
| Load Impedance |
≥1mΩ min (5A); ≥1kΩ (200A) |
| Working/Common Mode Voltage |
600VAC |
| Output Termination |
5 ft Lead |
| Mechanical |
| Operating Temperature |
73.4° to 37.4°F (23° ± 3°C) |
| Storage Temperature |
-43° to 158°F (-40° to 70°C), between 10 and 90% humidity |
| Maximum Conductor Size |
3.94" (100mm) |
| Dimensions |
12.25 x 5.9 x 1.639" (31.1 x 15 x 4.1mm) |
| Weight |
4.4 lbs (2kg) |
| Polycarbonate Material |
Handles: UL94 VO; Jaws: UL94 V2 |
| Safety |
| Electrical |
Dielectric strength test: 2kVAC |
| Maximum work voltage |
600VAC |
| CE Mark |
Yes |
|